KITOZER Battery FAQ: Float Voltage Setting

Correct float voltage is the single most important parameter for VRLA battery service life. KITOZER recommends setting the UPS float charger to 2.25V to 2.27V per cell at 25 degrees Celsius for common AGM batteries. Every 8 degrees Celsius rise above 25 degrees halves expected battery life, so the charge voltage must be temperature compensated by minus 3mV per cell per degree. Measure each battery terminal with a calibrated multimeter quarterly and record the reading; any cell drifting more than 0.05V from the average should be flagged for replacement. Over-float causes grid corrosion and dry-out, while under-float leaves the pack chronically undercharged and leads to rapid capacity loss during outage events.

Table of Contents

Setting

2.25 to 2.27V per cell at 25 degrees, minus 3mV per degree above 25. KITOZER matched batteries from $55/pc.

Price

From $55/pc. Contact +86 13922289957 for battery pack quotation.