KITOZER Battery Internal Resistance Test Standard FAQ

This FAQ summarizes the internal resistance test standard used on KITOZER battery banks. A calibrated impedance meter should measure each block every six months, and the value must be compared with the baseline recorded at commissioning. A rise of more than 20 percent from baseline indicates an aging block; a rise of more than 40 percent is the threshold for replacement. Always test at float voltage, clean the post with a wire brush, and record temperature because resistance readings shift with temperature. Trend reports should be stored with the DCIM system so that predictive replacement can be planned before failure.

Thresholds

Warning 20 percent rise, replacement 40 percent rise over baseline. Battery impedance testers from $680.