Table of Contents
ToggleProduct Overview
KITOZER 48-channel battery internal resistance tester goes beyond simple voltage monitoring by measuring the internal resistance of each battery cell online, which is the most reliable indicator of VRLA battery health. The unit injects a low-amplitude AC test signal onto the charging string and measures the voltage response, computing internal resistance without disconnecting the battery. Rising internal resistance is the early warning of dry-out, grid corrosion, or soft short, typically appearing months before a visible voltage drop. The tester logs resistance trends per cell and alarms on abnormal values, supporting predictive battery replacement planning in UPS and substation DC systems.
Technical Specifications
48 cell channels, internal resistance measurement range 0.000mOhm to 3000mOhm, accuracy plus or minus 0.5 percent. Cell voltage range 0V to 3V, accuracy plus or minus 5mV. Temperature per channel optional up to 12 probes. String current via hall sensor. Main unit 7 inch color touchscreen. RS485 Modbus RTU, Ethernet Modbus TCP, Web HMI. Alarm relay outputs 8. Internal memory 1GB for one year of trends. Power supply 85V to 265VAC. Operating temperature 0C to plus 50C. CE, KITOZER brand, three year warranty.
Application Scenarios
This tester is used in large data center battery rooms with hundreds of VRLA cells, in utility substation DC systems, and in industrial UPS systems where battery failure during a power outage is unacceptable. It is also deployed in solar power plants and telecom central offices with long battery strings. The 48-channel unit covers a full 110V or 220V substation battery string in one device, and multiple units can be cascaded for larger UPS banks. Trend data supports capital planning by identifying which cells are approaching end of life before the next outage test.
Advantages and Features
Internal resistance is a far more sensitive health indicator than open-circuit voltage, which often looks normal until the cell is fully degraded. Online testing means the battery string stays on float charge during measurement, so no outage window is needed. Trend logging with Web HMI lets engineers compare resistance values across quarters and years. Alarm thresholds are programmable per cell, so a single weak cell triggers early warning without alarming the whole string. The tester also records conductance and voltage at the same time, supporting correlation analysis during failure investigation.
Installation and Maintenance
Mount the main unit in the battery room cabinet and run sense leads to each cell terminal. Use shielded twisted pair for resistance sense leads to avoid noise. Install the hall current sensor around the main battery cable. Set cell type, nominal voltage, and alarm thresholds through the touchscreen. Baseline the resistance values during commissioning and use those values as the reference for future trend comparisons. Maintenance includes annual sense-cable resistance check and calibration verification. Clean terminals if corrosion appears.
Price
From $1,280/pc. Contact +86 13922289957 for 48-channel resistance tester pricing.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com