KITOZER Battery Replacement Criteria FAQ

This FAQ lists the objective criteria that trigger battery replacement on a KITOZER battery system. Replace any block that shows case swelling, leakage, post corrosion, or vent activation. Replace any block whose internal resistance has risen more than 40 percent from baseline, or whose capacity discharge result is below 80 percent of rated. Also replace the whole string when the average block age reaches the design service life, typically 5 years for VRLA in a 25 C room. Always replace the full string rather than mixing old and new blocks, because mismatched aging causes premature failure of the newer blocks.

Replacement Triggers

Swelling, leakage, 40 percent resistance rise, 80 percent capacity, 5 year age. VRLA blocks from $45.