KITOZER battery replacement cycle FAQ explains when to replace valve-regulated lead-acid and lithium battery strings in UPS and energy storage systems. Waiting too long risks runtime collapse during an outage; replacing too early wastes budget.
Table of Contents
ToggleReplacement Criteria
Valve-regulated lead-acid: design life 5 years at 25 degrees C, usually replaced at 3-4 years in warm rooms. Lithium iron phosphate: 10-15 year design life, replaced when capacity falls below 80 percent. Test methods: monthly voltage float check, quarterly internal resistance test, annual discharge load test. Replacement trigger: any block more than 20 percent deviation from string average, or capacity below 80 percent of rated. Never mix old and new blocks in one string.
Price
From $120 per 12V 100Ah block. Contact +86 13922289957 for battery quote.