Busway (busbar trunking) is replacing traditional cable distribution in modern data centers because it allows tap-off units at any outlet along the run, making power reconfiguration fast and modular. KITOZER supplies plug-in busway from 100 A to 6300 A for UPS and generator feed applications.
Table of Contents
ToggleCapacity Selection
Begin with total downstream load plus future growth margin of 20 to 30 percent. Derate ampacity for ambient temperature above 35 degrees Celsius and for enclosure type (IP54 versus IP30). Calculate voltage drop along the run, keeping it below 2 percent at full load for long horizontal busway. Choose tap-off unit ratings (30 A, 60 A, 125 A, 250 A) matching PDU or rack power demands. Verify short-circuit withstand rating (Icw) exceeds available fault current from upstream switchgear.
Installation Notes
Maintain bending radius per manufacturer instructions. Use expansion joints for long runs above 30 meters. Maintain separation from cooling pipes and cable trays. KITOZER busway includes tap-off units with molded case switches and optional meter modules for per-outlet energy monitoring.