KITOZER Busway FAQ: Infrared Thermography Inspection Cycle

Busway joints and tap-off boxes develop hot spots from loose torque and oxidization. KITOZER recommends IR thermographic inspection every 12 months on energized busway under at least 30 percent load. Best practice is quarterly for main switchgear bus and semi-annual for sub-distribution bus. Use a resolution of at least 320×240 detector and emissivity set to 0.95 on painted surfaces. Flag any joint 15C above ambient or 10C above adjacent phases for immediate retorque under outage. Store radiometric images against the as-built drawing number.

Table of Contents

Safety Rules

Only qualified electricians open tap-off covers, always wear arc-flash suit rated for the available fault current, and keep clear the working clearance. KITOZER busway covers include inspection windows on premium models.

Price

From $2,200 per day IR inspection crew. Contact +86 13922289957 for thermography schedule.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com