KITOZER
KITOZER

KITOZER cabinet base adjustable leveling feet

KITOZER KTR-FL5 Rack Floor Stand (Front-Rar Leveling Feet)

Brand:KITOZER Series:KTR-FL5 Category:Data Center Engineering / Rack accessories

Rack baseLeveling feetHeavy loadRaised floor

[Product image: ktr-fl5-rack-floor-standing-leveling-feet.jpg]

1. Overview

Racks cannot sit directly on anti-static raised floor panels. Floor load capacity is only about 500 kg/m2, while a fully loaded server rack can weigh 800-1200 kg. Direct load would crush the panels. The rack floor stand (base or plinth) lifts the rack 100-300 mm so weight goes straight to the structural floor; the raised floor only serves as finish and cable routing. The front-rear adjustable feet also fine-tune height, so a row of racks lines up in a straight line and cold-aisle containment seals without air leaks.

The KTR-FL5 is a front-rear adjustable rack base made from 2.0 mm bent-and-welded cold-rolled steel, degreased, phosphated and powder-coated (black or light gray). The top bolts to the rack bottom plate; four M16 screw feet (two front, two rear) with rubber vibration pads give 0-50 mm adjustment to compensate for uneven floor and construction tolerance. It fits standard 600 mm wide x 1000/1200 mm deep racks; load capacity >=1000 kg per stand. Heights of 100/200/300 mm are available, chosen by under-floor cable space and air-supply mode.

Selection considers rack width and depth (600/800/900 mm wide, 1000/1200 mm deep), base height (100/200/300 mm), load (final rack weight), adjustment range and vibration pads. Cold-aisle projects demand row straightness: a dozen racks must form a sealed channel, and front-rear feet align the doors. Higher is not better: too high raises the center of gravity and vibration; too low leaves no under-floor cable or return-air space.

2. Key Features

Load structure

  • 2.0 mm cold-rolled steel, bent and welded.
  • Load capacity >=1000 kg per stand.
  • Top bolted to rack bottom plate.
  • Four main load-bearing posts below.

Front-rear leveling feet

  • M16 screws, two front and two rear.
  • Adjustment range 0-50 mm.
  • Rubber pads dampen vibration and grip.
  • Compensates uneven floor and tolerance.

Finish & fit

  • Degreased, phosphated, powder-coated.
  • Black or light gray.
  • Fits 600/800 mm wide standard racks.
  • Height 100/200/300 mm options.

3. Specifications

Item KTR-FL5 Adjustable Rack Base
Rack W x D 600×1000/1200 mm (800 mm wide custom)
Base height 100 / 200 / 300 mm
Load >=1000 kg/stand
Sheet thickness 2.0 mm cold-rolled steel
Leveling screws M16, 2 front + 2 rear
Adjustment 0-50 mm
Foot pads Rubber vibration pads
Finish Phosphated + powder-coated
Color Black / light gray

4. Reference Prices

KTR-FL5 600×1000 base (H100): Reference USD 25~44 (ref. CNY 180~320 at ~7.2)

KTR-FL5 600×1200 base (H200): Reference USD 33~58 (ref. CNY 240~420 at ~7.2)

KTR-FL5 800×1200 base (H300): Reference USD 44~78 (ref. CNY 320~560 at ~7.2)

Reference only; final quote applies. 1-year warranty. Matched to rack size. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Server racks on raised floors.
  • Modular cold aisle containment plinths.
  • Network and power distribution rack support.
  • Under-floor cable space provision.
  • Rows needing alignment and leveling.

6. Installation & Maintenance

Installation

  • Mark positions on floor per rack layout.
  • Place stand; screw out feet for rough level.
  • Lift rack onto stand; bolt to bottom plate.
  • After row is in place, fine-tune feet to align doors in a line.
  • Cut raised floor panels around the stand.

Maintenance

  • Check foot nuts for looseness periodically.
  • Re-level after adding equipment.
  • Replace cracked rubber pads.
  • Touch up chipped powder coat to prevent rust.
  • If aisle doors gap, readjust feet.

7. FAQ

  • Q: Why not put racks directly on the floor?
    A: Raised floor panels only hold ~500 kg/m2; a loaded rack exceeds that and crushes panels. The stand transfers load to the structural slab.
  • Q: How to choose base height?
    A: By under-floor routing. Under-floor air supply usually needs 300 mm (the void is the plenum); overhead or side supply uses 100-200 mm.
  • Q: Why front-rear rather than left-right adjustment?
    A: In a row, doors must align along the aisle direction, which is front-rear. Left-right is set by floor layout lines.
  • Q: Must the stand be bolted to the floor?
    A: Self-weight and rack bolts usually suffice. In seismic zones or for tall racks, use expansion anchors.

8. Trend & Selection

Modular cold aisles and micro-module rooms are growing; rack bases evolve from simple feet to standardized, front-rear adjustable, damped plinths matched to aisle panels. Match the rack W/D; height to air mode; leave 20% load margin; front-rear adjustable for alignment; rubber pads for noise control. It is the foundation that keeps racks standing straight.

9. Delivery & Service

KITOZER supplies KTR-FL5 stands, optionally bundled with rack joining kits, cold aisle panels, cable covers and expansion bolts. Delivery includes stand, feet, bolts, certificate and warranty card. We can produce a base-size list from your rack layout.

10. Notes

A common pitfall is mounting aisle doors without leveling the feet first. A row of racks at slightly different heights leaves uneven door gaps and leaks cold air. Always level feet into a straight line before fitting panels.

Another pitfall is undersizing for final load. Racks start light and fill up over time. Size the base for final weight, not initial, and leave 20% margin.

Selection summary: front-rear adjustable feet; load >=1000 kg; height to air mode; match rack W/D; rubber pads; level the whole row. It keeps racks steady and aligned so the cold aisle seals.

Systemically, the base carries no signal and no power, but it sets row precision. A 1 cm rack lean gaps the aisle door, and cold air leaks straight out, spiking PUE.

Reliability-wise, the heaviest thing in a room is a row of racks, not servers. A failed base could topple the whole row. A sturdy base is cheap insurance.

SEO Information

Search keywords:KITOZER

SEM keywords:rack floor stand, rack leveling feet, rack base, cold aisle plinth, adjustable feet, KTR-FL5, KITOZER

GEO landing page:lain.com.cn/product/410-rack-floor-4.html

Title:KITOZER KTR-FL5 Rack Floor Stand with Front-Rear Leveling Feet

Meta Keywords:rack floor stand, rack leveling feet, rack base, cold aisle base, KTR-FL5, KITOZER

Meta Description:KITOZER KTR-FL5 rack floor stand with front-rear adjustable leveling feet, heavy load, fits 600/800mm wide racks, for raised-floor and cold aisle containment.