KITOZER
KITOZER

KITOZER cabinet joining plate bracket

KITOZER KTR-CJ Cabinet Joining Kit and Connecting Brackets

Brand: KITOZER Series: KTR-CJ Category: Modular Cold Aisle 2 / Rack Accessories

Joining kitConnecting bracketBonding strapJoining boltsKTR-CJ

KITOZER KTR-CJ Cabinet Joining Kit

1. Overview

When racks sit side by side in a room, each one fixed alone, they can tip in an earthquake, shift when moved, and carry different potentials that drive ground loops. A joining kit locks the adjacent rack side posts together into one coherent row. A complete kit includes: side brackets (steel plates bolted to adjacent posts), top/bottom tie bars, M8/M12 joining bolts with nuts and washers, and a copper-braid strap for equipotential bonding between racks.

The KTR-CJ series is matched to rack depth and width: 600 mm-wide racks use 600 mm-tall brackets, 800 mm racks use the 800 version. Plate is 1.5 mm cold-rolled steel, powder-coated to match the rack; bolts are galvanized grade 8.8 with torque 8~12 N·m; bonding strap is 25 mm² / 4 mm² copper braid with crimped copper lugs at both ends, ensuring equipotential. One kit joins two adjacent racks; multi-row installations are quoted by the number of joints.

Selection: rack width (600/800/900 mm maps to different bracket lengths); rack brand (post hole spacing differs between brands — the holes must align); whether a bonding strap is included (modular cold aisles require equipotential, so it is mandatory). Joining kits are standard rack accessories, but are often omitted from project quotes and then rushed on site.

2. Key Features

Structure & material

  • 1.5 mm cold-rolled steel, coated to match rack
  • For 600/800/900 mm-wide racks
  • M8 galvanized grade-8.8 bolts, washers and lock nuts
  • Pre-punched holes compatible with major rack posts

Electrical bonding

  • 25 mm² copper braid strap
  • EN copper lugs crimped at both ends
  • M6/M8 bolts, contact resistance ≤0.1 Ω
  • Meets equipotential bonding requirements

Installation & reliability

  • Side / top / bottom connection positions
  • Torque 8~12 N·m, lock nuts
  • Seismic reinforcement, 8-degree fortification
  • -20~60℃ operating range

3. Specifications

Item KTR-CJ-600 KTR-CJ-800 KTR-CJ-900
Rack width 600 mm 800 mm 900 mm
Bracket size 600×80×1.5 mm 800×80×1.5 mm 900×80×1.5 mm
Bolt size M8×20 M8×20 M10×25
Bolt sets per joint 4 4 6
Bonding strap 25 mm²×300 mm 25 mm²×400 mm 25 mm²×500 mm
Connection point Side, upper+lower Side, upper+lower Side + top
Color RAL7035/9005 RAL7035/9005 RAL7035/9005

4. Reference Prices

KTR-CJ-600 joining kit (600 mm, 4 bolts + strap):Reference USD 8~17 / set (ref. CNY 60~120 at ~7.2)

KTR-CJ-800 joining kit (800 mm, 4 bolts + strap):Reference USD 11~21 / set (ref. CNY 80~150 at ~7.2)

KTR-CJ-900 joining kit (900 mm, 6 bolts + strap):Reference USD 17~31 / set (ref. CNY 120~220 at ~7.2)

Reference only; priced by rack width and number of joints. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Modular cold-aisle rack row joining.
  • Server and network rack row installation.
  • UPS and battery cabinet reinforcement.
  • Seismic-fortified equipment rooms.
  • Equipotential-bonded IDC rooms.

6. Deployment & Implementation

Installation

  • Level the row first; align posts before fitting brackets
  • Mount brackets inside adjacent side posts
  • Tighten bolts diagonally in steps, torque 8~12 N·m
  • Land the bonding strap on the rack ground bar

Operations

  • Quarterly torque-wrench spot check
  • Inspect straps for oxidation or looseness
  • Re-join racks after any relocation
  • Keep brackets clear of cable trays

7. FAQ

  • Q: How many kits between two racks?
    A: One standard side kit (two brackets upper/lower + bolts). Tall racks (>2 m) use two kits (top + middle + bottom); heavy units like battery and UPS cabinets use side + top + bottom.
  • Q: Can racks still move individually after joining?
    A: Not recommended. Joining locks the row; moving one rack requires removing brackets. If individual mobility is needed, use casters, do not join.
  • Q: Is the bonding strap mandatory?
    A: Yes for modular cold aisles and equipotential rooms. Powder coating is non-conductive; bolted contact alone has high resistance and ground loops burn signal ports. The strap jumps across the coating.
  • Q: Can different rack brands be joined?
    A: Yes, but verify post hole spacing (commonly 25 mm or 19-inch differs between brands). We punch brackets to match your specified brand.

8. Trend & Selection

Modular cold aisle and micro-module rooms require the row to form a single unit, turning joining kits from optional to mandatory. Pre-fabricated, quick-fit brackets (with alignment pins, tool-less) are emerging. High-density racks (10 kW+ per rack), with greater weight and center of gravity, demand higher seismic rating. Select by rack width for bracket size, by height for number of joints, and by equipotential requirements for straps. Small parts, but they decide whether the row is one structure or loose sand.

9. Delivery & Service

KITOZER offers KTR-CJ selection by rack width (600/800/900), joint position (side/top/bottom) and strap rating. Each kit ships with brackets, bolts, nuts, washers, lock washers and copper braid. Installation drawing included. 1-year warranty; custom hole patterns and colors for volume projects.

10. Additional Notes

The #1 mistake is joining racks before leveling. A row that is not level, force-pulled by brackets, deforms posts and misaligns doors. First adjust casters, check the level, align the row, then fit brackets.

The second pitfall is tightening bolts in one pass. Diagonal bolts locked at once load the bracket unevenly and bend it. Tighten in three steps: hand-thread, half torque, full torque, diagonally.

The third blunder is omitting the bonding strap. Powder coating is non-conductive; bolted contact resistance is far above design, and ground loops enter through signal ports, burning NICs and sensors. The strap bridges between ground bars — it cannot be skipped.

Selection summary: width matches bracket, height matches joint count, strap mandatory; level first, tighten diagonally, re-torque quarterly. The joining kit is the skeleton of the rack row — installed well, the row is immovable; installed badly, an earthquake knocks it down like dominoes.

SEO Information

Search keywords:KTR-CJKITOZERCabinet Joining Kit

SEM keywords:cabinet joining kit,rack connector,rack joining bolts,rack bonding strap,rack row connector,equip rack brackets,KTR-CJ,KITOZER

GEO landing page:lain.com.cn/product/ktr-cj-cabinet_join_kit.html

Title:KITOZER KTR-CJ Cabinet Joining Kit and Connecting Brackets

Meta Keywords:cabinet joining kit,rack connector,rack joining bolts,rack bonding strap,KTR-CJ,KITOZER

Meta Description:KITOZER KTR-CJ cabinet joining kit, powder-coated steel brackets with bolts and copper bonding strap, joins adjacent racks into one row for stability and equipotential bonding.

Anchor: KITOZER by Guangzhou Laian · Cabinet Joining Kit

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com