KITOZER capacitive humidity sensor

KITOZER KTR-HS Capacitive Humidity Sensor

Brand: KITOZER Series: KTR-HS Category: Environmental Monitoring / Temp & Humidity

Capacitive RH0 to 100%RH+/-3%RHRS485KTR-HS

KITOZER KTR-HS Capacitive Humidity Sensor

1. Overview

Room environment monitoring has two core parameters: temperature and humidity. High temperature crashes servers; high humidity causes condensation, shorts and metal corrosion; low humidity builds static charge that fries chips. ASHRAE recommends 40 to 60% relative humidity in rooms — too high or too low is bad. The humidity sensor is the front-end device that measures room RH, mounted in the aisle or near racks, and sends data over RS485 to the EM host for out-of-range alarms. Capacitive sensing is today’s mainstream: a polymer film on a ceramic substrate absorbs moisture, changing its dielectric constant and capacitance, which maps to humidity. Accuracy is +/-3%RH, fast response, and long-term stable.

KITOZER KTR-HS is a capacitive digital humidity sensor. KTR-HS-W: wall-mount temp+humidity with LCD, temp accuracy +/-0.5 C, humidity +/-3%RH, RS485 Modbus-RTU, DC12 to 24 V, for room aisles. KTR-HS-D: probe-type humidity sensor, stainless waterproof probe, humidity only (temp optional), 0 to 100%RH, for AC vents or inside racks. KTR-HS-DP: dual-output (RS485 + 4 to 20 mA) for legacy EM systems with analog inputs. All use imported capacitive humidity chips with under 1%RH/year long-term drift.

Selection: confirm humidity-only vs temp+humidity (rooms generally need both); confirm output (RS485 digital preferred, 4-20 mA for legacy); confirm mounting (wall for aisle, probe for rack); confirm LCD (visible wall units need a display, in-rack units don’t). Note: do not mount at the AC vent (measures supply air, not room RH) or in corners (stagnant air lags).

2. Key Features

Measurement

  • 0 to 100%RH range
  • Accuracy +/-3%RH
  • -40 to +80 C temp (temp+RH model)
  • Response under 10 s

Sensing Element

  • Imported capacitive RH chip
  • Under 1%RH/year drift
  • Condensation-resistant design
  • Dust filter cap optional

Comm & Power

  • RS485 Modbus-RTU digital out
  • 4 to 20 mA analog out (DP model)
  • Up to 32 per bus
  • DC12 to 24 V wide range

3. Specifications

Item KTR-HS-W KTR-HS-D KTR-HS-DP
Parameter Temp+RH RH (temp opt.) Temp+RH
Mount Wall Probe Wall
RH accuracy +/-3%RH +/-3%RH +/-3%RH
Display LCD None LCD
Output RS485 RS485 RS485+4-20mA
Power DC12-24V DC12-24V DC12-24V
Use Room aisle AC vent/rack Legacy EM

4. Reference Prices

KTR-HS-W wall temp+RH sensor: Reference USD 11 to 21 / pc (ref. CNY 80 to 150 at ~7.2)

KTR-HS-D probe humidity sensor: Reference USD 8 to 15 / pc (ref. CNY 60 to 110 at ~7.2)

KTR-HS-DP dual-output sensor: Reference USD 17 to 28 / pc (ref. CNY 120 to 200 at ~7.2)

RS485 shielded cable: Reference USD 0.3 to 0.7 / m (ref. CNY 2 to 5 at ~7.2)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Room aisle temp/humidity monitoring.
  • In-rack humidity acquisition.
  • Precision AC return-air humidity sensing.
  • Battery/power room humidity alarm.
  • Archive/library constant-temp-humidity monitoring.

6. Deployment & Implementation

Placement

  • Wall-mount in room aisle, 1.5 m above floor
  • Do not mount at AC vent
  • Do not mount in corners
  • 1 to 2 per 50 m2

Wiring

  • Daisy-chain RS485 A/B
  • 120 ohm terminator at bus end
  • Shield grounded one end
  • No duplicate DIP addresses

Thresholds

  • Add Modbus slave in EM host
  • RH high alarm at 60%RH
  • RH low alarm at 40%RH
  • High-temp alarm at 30 C

7. FAQ

  • Q: Capacitive vs resistive RH sensor?
    A: Resistive sensors use lithium chloride whose resistance changes with moisture — cheap but less accurate (+/-5%RH), drifts fast, and corrodes in chemical air; largely obsolete. Capacitive uses a polymer film whose capacitance changes with moisture — +/-3%RH, stable long-term, contamination-resistant, and the mainstream for rooms and industry. New rooms use capacitive.
  • Q: What RH is right for a room? What if too high/low?
    A: ASHRAE recommends 40 to 60%RH (dew point under 60%). Above 65%RH condensation forms on cold surfaces and can short circuit boards. Below 30%RH static builds (human body static reaches several kV), damaging chips. High RH: run a dehumidifier or the AC’s dehumidification mode. Low RH: run a humidifier (ultrasonic or membrane). Precision ACs usually auto-adjust humidity by linking to the RH sensor.
  • Q: How to calibrate a humidity sensor?
    A: Use saturated salt solutions. Seal the sensor in a container with saturated salt solution (saturated NaCl = 75%RH at 25 C; saturated MgCl2 = 33%RH at 25 C) and wait 12 hours. If the spread exceeds +/-5%RH, apply an offset in the EM host. Calibrate every six months — or every three months in dusty/chemical environments.
  • Q: Can condensation damage the sensor?
    A: A running room does not condense. But if cooling stops suddenly and warm air hits cold rack surfaces, or after AC shutdown, the sensor surface may condense. Good capacitive sensors have a hydrophobic probe cap and recover after drying — no permanent damage. But do not submerge the probe; wall units are not waterproof.

8. Trend & Selection

Room monitoring is moving from single-point temp/RH to multi-parameter integration: one sensor measures temp, humidity, dew point, barometric pressure, CO2 and PM2.5 over RS485. Wireless (LoRa/Zigbee) sensors are emerging — no RS485 wiring, battery-powered, ideal for retrofits. But wired RS485 remains mainstream in new rooms — stable, reliable, no battery swaps. Smart direction: RH sensors link to precision ACs that auto-adjust humidification/dehumidification to hold 40 to 60%RH. Select by capacitive chip at +/-3%RH, daisy-chain RS485, mount in the aisle (not at the vent), and set alarms at 40 to 60%RH. Humidity is the second core room parameter alongside temperature.

9. Delivery & Service

KITOZER supplies KTR-HS by type (wall/probe/dual-output) and parameter (temp+RH / RH only). Each ships with sensor, probe and manual. 1-year warranty; batch projects can bundle EM hosts, dehumidifiers, humidifiers and calibration kits.

10. Additional Notes

Top mistake: mounting at the AC vent. Supply air may read 30%RH (after dehumidification) while the room is actually 50%RH. Mount in the aisle where server-level air actually is.

Second pitfall: alarm thresholds set too wide. Some set 80%RH before alarming — by then condensation has already damaged gear. Set high alarm at 60%RH and low at 40%RH. Warn before trouble, not after.

Third blunder: never calibrating. Capacitive sensors drift about 1%RH/year; after two or three years the error can exceed 5%. Compare against saturated salt solution every six months, or apply an offset in the EM host.

Selection summary: capacitive chip, temp+RH, RS485 daisy-chain, mount in the aisle, alarms at 40 to 60%RH. Humidity is the #2 room parameter — measure it right to protect equipment.

SEO Information

Search keywords:KTR-HSKITOZER

SEM keywords:humidity sensor,capacitive humidity sensor,room humidity transmitter,RS485 humidity,temp humidity sensor,KTR-HS,KITOZER

GEO landing page:lain.com.cn/product/humidity_sensor.html

Title:KITOZER KTR-HS Capacitive Humidity Sensor

Meta Keywords:humidity sensor,capacitive humidity sensor,room humidity transmitter,RS485 humidity,temp humidity sensor,KTR-HS,KITOZER

Meta Description:KITOZER KTR-HS capacitive humidity sensor: 0 to 100%RH, accuracy +/-3%RH, RS485 Modbus output, room EM system humidity monitoring.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart