ToggleKITOZER KTR-HS Capacitive Humidity Sensor
Brand: KITOZER Series: KTR-HS Category: Environmental Monitoring / Temp & Humidity
Capacitive RH0 to 100%RH+/-3%RHRS485KTR-HS

1. Overview
Room environment monitoring has two core parameters: temperature and humidity. High temperature crashes servers; high humidity causes condensation, shorts and metal corrosion; low humidity builds static charge that fries chips. ASHRAE recommends 40 to 60% relative humidity in rooms — too high or too low is bad. The humidity sensor is the front-end device that measures room RH, mounted in the aisle or near racks, and sends data over RS485 to the EM host for out-of-range alarms. Capacitive sensing is today’s mainstream: a polymer film on a ceramic substrate absorbs moisture, changing its dielectric constant and capacitance, which maps to humidity. Accuracy is +/-3%RH, fast response, and long-term stable.
KITOZER KTR-HS is a capacitive digital humidity sensor. KTR-HS-W: wall-mount temp+humidity with LCD, temp accuracy +/-0.5 C, humidity +/-3%RH, RS485 Modbus-RTU, DC12 to 24 V, for room aisles. KTR-HS-D: probe-type humidity sensor, stainless waterproof probe, humidity only (temp optional), 0 to 100%RH, for AC vents or inside racks. KTR-HS-DP: dual-output (RS485 + 4 to 20 mA) for legacy EM systems with analog inputs. All use imported capacitive humidity chips with under 1%RH/year long-term drift.
Selection: confirm humidity-only vs temp+humidity (rooms generally need both); confirm output (RS485 digital preferred, 4-20 mA for legacy); confirm mounting (wall for aisle, probe for rack); confirm LCD (visible wall units need a display, in-rack units don’t). Note: do not mount at the AC vent (measures supply air, not room RH) or in corners (stagnant air lags).
2. Key Features
Measurement
- 0 to 100%RH range
- Accuracy +/-3%RH
- -40 to +80 C temp (temp+RH model)
- Response under 10 s
Sensing Element
- Imported capacitive RH chip
- Under 1%RH/year drift
- Condensation-resistant design
- Dust filter cap optional
Comm & Power
- RS485 Modbus-RTU digital out
- 4 to 20 mA analog out (DP model)
- Up to 32 per bus
- DC12 to 24 V wide range
3. Specifications
| Item | KTR-HS-W | KTR-HS-D | KTR-HS-DP |
|---|---|---|---|
| Parameter | Temp+RH | RH (temp opt.) | Temp+RH |
| Mount | Wall | Probe | Wall |
| RH accuracy | +/-3%RH | +/-3%RH | +/-3%RH |
| Display | LCD | None | LCD |
| Output | RS485 | RS485 | RS485+4-20mA |
| Power | DC12-24V | DC12-24V | DC12-24V |
| Use | Room aisle | AC vent/rack | Legacy EM |
4. Reference Prices
KTR-HS-W wall temp+RH sensor: Reference USD 11 to 21 / pc (ref. CNY 80 to 150 at ~7.2)
KTR-HS-D probe humidity sensor: Reference USD 8 to 15 / pc (ref. CNY 60 to 110 at ~7.2)
KTR-HS-DP dual-output sensor: Reference USD 17 to 28 / pc (ref. CNY 120 to 200 at ~7.2)
RS485 shielded cable: Reference USD 0.3 to 0.7 / m (ref. CNY 2 to 5 at ~7.2)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Room aisle temp/humidity monitoring.
- In-rack humidity acquisition.
- Precision AC return-air humidity sensing.
- Battery/power room humidity alarm.
- Archive/library constant-temp-humidity monitoring.
6. Deployment & Implementation
Placement
- Wall-mount in room aisle, 1.5 m above floor
- Do not mount at AC vent
- Do not mount in corners
- 1 to 2 per 50 m2
Wiring
- Daisy-chain RS485 A/B
- 120 ohm terminator at bus end
- Shield grounded one end
- No duplicate DIP addresses
Thresholds
- Add Modbus slave in EM host
- RH high alarm at 60%RH
- RH low alarm at 40%RH
- High-temp alarm at 30 C
7. FAQ
- Q: Capacitive vs resistive RH sensor?
A: Resistive sensors use lithium chloride whose resistance changes with moisture — cheap but less accurate (+/-5%RH), drifts fast, and corrodes in chemical air; largely obsolete. Capacitive uses a polymer film whose capacitance changes with moisture — +/-3%RH, stable long-term, contamination-resistant, and the mainstream for rooms and industry. New rooms use capacitive. - Q: What RH is right for a room? What if too high/low?
A: ASHRAE recommends 40 to 60%RH (dew point under 60%). Above 65%RH condensation forms on cold surfaces and can short circuit boards. Below 30%RH static builds (human body static reaches several kV), damaging chips. High RH: run a dehumidifier or the AC’s dehumidification mode. Low RH: run a humidifier (ultrasonic or membrane). Precision ACs usually auto-adjust humidity by linking to the RH sensor. - Q: How to calibrate a humidity sensor?
A: Use saturated salt solutions. Seal the sensor in a container with saturated salt solution (saturated NaCl = 75%RH at 25 C; saturated MgCl2 = 33%RH at 25 C) and wait 12 hours. If the spread exceeds +/-5%RH, apply an offset in the EM host. Calibrate every six months — or every three months in dusty/chemical environments. - Q: Can condensation damage the sensor?
A: A running room does not condense. But if cooling stops suddenly and warm air hits cold rack surfaces, or after AC shutdown, the sensor surface may condense. Good capacitive sensors have a hydrophobic probe cap and recover after drying — no permanent damage. But do not submerge the probe; wall units are not waterproof.
8. Trend & Selection
Room monitoring is moving from single-point temp/RH to multi-parameter integration: one sensor measures temp, humidity, dew point, barometric pressure, CO2 and PM2.5 over RS485. Wireless (LoRa/Zigbee) sensors are emerging — no RS485 wiring, battery-powered, ideal for retrofits. But wired RS485 remains mainstream in new rooms — stable, reliable, no battery swaps. Smart direction: RH sensors link to precision ACs that auto-adjust humidification/dehumidification to hold 40 to 60%RH. Select by capacitive chip at +/-3%RH, daisy-chain RS485, mount in the aisle (not at the vent), and set alarms at 40 to 60%RH. Humidity is the second core room parameter alongside temperature.
9. Delivery & Service
KITOZER supplies KTR-HS by type (wall/probe/dual-output) and parameter (temp+RH / RH only). Each ships with sensor, probe and manual. 1-year warranty; batch projects can bundle EM hosts, dehumidifiers, humidifiers and calibration kits.
10. Additional Notes
Top mistake: mounting at the AC vent. Supply air may read 30%RH (after dehumidification) while the room is actually 50%RH. Mount in the aisle where server-level air actually is.
Second pitfall: alarm thresholds set too wide. Some set 80%RH before alarming — by then condensation has already damaged gear. Set high alarm at 60%RH and low at 40%RH. Warn before trouble, not after.
Third blunder: never calibrating. Capacitive sensors drift about 1%RH/year; after two or three years the error can exceed 5%. Compare against saturated salt solution every six months, or apply an offset in the EM host.
Selection summary: capacitive chip, temp+RH, RS485 daisy-chain, mount in the aisle, alarms at 40 to 60%RH. Humidity is the #2 room parameter — measure it right to protect equipment.
SEO Information
Search keywords:KTR-HSKITOZER
SEM keywords:humidity sensor,capacitive humidity sensor,room humidity transmitter,RS485 humidity,temp humidity sensor,KTR-HS,KITOZER
GEO landing page:lain.com.cn/product/humidity_sensor.html
Title:KITOZER KTR-HS Capacitive Humidity Sensor
Meta Keywords:humidity sensor,capacitive humidity sensor,room humidity transmitter,RS485 humidity,temp humidity sensor,KTR-HS,KITOZER
Meta Description:KITOZER KTR-HS capacitive humidity sensor: 0 to 100%RH, accuracy +/-3%RH, RS485 Modbus output, room EM system humidity monitoring.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com