KITOZER CDU dual-stage filtration unit protects cold plate micro-channels from particulates in the secondary loop. The first stage uses a 100 mesh mesh screen capturing large debris from commissioning, while the second stage employs a 40 micron spun filter polishing the loop during operation. A differential pressure switch across the filter housing triggers a maintenance alarm before pressure drop affects pump performance, extending coolant service intervals.
Table of Contents
ToggleSpecifications
CE, 100 mesh plus 40 micron dual stage, stainless steel housing, EPDM seals, working pressure 10 bar, differential pressure switch 0.5 bar, ball valve isolation, drain port, water-glycol compatible, KITOZER, 5 year warranty.
Price
From $680/pc. Contact +86 13922289957 for filtration pricing.