KITOZER Chilled Water Pump 100m3/h Centrifugal End Suction

The KITOZER 100 m3 per hour end suction centrifugal pump is designed as the workhorse of chilled water secondary loops in commercial HVAC systems, small data center cooling loops, and industrial process water circulation. With a closed impeller and mechanical seal, the pump delivers stable flow with low vibration and quiet operation. The integrated motor meets IE3 premium efficiency, and the pump and motor are mounted on a common cast iron baseplate for alignment precision. It is available with either fixed speed or inverter duty motor, and can be supplied with a variable frequency drive for flow modulation.

Product Overview

KITOZER end suction pumps use a back pull out design, allowing mechanical seal and bearing inspection without removing the pump casing or disconnecting piping. The wet end is cast iron with bronze impeller for long service life in closed water loops. Single mechanical seal with ceramic silicon carbide faces is standard, with double mechanical seal available for open loop or high temperature applications. A drain plug and vent plug are included on the casing. Flanged inlet and outlet comply with PN16 standard for direct mounting to standard HVAC piping flanges.

Technical Specifications

Rated flow 100 m3 per h, rated head 32 m. Pump speed 2900 rpm. Motor power 15 kW, IE3 efficiency, 3 phase 380 V 50 Hz. NPSH required 4.5 m. Inlet flange DN125, outlet flange DN100, PN16. Maximum working pressure 16 bar. Maximum liquid temperature 120 C. Mechanical seal single spring type. Weight 280 kg. Standard materials: casing HT250 cast iron, impeller bronze, shaft 45 carbon steel with stainless sleeve. ISO 9906 grade 2 hydraulic performance tolerance. CE certified, 2 year warranty.

Application Scenarios

This pump is typically installed as a secondary chilled water circulation pump serving fan coil units and air handling units in office buildings, hotels, hospitals, and shopping malls. It also works as a condenser water pump in small chiller plants, a process water pump in manufacturing, and a solar thermal loop circulation pump. When installed in a variable volume system, pairing with a VFD controlled by differential pressure sensors on the farthest circuit reduces pump energy by 30 to 50 percent compared with constant speed operation. Twin pump standby configuration is recommended for mission critical systems.

Advantages and Features

The optimized hydraulic impeller offers high efficiency at duty point and a wide stable operating range. The back pull out design minimizes maintenance downtime. IE3 motor reduces electricity consumption across the 8000 hours per year typical of HVAC operation. Casing foot design absorbs piping loads, reducing stress on mechanical seals. Optional baseplate mounted spring vibration isolators further attenuate noise transmission to the building. Flushed seal version is available for water with suspended particles. The pump is also available in stainless steel 316 construction for potable water or corrosive process loops.

Installation and Maintenance

Install the pump on a rigid foundation with flexible connectors on suction and discharge sides. The suction pipe should be short and straight to avoid air pockets. Always prime the pump before startup and ensure suction pressure is above NPSH required. Never run the pump dry. Check rotation direction during first start. Weekly inspection includes seal leakage, bearing temperature, and vibration. Annual maintenance includes greasing bearings, inspecting impeller wear ring clearance, and verifying shaft alignment. Replace mechanical seal when leakage exceeds 10 drops per minute. Drain the pump before freezing weather if installed outdoors.