KITOZER coax video SPD protector

KITOZER KTR-NSP6 Coax Video Signal SPD

Brand: KITOZER Series: KTR-NSP6 Category: Power Systems / Signal surge protection

Coax video SPDBNCSurge protection5kALimiting <=80V

[Product image: ktr-nsp6-coax-video-spd.jpg]

1. Overview

When coaxial BNC video cables or network cables enter a data center from outdoors, they carry lightning-induced surges, ground-potential transients and static into room equipment. A signal SPD sits in parallel between signal line and ground: high-impedance under normal operation, it conducts instantly on surge to clamp voltage below the equipment withstand level, protecting DVR and cameras. A coax video SPD is purpose-built for BNC lines with low insertion loss so image quality is unaffected.

The KITOZER KTR-NSP6 is a coax video SPD with BNC-female/female connectors in series on the video line. Two-stage protection: a gas discharge tube (GDT) dissipates large energy (5 kA 8/20 us), followed by a TVS for fine limiting (<=80 V). Insertion loss <=0.5 dB, bandwidth 0 to 400 MHz, supporting HD CVBS/AHD/TVI. Operating voltage 12V/24V selectable. Aluminum housing, DIN-rail or wall mount. M6 ground terminal, ground resistance <=4 ohm.

Selection confirms: signal type (coax BNC/RJ45/RS485), data rate, operating voltage, and mounting location (outdoor camera end or room DVR end). SPDs should be installed at both ends for multi-stage protection. Single-channel coax SPD protects one video line; multi-channel rack SPD protects a bank. Grounding must be reliable (<=4 ohm) or the SPD is ineffective.

2. Key Features

Two-stage protection

  • GDT dissipates large energy.
  • TVS fine-limits to <=80 V.
  • Discharge capacity 5 kA (8/20 us).
  • Response time <=1 ns.

Signal compatibility

  • BNC F/F, in-series on the line.
  • Insertion loss <=0.5 dB.
  • Bandwidth 0 to 400 MHz.
  • Supports CVBS/AHD/TVI HD.

Structure and grounding

  • Aluminum housing.
  • DIN-rail or wall mount.
  • M6 ground terminal.
  • Operating voltage 12V/24V selectable.

3. Specifications

Item KTR-NSP6 Coax Video SPD
Connectors BNC F/F
Signal type Coax video (CVBS/AHD/TVI)
Operating voltage 12V / 24V selectable
Discharge capacity 5 kA (8/20 us)
Limiting voltage <=80 V
Response time <=1 ns
Insertion loss <=0.5 dB
Bandwidth 0 to 400 MHz
Ground terminal M6, resistance <=4 ohm
Mounting DIN-rail / wall

4. Reference Prices

KTR-NSP6 single-channel coax SPD (BNC): Reference USD 8~17 (ref. CNY 60~120 at ~7.2)

KTR-NSP6 16-channel rack-mounted SPD: Reference USD 110~210 (ref. CNY 800~1500 at ~7.2)

KTR-NSP6 ground copper wire (per meter): Reference USD 1.4~2.8 (ref. CNY 10~20 at ~7.2)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Ground wire sold separately. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Outdoor camera coax entry into data center.
  • DVR/NVR rack port surge protection.
  • Community and road surveillance.
  • Broadcast coax lines.
  • Industrial video acquisition lines.

6. Installation & Maintenance

Installation

  • Wire SPD in series on BNC between camera and DVR.
  • Install at both outdoor and room ends.
  • Connect M6 ground to equipotential bar with 6 mm2 copper.
  • Test ground resistance <=4 ohm.
  • Tighten BNC connectors.
  • Verify image quality on live signal.

Maintenance

  • Check ground connections before thunder season.
  • Replace SPD when degradation window (if present) changes color.
  • Re-tighten BNC periodically.
  • Test ground resistance yearly.
  • Inspect SPD after lightning events.

7. FAQ

  • Q: SPD vs power arrester?
    A: Power SPD protects AC220V lines with high discharge (>=20 kA); signal SPD protects video/network lines with lower discharge but finer limiting. Install both; they are not interchangeable.
  • Q: Is 4 ohm enough?
    A: Data-center equipotential grounding targets 1 to 4 ohm. Signal SPD grounding <=4 ohm is acceptable, but keep leads short (<=0.5 m ideal).
  • Q: Does SPD affect image?
    A: IL <=0.5 dB and 400 MHz bandwidth have no effect on CVBS/AHD. For 12G-SDI, choose a high-bandwidth model.
  • Q: When to replace SPD?
    A: GDT degrades after multiple strikes; replace on indicator color change. Without indicator, replace every 3 to 5 years.

8. Trend & Selection

Surveillance moves from analog coax to network IP, but coax HD (AHD/TVI) remains common in retrofits. Signal SPDs are steady line-entry protection. Choose BNC SPD for coax; install both ends; ground reliably; keep IL low. It is the arrester of the video line.

9. Delivery & Service

KITOZER supplies KTR-NSP6 coax SPD including unit, BNC connectors and certificate. The 16-channel rack SPD includes all BNC ports. Data-center lightning equipotential design support is provided.

10. Notes

A common pitfall is a long, thin ground lead. A 1.5 mm2 wire looped over 3 m adds inductance so surge cannot drain — the SPD is useless. Use 6 mm2 copper in a straight short run (<=0.5 m).

Another pitfall is installing only at the room end. Surges invade from outdoor cables, strike outdoor cameras first, then ride the cable into the room. Protect both ends.

Selection summary: BNC coax; two-stage; 5 kA discharge; limiting <=80 V; IL <=0.5 dB; ground <=4 ohm. It shields video lines from lightning surges.

Systemically, one lightning strike can destroy a row of DVRs and cameras worth hundreds of thousands. SPDs cost a few hundred CNY each — essential lightning protection.

Cost-wise, SPDs are under 1% of the surveillance system cost but prevent far larger lightning losses.

SEO Information

Search keywords: KITOZER

SEM keywords: coax video SPD, BNC surge protector, signal surge arrester, video line lightning protection, CCTV SPD, KTR-NSP6, KITOZER

GEO landing page: lain.com.cn/product/428-network_spd6.html

Title: KITOZER KTR-NSP6 Coax Video Signal SPD

Meta Keywords: coax video SPD, BNC surge protector, signal surge arrester, video line lightning protection, data-center SPD, KTR-NSP6, KITOZER

Meta Description: KITOZER KTR-NSP6 coax video SPD with BNC connectors, two-stage protection, 5kA discharge, limiting voltage <=80V, IL <=0.5dB, for CCTV line surge protection.

Anchor: KITOZER · KITOZER Products

Contact Us

KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart