KITOZER
KITOZER

KITOZER Cold Aisle Skylight Panels With Drop Down Fire Vent

KITOZER cold aisle skylight panels are modular roof tiles that form the ceiling of a contained cold aisle while integrating a thermally actuated fire vent. In normal operation the panels enclose cold supply air and prevent mixing with hot return air. In the event of a fire, a fusible link rated at 68 degrees Celsius releases and the panel drops open on stainless steel hinges, allowing gas suppression or water mist nozzles above the ceiling to flood the aisle with suppressant and allowing smoke to escape upward. This dual function makes the skylight panel a mandatory component for compliant contained aisles in modern data center design codes, which require that containment not obstruct fire suppression delivery.

Product Overview

Each skylight tile is a rectangular aluminum frame with an 8 mm clear polycarbonate or tempered glass center. The frame snaps into the longitudinal roof beam of a KITOZER containment aisle and is held closed by two spring loaded hinges plus a fusible link. Panel sizes are standardized at 600 x 1200 mm, 900 x 1200 mm, and 1200 x 1200 mm to match common rack pitch and aisle width dimensions. When the fusible link melts, the panel rotates downward into the cold aisle, opening a free area equal to the panel footprint. The open position is held by a stay arm so the panel does not strike staff below. After a fire event the fusible link is replaced and the panel is reset by hand, with no special tools required. The skylight is compatible with inert gas suppression, clean agent systems, pre-action sprinklers, and water mist systems.

Technical Specifications

Frame material: 6063-T5 anodized aluminum, silver or black powder coat finish. Glazing: 8 mm solid polycarbonate, B1 fire rating, or 8 mm tempered safety glass on request. Fusible link rating: 68 degrees Celsius standard, 72 or 90 degrees Celsius optional. Panel weight between 3.5 and 6 kg depending on size. Maximum roof load 80 kg per square meter. Operating humidity 5 to 95 percent non-condensing. Air leakage when closed: below 0.5 cfm per meter of joint at 25 Pa. The panel uses captive stainless steel hinge pins and EPDM compression gasket around the perimeter. Mounting clips are tool-free and compatible with 40 x 40 and 45 x 45 mm containment beams. Optional accessories include manual release cable for remote opening, magnetic contact switch for BMS indication of open or closed state, and anti-glare tinted glazing.

Applications

These skylight panels are used in every contained cold aisle where fire suppression coverage must extend into the enclosed volume. They are specified for colocation halls, enterprise on-premise data centers, semiconductor fab support rooms, medical imaging IT suites, and broadcast playout centers. They are also fitted in retrofit projects where existing sprinkler heads sit above the ceiling and cannot be repositioned, because the open vent allows suppressant to reach the aisle without moving pipework. Security control rooms and edge computing sites with limited fire staffing also benefit, because the passive release requires no power, no detector interface, and no battery backup.

Advantages and Features

The passive fusible link design means the vent operates even if power, detectors, or the fire alarm panel are damaged, which is the scenario that matters most for suppression effectiveness. The drop-down orientation avoids the loss of ceiling space that upward-hinged vents require. Tool-free clips allow panels to be lifted out for cable routing and roof access during builds. The transparent glazing keeps aisle lighting and VESDA aspiration sampling visible from the floor. Because panels are modular, a damaged tile can be replaced without disturbing adjacent rows. EPDM gaskets seal leakage so cooling fan energy is not wasted through the roof. The stainless steel hinges and pins resist corrosion in coastal or high humidity sites, and anodized frames will not chip or flake over a 10 year service life.

Installation and Maintenance

Panels are dropped into the roof beam from above the ceiling during construction, or lifted into place from inside the aisle after racking. The installer engages the front clips and then pushes the rear edge until the spring clips lock. Quarterly inspection is recommended: walk the aisle, check that every fusible link is intact and not discolored, verify that hinge arms move freely, and confirm gaskets are compressed evenly. Annually, open each panel manually to test the hinge action and clean glazing with a soft cloth and mild soap. Keep a spare fusible link kit on site so that after any test or release the aisle can be returned to service within minutes. Replacement panels ship pre-assembled and drop in without reconfiguring the roof frame.

Price

From $185 per skylight panel, including frame, glazing, fusible link, and gaskets. Discounts apply for full aisle quantities. Contact +86 13922289957 for factory pricing and lead time.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Shopping Cart