Table of Contents
ToggleKITOZER KTR-GS Combustible Gas Sensor for Data Center
Brand: KITOZER Series: KTR-GS Category: Environmental Monitoring / Gas Detection
combustible gasRS48525% LELcat/IRKTR-GS

1. Overview
The room itself does not burn gas, but the adjacent canteen kitchen, diesel-generator tank, battery-room hydrogen and FM-200 cylinder room all carry leak risks. Natural gas (methane) explodes on ignition; batteries vent hydrogen during charging, accumulating into the 4%~75% explosive range; FM-200 is non-flammable but high-pressure leaks cause asphyxiation. Room gas sensors monitor combustibles 24/7, alarm above 25% LEL and start exhaust fans to prevent explosion and asphyxiation.
The KITOZER KTR-GS detects methane (natural gas), LPG and hydrogen. Two principles: catalytic bead (covers most combustibles, low cost) and infrared IR (methane, long life, poison-resistant). Range 0~100% LEL, alarm default 25% LEL (adjustable). Output: RS485 Modbus-RTU to the environment host, or dry contact directly to the exhaust fan. DC 9~24 V, wall-mount, with local sound/light alarm.
Selection: gas type — methane sensor for natural gas, hydrogen sensor for battery rooms, general catalytic for mixed risks; principle — catalytic bead element replaced every 3~5 years, IR lasts 5~8 years for unmanned rooms; and location — lighter-than-air gases (methane, hydrogen) mount 30 cm below the ceiling, heavier-than-air (LPG) 30 cm above the floor. Sensors are consumables calibrated yearly with certified gas.
2. Key Features
Detection
- 0~100% LEL
- Alarm at 25% LEL
- Catalytic bead / IR
- Response <=30 s
Output
- RS485 Modbus-RTU
- Dry contact
- Local sound/light
- Exhaust fan interlock
Mounting
- Wall-mount
- DC 9~24 V
- ABS explosion-proof case
- -20~50C operating
3. Specifications
| Item | KTR-GS-S1 | KTR-GS-S2 | KTR-GS-S3 |
|---|---|---|---|
| 型号 | KTR-GS-M1 | KTR-GS-H1 | KTR-GS-IR1 |
| 检测气体 | 甲烷/天然气 | 氢气 | 甲烷(红外) |
| 原理 | 催化燃烧 | 催化燃烧 | 红外IR |
| 量程 | 0~100%LEL | 0~100%LEL | 0~100%LEL |
| 报警阈值 | 25%LEL | 25%LEL | 25%LEL |
| 输出 | RS485+开关量 | RS485+开关量 | RS485+开关量 |
| 寿命 | 3~5年 | 3~5年 | 5~8年 |
| 安装位置 | 天花板下30cm | 天花板下30cm | 天花板下30cm |
4. Reference Prices
KTR-GS-M1 methane catalytic-bead sensor: Reference USD 39~67 / pc (ref. CNY 280~480 at ~7.2)
KTR-GS-H1 hydrogen sensor (battery room): Reference USD 53~86 / pc (ref. CNY 380~620 at ~7.2)
KTR-GS-IR1 methane IR sensor (long life): Reference USD 94~153 / pc (ref. CNY 680~1100 at ~7.2)
Calibration gas (1 L aluminum cylinder): Reference USD 21~39 / bottle (ref. CNY 150~280 at ~7.2)
Reference only; priced by gas type and principle. 1-year warranty. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Adjacent canteen kitchen natural-gas monitoring.
- Battery-room hydrogen leak monitoring.
- Diesel-generator tank area combustibles.
- Gas-cylinder room (FM-200) monitoring.
- Underground garage gas leaks.
6. Deployment & Implementation
Installation
- Mount lighter-than-air gases below ceiling
- Mount heavier-than-air gases above floor
- 3~6 m from the source
- Daisy-chain RS485
Operations
- Calibrate yearly with certified gas
- Replace element every 3~5 years
- Test sound/light alarm
- Test exhaust-fan interlock
7. FAQ
- Q: What does LEL mean?
A: LEL (Lower Explosive Limit) is the lowest gas concentration that explodes on ignition. Methane LEL = 5% by volume; 25% LEL = 1.25%. A 0~100% LEL sensor maps to 0~5% methane by volume. - Q: Why a hydrogen sensor in the battery room?
A: Lead-acid charging splits water into hydrogen, with an explosive range of 4%~75% by volume. Poor ventilation lets hydrogen reach 4% and ignite on a spark. The sensor alarms at 25% LEL (=1% hydrogen) and starts exhaust. - Q: Catalytic bead or IR?
A: Catalytic bead is cheap but poisoned by silicone and H2S, element replaced every 3~5 years. IR lasts 5~8 years, resists poisoning, but costs 2~3x more. Choose IR for unmanned rooms, catalytic for manned sites. - Q: Do sensors need calibration?
A: Yes. Flow certified gas (1.5% methane) yearly and compare reading and alarm point. Re-calibrate if off >+/-5% LEL; replace if off >+/-10% LEL.
8. Trend & Selection
Sensors are moving from single gas to multi-gain probes (combustible + CO + O2 + temp/humidity in one head). Wireless LoRa sensors suit retrofit without cabling. IR costs are falling and replacing catalytic beads. On-board AI self-diagnosis distinguishes real leaks from poisoned sensors, cutting false alarms.
9. Delivery & Service
KITOZER supplies KTR-GS by gas type (methane/hydrogen/general), principle (catalytic/IR) and output (RS485/dry contact). Ships with sensor, bracket, power and manual. Calibration certificate included. 1-year warranty; batch projects can add exhaust fans, dampers, environment hosts and calibration gas.
10. Additional Notes
The #1 mistake is wrong mounting. Methane is lighter than air, so a floor-mounted sensor never sees it — methane has already risen to the ceiling. Mount lighter gases 30 cm below the ceiling; heavier gases 30 cm above the floor.
The second pitfall is alarm without fan interlock. The sensor alarms but the exhaust fan is not interlocked; a platform popup goes unnoticed and gas keeps accumulating. The dry contact must directly start the fan while reporting to the host.
The third blunder is no calibration or replacement. Five years without calibration ages the catalytic bead; a real 50% LEL leak reads as 10%. Calibrate yearly and replace the element every 3~5 years.
Selection summary: light gases below ceiling, heavy gases above floor, dry contact directly interlocks the fan, annual calibration and 3~5 year element replacement. The gas sensor is the room’s nose — a missed leak is a time bomb.
SEO Information
Search keywords:KTR-GSKITOZERCombustible Gas Sensor for Data Center
SEM keywords:combustible gas sensor,gas detector,natural gas sensor,methane detector,KTR-GS,KITOZER
GEO landing page:lain.com.cn/product/ktr-gs-gas_sensor.html
Title:KITOZER KTR-GS Combustible Gas Sensor for Data Center
Meta Keywords:combustible gas sensor,gas detector,natural gas sensor,methane detector,KTR-GS,KITOZER
Meta Description:KITOZER KTR-GS combustible gas sensor, catalytic/IR principle, methane/hydrogen, RS485 + dry contact, for room environment monitoring.
Anchor: KITOZER by Guangzhou Laian · Combustible Gas Sensor for Data Center
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com