KITOZER Computer Room Air Conditioning Solution

I. System Introduction

1.1 System Overview

The KITOZER computer room air conditioning system is a professional cooling solution exclusively designed for precision environments such as data centers, computer rooms and server rooms. It features precise constant temperature and humidity control, large air volume and high sensible heat ratio. The system accurately regulates ambient temperature within 18-27℃ and relative humidity within 40%-60%RH, meeting the stringent environmental requirements for stable operation of various IT equipment.

Covering multiple types including room-level, row-interline, in-row and wall-mounted air conditioners, and equipped with a professional condensate drainage system, it provides all-round heat dissipation support for computer rooms of different scales and heat densities, ensuring 24/7/365 continuous and stable operation of equipment.

1.2 System Working Principle

The KITOZER computer room air conditioning system operates based on dual mechanisms of refrigeration cycle and air circulation:

1. Refrigeration Cycle: Adopts direct expansion or chilled water refrigeration technology. Through four core components (compressor, condenser, expansion valve and evaporator), it completes the phase change cycle of refrigerant and transfers indoor heat to the outdoor environment.

2. Air Circulation: EC energy-saving fans deliver large-volume air circulation with air changes ≥30 times per hour, ensuring uniform indoor temperature distribution and eliminating local hotspots.

3. Temperature & Humidity Control: Equipped with high-precision temperature and humidity sensors and a PID intelligent control system, it monitors environmental parameters in real time and automatically adjusts refrigeration, heating, humidification and dehumidification functions to maintain stable ambient conditions.

4. Condensate Drainage: Condensate generated during operation is discharged safely and efficiently via gravity drainage or pump drainage modes to eliminate water leakage risks in the computer room.

data center air conditioning solutions (9)

II. System Composition

System ModuleCore ComponentsFunctional Description
Refrigeration SystemCompressor, condenser, evaporator, expansion valve, refrigerant pipelineRealizes heat transfer and reduces indoor air temperature
Air Handling SystemEC energy-saving fan, high-efficiency filter, heater, humidifier, dehumidifierRegulates air temperature, humidity and cleanliness, and realizes indoor air circulation
Control SystemMicroprocessor, temperature & humidity sensor, pressure sensor, control panel, communication moduleEnables intelligent monitoring and control, supporting remote management and fault alarm
Water SystemCondensate drip tray, drainage pipe, lift pump, water seal device, filterDischarges condensate safely and prevents water leakage and secondary condensation
Power Distribution SystemAir switch, contactor, thermal relay, frequency converter, surge protectorEnsures safe and stable power supply and supports variable-frequency energy-saving operation
Accessory SystemShockproof pad, vibration damper, thermal insulation material, silencer, mounting bracketOptimizes installation effect, reduces operating noise and improves system efficiency
data center air conditioning solutions (8)

III. System Classification

3.1 Classification by Installation Type

3.1.1 Room-level Precision Air Conditioner

  • Installed on one side or corner of the computer room for centralized cooling of the entire space
  • Air supply modes: bottom supply & top return, top supply & bottom return, side supply
  • Applicable scenarios: small and medium-sized computer rooms (50-1000㎡) with single cabinet power ≤8kW

3.1.2 Row-interline Air Conditioner

  • Installed between cabinet rows with horizontal air supply and return
  • Close to heat sources with zero distance, featuring high cooling efficiency and local hotspot elimination
  • Applicable scenarios: medium and large-sized data centers with single cabinet power of 8-20kW

3.1.3 In-row Air Conditioner

  • Integrated with server cabinets and installed in cabinet rows
  • Adopts back-to-back or face-to-face deployment for hot and cold aisle isolation
  • Applicable scenarios: high-density data centers, micro-module computer rooms with single cabinet power ≥20kW

3.1.4 Integrated Wall-mounted Dedicated Computer Room Air Conditioner

  • Wall-mounted installation saves floor space with no room occupation
  • Integrated design enables simple installation and convenient maintenance
  • Applicable scenarios: small computer rooms, network cabinet rooms, edge computing nodes with cooling capacity ≤10kW

3.1.5 Condensate Drainage System for Air Conditioners

  • Available in two drainage modes: gravity drainage and pump drainage
  • Equipped with water seal device, filter and alarm system
  • Applicable to all computer room air conditioning systems to ensure safe condensate discharge

3.2 Classification by Cooling Method

Cooling MethodWorking PrincipleAdvantagesApplicable Scenarios
Air-cooledCondenser cooled by outdoor ambient air without cooling water system requiredSimple installation, low maintenance cost and high system reliabilitySmall and medium-sized computer rooms and water-scarce areas
Water-cooledCondenser cooled by cooling water with supporting cooling tower or water source requiredHigh cooling efficiency, low operating noise and suitability for high-load operationLarge-scale data centers and high-density computer rooms
Dual-source CoolingIntegrates both air-cooled and water-cooled cooling modesRedundant design improves system reliability with remarkable energy-saving effectCore business computer rooms requiring ultra-high availability
Free CoolingDirect cooling via low-temperature outdoor air to reduce compressor operating hoursEnergy consumption reduced by over 30% with eco-friendly performanceLarge-scale data centers in cold climate regions
data center air conditioning solutions (6)

IV. System Configuration List (KITOZER Brand)

4.1 Configuration List of Room-level Precision Air Conditioner

No.Equipment NameModelBrandQuantityUnitFunctional Description
1Room-level Precision Air Conditioner Indoor UnitKTR-20KITOZER1Set20kW cooling capacity, constant temperature & humidity, bottom air supply and top air return
2Room-level Precision Air Conditioner Outdoor UnitKTR-20CKITOZER1SetAir-cooled condenser matched with indoor unit
3Temperature & Humidity SensorKTS-01KITOZER2PcsAccuracy: ±0.5℃, ±3%RH, real-time environmental parameter monitoring
4High-efficiency Air FilterKAF-03KITOZER2SetsG4 filtration efficiency for indoor air purification
5Condensate Lift PumpKCP-02KITOZER1SetMax lifting height 8m, flow rate 20L/min
6Drainage Pipe & AccessoriesKDP-01KITOZER1SetIncludes PVC pipes, elbows, tees and water seal devices
7Control System ModuleKCS-01KITOZER1SetIntelligent control with remote monitoring and fault alarm support
8Installation AccessoriesKMA-01KITOZER1SetIncludes shockproof pads, brackets and thermal insulation materials

4.2 Configuration List of Row-interline Air Conditioner

No.Equipment NameModelBrandQuantityUnitFunctional Description
1Row-interline Air Conditioner UnitKIR-30KITOZER1Set30kW cooling capacity, horizontal air supply, hot and cold aisle isolation
2Row-interline Air Conditioner BracketKIS-02KITOZER1SetCompatible with standard cabinets for inter-row installation
3Temperature & Humidity SensorKTS-01KITOZER2PcsInstalled in hot/cold aisles for accurate temperature distribution monitoring
4Condensate Collection DeviceKCC-01KITOZER1SetIntegrated drip tray and drainage interface
5Condensate Drainage PipeKDP-02KITOZER1SetSpecial corrosion-resistant drainage pipe with gradient ≥2%
6Intelligent Control SystemKCS-02KITOZER1SetSupports group control and docking with data center management system
7Backup Power ModuleKBP-01KITOZER1SetSustains 30-minute operation after power failure for equipment protection

4.3 Configuration List of In-row Air Conditioner

No.Equipment NameModelBrandQuantityUnitFunctional Description
1In-row Air Conditioner Indoor UnitKMR-40KITOZER1Set40kW cooling capacity, horizontal air supply, cabinet integrated design
2In-row Air Conditioner Outdoor UnitKMR-40CKITOZER1SetHigh-efficiency air-cooled condenser with EC fan energy-saving design
3Cabinet Integrated BracketKMS-03KITOZER1SetMatches standard 19-inch cabinets for seamless integration
4Air DistributorKAD-01KITOZER1SetOptimizes airflow distribution and improves cooling efficiency
5Condensate Lift Pump UnitKCP-03KITOZER1SetDual-pump redundant design ensures safe drainage
6Intelligent Group Control SystemKCC-02KITOZER1SetSupports coordinated operation and load balancing of multiple units
7Remote Monitoring ModuleKRM-01KITOZER1SetSupports Web & APP remote management and fault early warning

4.4 Configuration List of Integrated Wall-mounted Air Conditioner

No.Equipment NameModelBrandQuantityUnitFunctional Description
1Integrated Wall-mounted Air ConditionerKWB-08KITOZER1Set8kW cooling capacity, dedicated for computer rooms, wall-mounted installation
2Mounting BracketKWS-01KITOZER1SetLoad capacity ≥100kg for firm and safe installation
3Condensate Drainage PipeKDP-03KITOZER1SetSpecial PVC pipe with length of 5m
4Temperature & Humidity ControllerKWC-01KITOZER1PcBuilt-in sensor for precise temperature and humidity control
5Remote ControllerKWR-01KITOZER1PcSupports remote operation and convenient management

4.5 Configuration List of Condensate Drainage System

No.Equipment NameModelBrandQuantityUnitFunctional Description
1Condensate Collection TrayKCC-02KITOZER1SetCompatible with various air conditioner models with anti-overflow design
2Condensate Lift PumpKCP-04KITOZER1SetMax lifting height 10m, flow rate 30L/min
3Water Seal DeviceKWP-01KITOZER1PcU-type trap with water seal height ≥50mm
4Drainage PipeKDP-04KITOZER1MeterDN25 PVC pipe with corrosion resistance and thermal insulation treatment
5FilterKWF-01KITOZER1PcPrevents pipeline blockage by impurities
6Water Leakage DetectorKLD-01KITOZER1PcReal-time water leakage monitoring and alarm reminder
7Control ModuleKCM-01KITOZER1PcAutomatically controls pump operation and fault alarm
data center air conditioning solutions (4)

V. System Schematic Diagram

5.1 Schematic Diagram of Room-level Precision Air Conditioning System

5.2 Schematic Diagram of Row-interline / In-row Air Conditioning System

5.3 Schematic Diagram of Integrated Wall-mounted Air Conditioner

VI. Product Technical Parameters

6.1 Room-level Precision Air Conditioner (KTR Series)

Parameter ItemKTR-10KTR-20KTR-30KTR-50
Cooling Capacity (kW)10203050
Sensible Heat Ratio0.90.90.90.9
Air Volume (m³/h)360072001080018000
Air Supply ModeBottom/Top SupplyBottom/Top SupplyBottom/Top SupplyBottom/Top Supply
Temperature Control Range18-27℃18-27℃18-27℃18-27℃
Humidity Control Range40%-60%RH40%-60%RH40%-60%RH40%-60%RH
Temperature Control Accuracy±0.5℃±0.5℃±0.5℃±0.5℃
Humidity Control Accuracy±3%RH±3%RH±3%RH±3%RH
Compressor TypeScroll TypeScroll TypeScroll TypeScroll Type
Fan TypeEC Energy-saving FanEC Energy-saving FanEC Energy-saving FanEC Energy-saving Fan
Power Supply380V/50Hz380V/50Hz380V/50Hz380V/50Hz
Energy Efficiency Ratio (EER)3.23.53.63.8

6.2 Row-interline Air Conditioner (KIR Series)

Parameter ItemKIR-20KIR-30KIR-40KIR-60
Cooling Capacity (kW)20304060
Sensible Heat Ratio0.950.950.950.95
Air Volume (m³/h)600090001200018000
Air Supply ModeHorizontal SupplyHorizontal SupplyHorizontal SupplyHorizontal Supply
Installation TypeInter-row InstallationInter-row InstallationInter-row InstallationInter-row Installation
Temperature Control Range18-27℃18-27℃18-27℃18-27℃
Humidity Control Range40%-60%RH40%-60%RH40%-60%RH40%-60%RH
Compressor TypeVariable-frequency ScrollVariable-frequency ScrollVariable-frequency ScrollVariable-frequency Scroll
Fan TypeEC Energy-saving FanEC Energy-saving FanEC Energy-saving FanEC Energy-saving Fan
Power Supply380V/50Hz380V/50Hz380V/50Hz380V/50Hz
Energy Efficiency Ratio (EER)4.04.24.34.5

6.3 In-row Air Conditioner (KMR Series)

Parameter ItemKMR-30KMR-40KMR-50KMR-60
Cooling Capacity (kW)30405060
Sensible Heat Ratio0.980.980.980.98
Air Volume (m³/h)9000120001500018000
Air Supply ModeHorizontal SupplyHorizontal SupplyHorizontal SupplyHorizontal Supply
Installation TypeIn-row InstallationIn-row InstallationIn-row InstallationIn-row Installation
Cabinet Compatibility19-inch Standard Cabinet19-inch Standard Cabinet19-inch Standard Cabinet19-inch Standard Cabinet
Temperature Control Range18-27℃18-27℃18-27℃18-27℃
Humidity Control Range40%-60%RH40%-60%RH40%-60%RH40%-60%RH
Compressor TypeDual Variable-frequency ScrollDual Variable-frequency ScrollDual Variable-frequency ScrollDual Variable-frequency Scroll
Fan TypeEC Energy-saving FanEC Energy-saving FanEC Energy-saving FanEC Energy-saving Fan
Power Supply380V/50Hz380V/50Hz380V/50Hz380V/50Hz
Energy Efficiency Ratio (EER)4.54.64.74.8

6.4 Integrated Wall-mounted Air Conditioner (KWB Series)

Parameter ItemKWB-05KWB-08KWB-10
Cooling Capacity (kW)5810
Sensible Heat Ratio0.850.850.85
Air Volume (m³/h)180028803600
Air Supply ModeSide SupplySide SupplySide Supply
Installation TypeWall-mountedWall-mountedWall-mounted
Temperature Control Range18-27℃18-27℃18-27℃
Humidity Control Range40%-60%RH40%-60%RH40%-60%RH
Compressor TypeRotary TypeRotary TypeRotary Type
Fan TypeCentrifugal FanCentrifugal FanCentrifugal Fan
Power Supply220V/50Hz220V/50Hz220V/50Hz
Energy Efficiency Ratio (EER)3.03.13.2

6.5 Condensate Drainage System (KCP Series)

Parameter ItemKCP-02KCP-03KCP-04
Max Lifting Height (m)81012
Max Flow Rate (L/min)203040
Power Supply220V/50Hz220V/50Hz220V/50Hz
Protection GradeIP44IP44IP44
Operating Noise (dB)≤45≤45≤45
Automatic ControlFloat Switch ControlFloat Switch ControlFloat Switch Control
Alarm FunctionWater Leakage AlarmWater Leakage AlarmWater Leakage Alarm
MaterialEngineering PlasticEngineering PlasticEngineering Plastic

VII. Product Application Scope

7.1 Data Center Industry

  • Large-scale cloud computing data centers, small and medium-sized enterprise data centers
  • Edge computing nodes, micro-module data centers
  • Core data centers in finance, telecommunications, Internet and other industries

7.2 Computer Room Industry

  • Computer rooms, server rooms, network rooms
  • Communication rooms, IDC rooms, hosting computer rooms
  • Control rooms for power, energy, transportation and other industries

7.3 Other Precision Environments

  • Laboratories, testing centers, metrology centers
  • Medical equipment rooms, precision instrument rooms
  • Archives, museums, libraries (constant temperature & humidity requirements)
  • Industrial automation control rooms, PLC computer rooms

VIII. Product Advantages

8.1 Precise Control & Stable Reliability

  • High-precision temperature and humidity control: ±0.5℃ temperature accuracy and ±3%RH humidity accuracy, meeting stringent requirements of IT equipment
  • Large air volume design with air changes ≥30 times per hour eliminates local hotspots and ensures indoor temperature uniformity ≤±2℃
  • 24/7 uninterrupted operation with MTBF ≥80,000 hours, supporting 365-day continuous operation

8.2 High Energy Efficiency & Cost Reduction

  • EC energy-saving fans reduce energy consumption by over 30% compared with traditional fans
  • Variable-frequency compressors automatically adjust speed according to load, significantly improving EER under partial load conditions
  • Free cooling technology utilizes low-temperature outdoor air for direct cooling, greatly reducing compressor operating hours
  • Heat recovery function recycles waste heat from computer rooms for heating other areas to improve energy utilization rate

8.4 Intelligent Management & Convenient O&M

  • Intelligent control system supports remote monitoring, fault alarm and automatic switching to reduce O&M costs
  • Group control function enables coordinated operation and load balancing of multiple units to improve system efficiency
  • Automatic fault self-diagnosis detects and records fault information for rapid positioning and shortened maintenance time
  • Historical data recording stores over 1-year operating data for data analysis and trend prediction

8.5 Comprehensive Safety Protection

  • Multi-protection functions including over-voltage, over-current, over-heat, over-humidity and under-voltage protection prevent equipment damage
  • Anti-leakage design adopts dual-pump redundant condensate lifting and water leakage alarm to avoid room water hazards
  • G4-grade high-efficiency filtration protects IT equipment from dust erosion and extends service life

8.6 Flexible Adaptation & Easy Expansion

  • Various installation types including room-level, inter-row, in-row and wall-mounted adapt to different room layouts
  • Modular design supports on-demand capacity expansion, reducing initial investment and adapting to business growth
  • Multiple cooling modes (air-cooled, water-cooled, dual-source, free cooling) fit diverse application scenarios

IX. Bid-winning Parameter Specifications

9.1 Bid Parameters for Room-level Precision Air Conditioner

  1. Brand: KITOZER, Model: KTR Series
  2. Cooling capacity: 10-50kW, sensible heat ratio ≥0.9
  3. Temperature control range: 18-27℃, control accuracy: ±0.5℃
  4. Humidity control range: 40%-60%RH, control accuracy: ±3%RH
  5. Air supply mode: bottom/top air supply, air volume ≥3600m³/h (10kW model)
  6. Compressor: scroll type; Fan: EC energy-saving fan
  7. Protection grade: indoor unit IP20, outdoor unit IP54
  8. Communication interface: RS485, supports Modbus protocol for room monitoring system access
  9. Equipped with heating, humidification and dehumidification functions to meet annual operation requirements
  10. MTBF ≥80,000 hours with 3-year warranty

9.2 Bid Parameters for Inter-row / In-row Air Conditioner

  1. Brand: KITOZER, Model: KIR/KMR Series
  2. Cooling capacity: 20-60kW, sensible heat ratio ≥0.95 (inter-row) / ≥0.98 (in-row)
  3. Air supply mode: horizontal air supply at cabinet height, adapting to hot and cold aisle isolation
  4. Installation type: inter-row/in-row installation without raised floor required
  5. Compressor: variable-frequency scroll type; Fan: EC energy-saving fan; EER ≥4.0
  6. Temperature control accuracy: ±0.5℃; Humidity control accuracy: ±3%RH
  7. Supports group control of up to 32 coordinated operating units
  8. Equipped with automatic fault switching function to improve system reliability
  9. Protection grade: IP20 for computer room environment adaptation
  10. MTBF ≥100,000 hours with 3-year warranty

9.3 Bid Parameters for Integrated Wall-mounted Air Conditioner

  1. Brand: KITOZER, Model: KWB Series
  2. Cooling capacity: 5-10kW, sensible heat ratio ≥0.85
  3. Installation type: wall-mounted with no floor space occupation
  4. Temperature control range: 18-27℃, control accuracy: ±1℃
  5. Humidity control range: 40%-60%RH, control accuracy: ±5%RH