Toggle1. System Introduction
The KITOZER ATS Cabinet (Automatic Transfer Switch) is a dual-power automatic transfer system specially designed for critical power environments such as computer rooms and data centers. As core equipment to guarantee power supply continuity, it enables fast and reliable switching between the normal power supply (mains electricity) and standby power supply (diesel generator / secondary mains electricity), ensuring uninterrupted operation of IT equipment and critical loads when the main power fails.
Adopting the design concepts of intelligent monitoring, rapid switching, mechanical interlock and multi-level protection, the system complies with Class A standards specified in GB50174-2008 Code for Design of Electronic Information System Computer Rooms, delivering top-tier power supply protection for data centers.
It real-time monitors voltage, frequency, phase and other parameters of the two power sources. When the normal power encounters undervoltage, overvoltage, phase loss or power loss, the system will automatically switch to the standby power within 50ms to 2s. Combined with UPS systems, it realizes zero-interruption power supply, acting as the lifeline of power infrastructure in computer rooms.
2. System Composition
The KITOZER ATS Cabinet system consists of the following core components to form a complete dual-power transfer solution:
| System Component | Main Composition | Function Description |
|---|---|---|
| ATS Switch Body | PC/CB class transfer switch, mechanical interlock mechanism, electric operating mechanism | Realize physical switching of two power sources; mechanical interlock prevents simultaneous closing of two power circuits to ensure power supply safety |
| Intelligent Control Unit | Microprocessor controller, voltage/current sensors, display interface, communication module | Real-time monitoring of power parameters, fault judgment, switching command output; support remote monitoring and data upload |
| Protection Components | Circuit breaker, fuse, surge protector, lightning protection module | Provide comprehensive protection against short circuit, overload, overvoltage, undervoltage and lightning strikes to safeguard loads and equipment |
| Cabinet Structure | High-strength cold-rolled steel cabinet, ventilation system, operation panel, indicator lights | Offer installation space and physical protection; facilitate operation and maintenance; protection rating ≥ IP20 |
| Auxiliary System | Power module, backup battery, signal indicators, operation buttons | Supply stable power to the control system and sustain its operation during main power failure; provide status indication and manual operation |
| Communication Interface | RS485 port, Modbus RTU/TCP protocol, SNMP module | Enable linkage with computer room monitoring systems and building automation systems for remote and centralized management |
3. System Classification
Classified by application scenarios and technical features, the KITOZER ATS Cabinet is divided into the following categories:
3.1 Classification by Switch Grade
| Type | Core Features | Application Scenarios |
|---|---|---|
| PC-class ATS Cabinet | Designed exclusively for power transfer, no built-in short-circuit protection (external circuit breaker required); switching time ≤ 50ms; mechanical service life ≥ 10,000 times | Large-scale data centers, Class A computer rooms; used with UPS systems for maximum reliability and ultra-fast switching |
| CB-class ATS Cabinet | Equipped with overcurrent trip unit and built-in short-circuit protection; capable of breaking short-circuit current directly without external circuit breakers | Small and medium-sized computer rooms, edge computing nodes; ideal for scenarios requiring integrated protection and simplified power distribution design |
3.2 Classification by Installation Method
- Floor-standing ATS Cabinet: Standard 19-inch cabinet design. Dimensions: 600/800mm (W) × 1800/2000mm (H) × 800/1000mm (D). Suitable for dedicated power distribution areas in computer rooms.
- Wall-mounted ATS Box: Compact structure. Dimensions: 300-600mm (W) × 400-800mm (H) × 200-400mm (D). Ideal for space-limited small computer rooms and edge computing nodes.
- Withdrawable ATS Cabinet: Core components can be pulled out for maintenance. Applicable to mission-critical computer rooms requiring online maintenance without power interruption.
3.3 Classification by Transfer Mode
- Mains-to-Generator ATS Cabinet: Normal power from mains electricity, standby power from diesel generator. Supports automatic start signal output for generators. For computer rooms without a second mains power supply.
- Mains-to-Mains ATS Cabinet: Transfer between two independent mains power sources. Adopted by computer rooms with dual mains access to achieve the highest level of power reliability.
- Bypass-type ATS Cabinet: Equipped with manual bypass function. When the main ATS switch malfunctions, the bypass switch maintains power supply to support online maintenance. Perfect for Class A computer rooms and critical loads.
3.4 Classification by Rated Current
- Small ATS Cabinet: Rated current 100-400A, for small & medium computer rooms, edge computing nodes and miniature data centers.
- Medium ATS Cabinet: Rated current 630-1250A, for standard data centers, cloud computing nodes and enterprise-level computer rooms.
- Large ATS Cabinet: Rated current 1600-4000A, for ultra-large data centers, cloud computing hubs and high-density server clusters.
4. System Configuration List (Brand: KITOZER)
4.1 Configuration List of PC-class Floor-standing ATS Cabinet (Rated Current: 630A)
| No. | Equipment Name | Model | Quantity | Specifications |
|---|---|---|---|---|
| 1 | PC-class ATS Cabinet Body | KITOZER-ATS-PC-630 | 1 Set | PC-class transfer switch, rated current 630A, rated voltage 400V, mechanical life 10,000 times, switching time ≤ 50ms |
| 2 | Intelligent Controller | KITOZER-ATSC-02 | 1 Set | 7-inch color touch screen; real-time monitoring of voltage/frequency/phase; compatible with Modbus RTU/TCP and RS485 communication |
| 3 | Main Circuit Breaker | KITOZER-MCB-630 | 2 Sets | Molded case circuit breaker, rated current 630A, short-circuit breaking capacity 50kA, 3P/4P optional |
| 4 | Surge Protector | KITOZER-SPD-40 | 1 Set | Nominal discharge current 40kA, Class B protection, response time ≤ 25ns, 3P+N configuration |
| 5 | Current Transformer | KITOZER-CT-600/5 | 3 Pcs | Ratio 600/5A, accuracy class 0.5, for current monitoring and protection control |
| 6 | Voltage Monitoring Module | KITOZER-VM-01 | 1 Set | Monitor three-phase voltage, frequency and phase; accuracy class 0.2; support overvoltage/undervoltage alarm |
| 7 | Operation Panel | KITOZER-OP-01 | 1 Set | Equipped with power indicator, running indicator, fault indicator, manual/automatic transfer switch and emergency stop button |
| 8 | Communication Module | KITOZER-CM-02 | 1 Pc | Support Modbus TCP/IP and SNMPv3; accessible to computer room monitoring systems |
| 9 | Cabinet Structure | KITOZER-CAB-800 | 1 Set | 800×2000×1000mm, high-strength cold-rolled steel, IP20 protection rating, front & rear double doors for easy maintenance |
| 10 | Auxiliary Power Supply | KITOZER-PS-03 | 1 Pc | Dual-input automatic transfer, 24VDC output, provides stable power for control system |
4.2 Configuration List of CB-class Wall-mounted ATS Box (Rated Current: 250A)
| No. | Equipment Name | Model | Quantity | Specifications |
|---|---|---|---|---|
| 1 | CB-class ATS Box Body | KITOZER-ATS-CB-250 | 1 Set | CB-class transfer switch, rated current 250A, built-in overcurrent protection, switching time ≤ 1s, mechanical life 8,000 times |
| 2 | Intelligent Controller | KITOZER-ATSC-01 | 1 Set | 4.3-inch color display; voltage/frequency monitoring; RS485 communication and Modbus RTU protocol |
| 3 | Surge Protector | KITOZER-SPD-20 | 1 Set | Nominal discharge current 20kA, Class C protection, response time ≤ 25ns, 3P+N configuration |
| 4 | Status Indicator Light | KITOZER-LT-01 | 1 Set | Mains indicator, standby power indicator, fault indicator and running indicator |
| 5 | Operation Buttons | KITOZER-PB-01 | 1 Set | Manual/automatic transfer button, emergency stop button and test button |
| 6 | Communication Interface | KITOZER-CM-01 | 1 Pc | RS485 port, Modbus RTU protocol, connectable to local monitoring systems |
| 7 | Cabinet Structure | KITOZER-CAB-400 | 1 Set | 400×600×250mm, wall-mounted, cold-rolled steel, IP30 protection rating |
| 8 | Auxiliary Power Supply | KITOZER-PS-02 | 1 Pc | Single input, 24VDC output, built-in backup battery, sustains control system operation for ≥ 4 hours |
4.3 Optional Accessories List
| Accessory Name | Model | Function Description |
|---|---|---|
| Bypass Switch Module | KITOZER-BP-01 | Enable online maintenance of ATS switch without power interruption; suitable for Class A computer rooms |
| Generator Auto-start Module | KITOZER-GS-01 | Control automatic start/stop of diesel generators; matched with mains-to-generator ATS cabinets |
| Energy Metering Module | KITOZER-EM-01 | Accurately measure power consumption of two power sources; support remote meter reading and energy consumption analysis |
| Temperature Monitoring Module | KITOZER-TM-01 | Monitor internal temperature of ATS cabinet to prevent overheating and trigger temperature alarm & protection |
| Remote O&M Module | KITOZER-RM-01 | 7×24h remote monitoring and fault diagnosis; support remote firmware upgrade and parameter configuration |
5. System Schematic Diagram & Working Principle
5.1 PC-class ATS Cabinet (Mains to Generator Transfer)
Circuit Diagram
Normal Power (Mains) → Main Circuit Breaker 1 → PC-class ATS Switch → Load (UPS / Power Distribution Cabinet)
Standby Power (Generator) → Main Circuit Breaker 2 → PC-class ATS Switch → Load (UPS / Power Distribution Cabinet)
Intelligent Controller ↔ Voltage/Current Sensor ↔ ATS Switch Body ↔ Communication Module ↔ Computer Room Monitoring System
Auxiliary Power Supply → Operation Panel → Indicator Lights → Manual Transfer Switch → Emergency Stop Button
Working Process
- The intelligent controller continuously monitors voltage, frequency, phase and other parameters of two power sources.
- Under normal conditions, the ATS switch is connected to mains electricity to supply power to loads.
- Once mains power fails, the controller sends a signal to start the diesel generator.
- After the generator runs stably (adjustable delay: 0-10s), the controller issues a transfer command.
- The ATS switch transfers power from mains to generator within ≤50ms. Combined with UPS, zero-interruption power supply is realized.
- When mains power recovers, the system switches back to mains after an adjustable delay (1-5 minutes).
- The controller stops the diesel generator and resumes normal operation.
5.2 CB-class ATS Cabinet (Mains to Mains Transfer)
Circuit Diagram
Normal Power (Mains 1) → CB-class ATS Switch (Built-in Circuit Breaker 1) → Load (Power Distribution Cabinet / IT Equipment)
Standby Power (Mains 2) → CB-class ATS Switch (Built-in Circuit Breaker 2) → Load (Power Distribution Cabinet / IT Equipment)
Intelligent Controller ↔ Voltage/Current Sensor ↔ Communication Module ↔ Computer Room Monitoring System
Auxiliary Power Supply → Operation Panel → Indicator Lights → Manual Transfer Switch
Working Process
- The controller monitors parameters of two independent mains power sources simultaneously.
- Normally, loads are powered by Mains 1.
- When Mains 1 fails, the ATS switch immediately transfers to Mains 2 within ≤1s.
- The built-in circuit breaker provides short-circuit and overload protection, no extra protective equipment required.
- After Mains 1 recovers, the system can automatically switch back or remain on Mains 2 (configurable).
- Dual mechanical and electrical interlocks prevent simultaneous closing of two power circuits.
5.3 Bypass-type ATS Cabinet
Circuit Diagram
Normal Power → Main ATS Switch → Load
Standby Power → Main ATS Switch → Load
Bypass Switch → Manual Operating Mechanism → Load
Intelligent Controller ↔ Status Monitoring ↔ Alarm System
Working Process
- In normal operation, the main ATS switch works for power transfer while the bypass switch remains open.
- When the main ATS switch needs maintenance or breaks down, manually activate the bypass switch to supply power to loads.
- The bypass circuit can take power from normal or standby source to ensure continuous power during maintenance.
- After maintenance, switch back to the main ATS circuit via the bypass switch.
- The bypass design supports online maintenance without power cut, ideal for Class A computer rooms and critical loads.
6. Technical Parameters
6.1 PC-class ATS Cabinet (KITOZER-ATS-PC Series)
| Parameter | ATS-PC-250 | ATS-PC-630 | ATS-PC-1250 |
|---|---|---|---|
| Rated Operating Voltage | 400V AC, 3P+N | 400V AC, 3P+N | 400V AC, 3P+N |
| Rated Insulation Voltage | 660V AC | 660V AC | 660V AC |
| Rated Operating Current | 250A | 630A | 1250A |
| Rated Frequency | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz |
| Switching Time | ≤50ms | ≤50ms | ≤50ms |
| Mechanical Life | ≥10,000 times | ≥10,000 times | ≥8,000 times |
| Electrical Life | ≥2,000 times | ≥2,000 times | ≥1,500 times |
| Short-circuit Withstand Current | 50kA/1s | 65kA/1s | 80kA/1s |
| Protection Rating | IP20 | IP20 | IP20 |
| Installation Method | Floor-standing / Wall-mounted | Floor-standing | Floor-standing |
| Communication Interface | RS485, Modbus RTU | RS485, Modbus RTU/TCP | RS485, Modbus RTU/TCP, SNMP |
| Control Power | 220V AC/24V DC | 220V AC/24V DC | 220V AC/24V DC |
| Cabinet Dimension | 600×1800×800mm | 800×2000×1000mm | 1000×2200×1200mm |
6.2 CB-class ATS Cabinet (KITOZER-ATS-CB Series)
| Parameter | ATS-CB-250 | ATS-CB-630 | ATS-CB-1250 |
|---|---|---|---|
| Rated Operating Voltage | 400V AC, 3P+N | 400V AC, 3P+N | 400V AC, 3P+N |
| Rated Insulation Voltage | 660V AC | 660V AC | 660V AC |
| Rated Operating Current | 250A | 630A | 1250A |
| Rated Frequency | 50Hz/60Hz | 50Hz/60Hz | 50Hz/60Hz |
| Switching Time | ≤1s | ≤1s | ≤1.5s |
| Mechanical Life | ≥8,000 times | ≥8,000 times | ≥6,000 times |
| Electrical Life | ≥1,500 times | ≥1,500 times | ≥1,000 times |
| Short-circuit Breaking Capacity | 50kA | 65kA | 80kA |
| Protection Rating | IP20/IP30 | IP20 | IP20 |
| Installation Method | Wall-mounted / Floor-standing | Floor-standing | Floor-standing |
| Communication Interface | RS485, Modbus RTU | RS485, Modbus RTU/TCP | RS485, Modbus RTU/TCP, SNMP |
| Control Power | 220V AC/24V DC | 220V AC/24V DC | 220V AC/24V DC |
| Cabinet Dimension | 400×600×250mm | 800×2000×1000mm | 1000×2200×1200mm |
6.3 Technical Parameters of Intelligent Controller
| Item | Specifications |
|---|---|
| Control Mode | Microprocessor intelligent control; auto / manual / remote control modes available |
| Monitored Parameters | Three-phase voltage, current, frequency, phase, power factor, energy metering |
| Protection Functions | Overvoltage, undervoltage, phase loss, power loss, frequency abnormality, overload and short-circuit protection |
| Communication Interface | RS485, Modbus RTU/TCP, SNMPv3 |
| Display | 7-inch color touch screen (PC-class) / 4.3-inch color display (CB-class), resolution 800×480 |
| Data Storage | Built-in memory, stores operation data and fault records for over 1 year |
| Control Accuracy | Voltage ±0.5%, Frequency ±0.1Hz, Current ±1% |
| Transfer Delay | Adjustable: 0-10s (generator start delay), 1-5min (mains recovery delay) |
| Linkage Function | Linked with UPS, diesel generator, computer room monitoring system and fire alarm system |
| Remote Management | Remote access and control via web browser and mobile APP |
7. Application Scope
The KITOZER ATS Cabinet system is applied to various critical power scenarios with top-grade power protection:
7.1 Data Center Industry
- Cloud computing data centers, supercomputing centers (Class A power supply, zero-interruption operation)
- Financial data centers (banks, securities, insurance; secure transaction & data operation)
- Telecom data centers & edge computing nodes (7×24h non-stop operation)
- Enterprise data centers (private cloud, hybrid cloud; high reliability & scalable capacity)
7.2 Computer Room & IT Facilities
- IDC hosting computer rooms
- AI computing centers (high-density GPU deployment)
- Edge computing nodes (5G base stations, IoT data collection centers)
- Modular data centers & containerized data centers (rapid deployment)
7.3 Special Scenarios
- Medical data centers (HIS, PACS systems)
- Scientific research computing centers
- Industrial control computer rooms
- Military command centers
- Government critical computer rooms & e-government systems
8. Product Advantages
8.1 High Reliability for Business Continuity
- Dual interlock: Mechanical & electrical interlocks eliminate the risk of simultaneous closing of two power circuits.
- Ultra-fast switching: PC-class ATS switches within 50ms to realize zero-interruption power supply with UPS, meeting Class A standards.
- Strong grid adaptability: Tolerate ±15% voltage fluctuation and ±5% frequency fluctuation.
- Long service life: Mechanical life up to 10,000 times; MTBF ≥ 200,000 hours.
- Multi-layer protection: Comprehensive protection against overvoltage, undervoltage, phase loss, overload and short circuit.
8.2 Intelligent Management & Simplified O&M
- Intuitive color touch screen for real-time parameter display and one-click fault diagnosis.
- Full remote monitoring via web and mobile APP to cut O&M costs.
- Accurate energy consumption statistics to support energy-saving optimization.
- Early fault warning reduces downtime risks.
- Long-term data storage for traceability and analysis.
8.3 Flexible Adaptability for Diverse Demands
- Complete current range from 100A to 4000A covering all application scenarios.
- Multiple installation types: floor-standing, wall-mounted and withdrawable.
- Multiple transfer modes: mains-to-generator, mains-to-mains and bypass type.
- Customizable functional modules: generator control, energy metering, temperature monitoring, etc.
- Seamless integration with mainstream power and monitoring equipment.
8.4 Safety Protection
- Cabinet protection rating ≥ IP20 to prevent electric contact hazards.
- Built-in Class B/C surge protectors against lightning and grid surges.
- Emergency stop button for rapid power cut in emergencies.
- Anti-misoperation design with lockable manual switches.
- Double-door cabinet design for safe and convenient maintenance.
8.5 Energy Saving & Cost Reduction
- Low-power controller: standby power ≤ 10W.
- Intelligent power management optimizes energy utilization.
- Compatible with natural cooling systems to lower carbon emission.
- Remote O&M reduces on-site labor costs.
- Long service life cuts equipment replacement frequency and lifecycle cost.
9. Bidding Specification Parameters
9.1 Basic Performance Requirements
- Rated operating voltage: 400V AC, 3P+N; rated insulation voltage: 660V AC.
- Rated operating current ≥ 630A; short-circuit withstand current ≥ 50kA/1s.
- Switching time: ≤50ms (PC-class), ≤1s (CB-class).
- Mechanical life ≥ 10,000 times (PC-class) / ≥8,000 times (CB-class); electrical life ≥ 2,000 times.
- Cabinet protection rating ≥ IP20.
9.2 Core Component Requirements
- ATS switch: PC/CB-class automatic transfer switch with mechanical interlock, brand: KITOZER or equivalent famous brand.
- Controller: ≥7-inch color touch screen, Chinese interface, data storage & export function (storage period ≥ 1 year).
- Surge protector: nominal discharge current ≥40kA (PC-class) / ≥20kA (CB-class), Class B/C protection.
- Communication: Equipped with RS485 port and Modbus RTU/TCP; SNMPv3 module optional for remote monitoring.
- Cabinet: High-strength cold-rolled steel (thickness ≥2mm), IP20, front & rear double doors.
9.3 Intelligent Control Requirements
- Real-time monitoring of three-phase voltage, current, frequency, phase, power factor and energy consumption.
- Configurable protection functions for overvoltage, undervoltage, phase loss, frequency abnormality, overload and short circuit.
- Support linkage with UPS, generator, monitoring and fire alarm systems.
- Remote access, control, fault diagnosis and parameter configuration via web and APP.
- Early fault warning (72 hours in advance) to minimize downtime.
9.4 Reliability & Safety Requirements
- Dual mechanical & electrical interlocks.
- Voltage adaptability: 380V±15%; frequency adaptability: 50Hz±2%; lightning protection equipped.
- Support N+1 redundant configuration.
- Equipped with emergency stop button, panel lock and status indicators to prevent misoperation.
- Comply with EU RoHS and WEEE directives, eco-friendly materials adopted.
9.5 After-sales Service Requirements
- Whole machine warranty ≥3 years; key components (ATS switch, controller) warranty ≥5 years.
- 7×24h technical support; response within 4 hours and on-site service within 24 hours for first-tier cities.
- National spare parts center: standard parts delivered within 48 hours, special parts within 72 hours.
- Free system operation and maintenance training.
- 2 free routine inspections per year during warranty period.
10. Overall Solutions
10.1 Solution for Small & Medium-sized Computer Rooms (100-300㎡)
Overview
Adopt KITOZER-ATS-CB-250/CB-400 wall-mounted CB-class ATS cabinets, matched with UPS and diesel generators to meet Class A power demands with cost-effectiveness and reliability.
Core Configuration
- 1 set of KITOZER-ATS-CB-250/CB-400 ATS cabinet
- 1 set of 10-20kVA UPS system (2N redundancy)
- 1 set of 50-100kW diesel generator
- Intelligent power distribution system & computer room monitoring system
Advantages
Low investment and short deployment cycle; built-in protection simplifies power distribution; wall-mounted design saves space; remote management reduces O&M cost; zero-interruption power supply guaranteed with UPS and generator.
10.2 Solution for Large-scale Data Centers (500-2000㎡)
Overview
Deploy KITOZER-ATS-PC-630/PC-1250 floor-standing PC-class ATS cabinets with 2N redundancy, combined with free cooling modules and intelligent management platform to achieve high reliability and low PUE.
Core Configuration
- 4 sets of PC-class ATS cabinets (2 active + 2 standby)
- 2 sets of 100-200kVA UPS systems (2N redundancy)
- 2 sets of 200-400kW diesel generators (1 active + 1 standby)
- Intelligent management platform, precision power distribution system, closed cold aisle system
Advantages
Switching time ≤50ms compliant with Class A standards; 2N redundancy ensures zero downtime; intelligent platform supports energy analysis and remote O&M; PUE reduced below 1.2; easy maintenance and expansion.
10.3 Modular Data Center Solution
Overview
Integrated KITOZER ATS module combined with server cabinets, UPS, power distribution and monitoring to form a complete micro-module data center for rapid deployment and flexible expansion.
Core Configuration
- Integrated ATS module (PC-class switch, controller, protection components)
- Standard 19-inch 42U server cabinet
- Rack-mounted UPS and battery pack
- PDU and environmental monitoring system
Advantages
Factory pre-assembled, on-site installation time reduced by 80%; plug-and-play for fast commissioning; on-demand expansion; high integration saves floor space; intelligent remote O&M.
10.4 Edge Computing Node Solution
Overview
Adopt compact KITOZER-ATS-CB-250 wall-mounted ATS box, matched with small UPS and generator to provide reliable power for distributed edge nodes.
Core Configuration
- 1 set of KITOZER-ATS-CB-250 wall-mounted ATS box
- 1 set of 10kVA mini UPS
- 1 set of 50kW mini diesel generator
- Intelligent monitoring module & precision PDU
Advantages
Compact wall-mounted structure saves space; low cost for large-scale deployment; remote management minimizes on-site work; low power consumption reduces operation cost; zero-interruption power supply for edge services.
11. Application Cases
11.1 Cloud Computing Data Center Project
Background: A leading cloud service provider built a large data center with 5,000 servers, requiring Class A zero-interruption operation and PUE<1.3.
Solution: 8 sets of KITOZER-ATS-PC-1250 (4 active + 4 standby, 2N redundancy), matched with 200kVA UPS and 400kW generators, centralized management via intelligent platform.
Effect: Power availability reaches 99.999%; switching time ≤50ms without server reboot; O&M manpower cut by 50%; PUE down to 1.25, annual power saving about 8 million RMB.
11.2 Core Computer Room Renovation for Financial Institution
Background: A state-owned bank upgraded its legacy computer room to Class A standard without service interruption.
Solution: 4 sets of KITOZER-ATS-PC-630 (2 active + 2 standby), phased online renovation.
Effect: Power reliability upgraded to 99.999%; trading system kept uninterrupted; O&M efficiency increased by 60%; annual O&M cost saved about 1.2 million RMB.
11.3 AI Computing Center Project
Background: An AI company built a GPU training center with 200 servers (15kW per cabinet) requiring continuous power supply.
Solution: 2 sets of KITOZER-ATS-PC-630 (1 active + 1 standby), matched with 100kVA UPS and 200kW generators.
Effect: Stable power for GPU clusters without reboot; computing efficiency increased by 20%; annual power saving about 500,000 RMB.
11.4 Modular 5G Edge Data Center Project
Background: A telecom operator deployed containerized modular data centers for 5G edge nodes, requiring fast delivery and remote management.
Solution: KITOZER integrated ATS modules for 10 micro-modules.
Effect: Full deployment completed within 30 days; stable outdoor operation with IP20; unattended remote O&M; PUE<1.35 meeting green data center standards.
12. Keywords & SEO & Tags
12.1 Search Keywords
Computer room ATS cabinet solution, KITOZER ATS cabinet, data center dual power transfer system, PC-class ATS cabinet, CB-class ATS cabinet, automatic transfer switch cabinet, mains-generator transfer cabinet, computer room power distribution solution, modular data center ATS cabinet, edge computing ATS box
12.2 SEO Optimization
- Title: KITOZER Computer Room ATS Cabinet Solution | Data Center Dual Power Transfer System | Zero-interruption Power Supply
- Meta Description: KITOZER ATS cabinet solutions are specially designed for data centers. Equipped with PC/CB-class automatic transfer switches with switching time ≤50ms, it realizes zero-interruption power supply together with UPS, suitable for all kinds of critical power environments.
- Keyword Layout: Distribute keywords reasonably in title, subtitles and body content with density of 2%-3%.
- Content Optimization: Provide detailed technical parameters, application cases and solutions to improve content value.
- Link Optimization: Internal links to related product pages; external links to authoritative industry standards and websites.
12.3 Tags
#ComputerRoomATSCabinet #DataCenterPowerDistribution #DualPowerTransfer #KITOZER #ZeroInterruptionPowerSupply #PCClassATS #CBClassATS #MainsGeneratorTransfer #ModularDataCenter #EdgeComputing