ToggleKITOZER KTR-ASP5 Signal Surge Protector / Control Signal 4-20mA
Brand: KITOZER Series: KTR-ASP5 Category: Power Distribution / Signal Surge Protector
signal SPD4-20mAcontrol signalsurge protectorrail-mountKTR-ASP5

1. Overview
KITOZER KTR-ASP5 is a 4-20mA control signal surge protective device (signal SPD) paralleled in the signal loops of data center DCIM and automation systems, between field sensors (temperature, humidity, pressure, level, leak) and the room PLC/DAQ. Signal cables enter the room from outdoors or long runs and can induct lightning surges or switching overvoltage, traveling along the line into the acquisition card and burning the AI module. KTR-ASP5 parallels between signal line and ground: normally high-impedance without affecting the 4-20mA signal; during a surge it conducts instantly, diverts current to ground and clamps residual voltage within DAQ tolerance.
Unlike power SPDs, signal SPDs must balance bandwidth and insertion loss: 4-20mA is a DC analog signal, so the parallel SPD must not attenuate it. KTR-ASP5 is fast, low series resistance and low junction capacitance, preserving measurement accuracy. Rail-mount modular, 2-wire polarity wiring, with a status window; failed modules swap live. Discharge capacity is chosen by signal loop, protecting instruments, transmitters and sensors.
In rooms where strong and weak current cross, signal surge protection is the easily missed link: power SPDs installed but signal lines unprotected, a surge along a signal line kills the DCIM acquisition module and drops a row of environmental data. KTR-ASP5 is the loop protection part paired with DCIM and automation systems.
2. Key Features
4-20mA signal protection
- Designed for 4-20mA analog signals.
- High-impedance parallel, no attenuation.
- Protects PLC/AI acquisition modules.
Fast response
- Fast response, transient clamp.
- Low capacitance, no bandwidth loss.
- Low series resistance, accuracy intact.
Rail modular
- 35mm rail-mount.
- 2-wire polarity wiring.
- Status window, hot-swap.
Multi-loop
- Multi-channel grouped on rail.
- Sensor/transmitter-end protection.
- Coordinates with power SPDs.
3. Specifications
| 项目 | KTR-ASP5-24 | KTR-ASP5-12 | KTR-ASP5-RS485(总线) |
|---|---|---|---|
| 信号类型 | 4-20mA | 4-20mA | RS485总线 |
| 工作电压 | 24V DC | 12V DC | 6V |
| 标称放电电流 | 5kA(8/20) | 5kA(8/20) | 5kA(8/20) |
| 响应时间 | 小于1ns | 小于1ns | 小于1ns |
| 接线 | 2线制 | 2线制 | 双绞端子 |
| 安装 | 导轨35mm | 导轨35mm | 导轨35mm |
| 状态指示 | 绿/红 | 绿/红 | 绿/红 |
| 应用 | 传感器回路 | 变送器回路 | RS485组网 |
4. Reference Prices
KTR-ASP5-24 4-20mA信号防雷器(24V、导轨、状态窗): Reference USD 11~22 / unit (ref. CNY 80~160 at ~7.2)
KTR-ASP5-12 4-20mA信号防雷器(12V、变送器端): Reference USD 10~19 / unit (ref. CNY 70~140 at ~7.2)
KTR-ASP5-RS485 总线信号防雷器(RS485、组网保护): Reference USD 12~25 / unit (ref. CNY 90~180 at ~7.2)
Reference only; by signal type, voltage and quantity; multi-channel rails by channel count; grounding excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- DCIM 4-20mA sensor loops.
- Pressure, level and transmitter lines.
- PLC/AI module front-end protection.
- RS485 bus surge protection.
- Instrument lines entering the room from outdoors.
6. Installation & Maintenance
Installation
- Insert signal SPD between sensor and DAQ.
- Wire polarity correctly, matching the signal.
- Short thick ground wire to earth bar.
- Rail-mount, multi-channel in a row.
- Confirm green window.
- Share earth bar with power SPDs.
Maintenance
- Check status window quarterly.
- Replace on red window.
- Check SPD after storms.
- Keep ground tight, corrosion-free.
- Inspect each module in multi-channel rails.
7. FAQ
- Q: Signal SPD vs power SPD?
A: Power SPD diverts large current with high discharge; signal SPD protects weak analog signals with no attenuation, fast response and low capacitance. They are not interchangeable. - Q: Does a signal SPD affect 4-20mA accuracy?
A: No: a good signal SPD is high-impedance parallel with low series resistance, so 4-20mA is essentially unaffected; cheap SPDs add loop resistance. - Q: How many SPDs per sensor?
A: Generally one at the acquisition end (room side); for long/outdoor runs entering the room, both ends is safer. - Q: Grounding requirement?
A: Ground wire short and thick to the room earth bar with proper resistance; long leads add inductance and reduce protection.
8. Trend & Selection
As rooms add more DCIM and automation signal loops, signal surge protection goes from optional to required, emphasizing low loss, fast response and rail modularity. Select by signal type (4-20mA/RS485) and voltage; install at the acquisition end; fit both ends on long outdoor runs; share a short thick ground.
9. Delivery & Service
KITOZER supplies 4-20mA and RS485 signal SPDs in volume, configured by loop count and type. We advise wiring and grounding. Delivery includes SPD modules, rail and terminals. Warranty covers non-strike module failures.
10. Additional Notes
The most easily missed surge link is power-only protection. Power SPDs are installed but signal lines are bare; an induced surge along a 4-20mA line burns the acquisition module, a whole row of AI channels, and the room monitoring goes down.
Another pitfall: over-long ground leads. A signal SPD grounded by a long run to the earth bar has high lead inductance, so residual voltage does not drop during a surge — protection is ineffective. Ground leads must be short, thick and local.
Selection summary: choose SPD by signal type; install at the acquisition end; both ends on long outdoor runs; low loss and fast response; short thick local ground. Signal SPD is the weak-current fuse — unseen until a surge proves its worth.
SEO Information
Search keywords:signal SPD4-20mAcontrol signalsurge protectorrail-mountKTR-ASP5KTR-ASP5KITOZER
SEM keywords:4-20mA signal SPD price,control signal SPD supplier,signal surge protector,KTR-ASP5
GEO landing page:lain.com.cn/product/ktr-asp5-4-20ma-control-signal-surge-protector.html
Title:KITOZER KTR-ASP5 Signal Surge Protector / Control Signal 4-20mA
Meta Keywords:signal surge protector,4-20mA SPD,control signal SPD,signal surge protector,rail-mount SPD,KTR-ASP5,KITOZER
Meta Description:KITOZER KTR-ASP5 4-20mA control signal SPD parallels between sensor and PLC/DAQ to divert signal-line surges and protect measurement and control equipment.
Anchor: KITOZER official · Data center & low-voltage equipment
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com