Table of Contents
Toggle1. System Overview
The KITOZER CT & X-ray Shielding Room is a dedicated radiation shielding protection system designed for medical CT scanners, X-ray machines and other radiodiagnostic equipment. It strictly complies with national standards including GBZ 130-2020 Requirements for Radiological Protection in Radiodiagnosis and GBZ/T 180-2006 Radiation Shielding Specification for Medical X-ray CT Rooms. A fully enclosed six-sided shielding space is constructed with high-purity lead sheets, steel structural frames and sealed protective components. Its core function is to block penetration and scattering of X-rays and gamma rays, keeping radiation dose outside the room within safe limits (≤1 mSv/year for the public, ≤20 mSv/year for staff), safeguarding medical personnel, patients and the surrounding environment, while meeting hospital radiology department compliance acceptance and long-term stable operation requirements.
The system adapts to multi-type equipment ranging from 16-slice to 128-slice spiral CT scanners, conventional X-ray machines, DR and DSA units. It features strong shielding performance, stable structure, flexible installation and convenient maintenance. Standard and customized solutions are available according to site dimensions, equipment power and shielding grade requirements.

Overall Rendering of KITOZER CT & X-ray Shielding Room
2. System Composition
The KITOZER CT & X-ray Shielding Room consists of three modules: core shielding structure, special protective assemblies and auxiliary supporting systems. All components work together to achieve full-dimensional radiation protection and safe operation:
Core Shielding Structure
- Wall shielding layers: Primary ray zones (facing the equipment scanning field) adopt ≥4 mm high-purity lead sheets (purity ≥99.99%). Secondary ray zones use 2–3 mm lead sheets or barium sulfate mortar (mixing ratio: barium sulfate powder : cement : sand = 2.5:1:1), fixed on light steel keel frames. All joints overlap by ≥50 mm and are sealed via welding plus lead glue.
- Floor shielding layers: The area directly beneath the equipment is fully covered with ≥4 mm lead sheets (welded joints); other areas use 2 mm lead sheets or 30 mm thick barium sulfate mortar, topped with anti-static PVC flooring.
- Ceiling shielding layers: Zones with human activity above require shielding equivalent to ≥4 mm lead, constructed with lead sheets + light steel keel suspended ceilings. Joints form a closed-loop shield connecting walls and floors.
- Steel structural frames: Main keels are 60×4 mm channel steel; secondary keels are 40×4 mm angle steel, fixed to the main building via expansion bolts. Overall flatness error ≤2 mm/m² with strong seismic stability.
Special Protective Assemblies
- Lead-lined protective doors: Door bodies lined with ≥4 mm lead sheets reinforced by steel frames, lead equivalent ≥4 mmPb. Door width ≥1.4 m (threshold-free), equipped with automatic door closers and equipment interlocks (equipment cannot start if the door is unclosed). Door gap ≤1 mm, fitted with lead rubber sealing strips to prevent ray leakage.
- Lead glass observation windows: ≥18 mm medical lead glass (lead equivalent ≥4 mmPb, light transmittance ≥85%), fully wrapped with lead plates around the perimeter and overlapping wall lead sheets by ≥100 mm. Joints filled with lead rubber strips for sealing.
- Penetration shielding components: A labyrinth lead baffle structure for cables, water pipes, ventilation ducts and other wall penetrations. Lead sheets cover all gaps and extend ≥5 cm, fitted with dedicated lead sleeves and waveguide windows to avoid ray leakage.
Auxiliary Supporting Systems
- Warning & interlock system: Ionizing radiation warning signs, audible-visual alarm lights and operating status indicators installed at the room entrance, interlocked with protective doors and equipment. Red lights activate with alarms during operation.
- Ventilation & lighting system: Special shielding waveguide windows (for ventilation without ray leakage) and explosion-proof LED lights to guarantee adequate air exchange and illumination inside the room.
- Earthing system: Independent earthing electrodes with earthing resistance ≤4 Ω, conducting induced current from shielding layers to the ground to avoid static accumulation and electromagnetic interference.
- Monitoring & call system: A monitoring display and two-way intercom installed in the operation area to observe patient status and enable doctor-patient communication in real time.
3. System Classification

Structural Drawing of CT & X-ray Shielding Room
The KITOZER CT & X-ray Shielding Room is categorized by three dimensions: shielding grade, structural form and installation method, adapting to diverse scenario demands.
Classification by Shielding Grade (Basic / Standard / Reinforced)
- Basic Grade (Entry-level) Applicable to conventional X-ray machines and CT scanners below 16-slice. Main wall lead equivalent ≥2.5 mmPb, secondary wall ≥1.5 mmPb, protective door ≥2.5 mmPb, observation window ≥2.5 mmPb. Ideal for small radiology departments in primary hospitals and community health service centers.
- Standard Grade (Mid-tier) Applicable to 64-slice spiral CT and DR units. Main wall lead equivalent ≥3.5 mmPb, secondary wall ≥2.5 mmPb, protective door ≥3.5 mmPb, observation window ≥3.5 mmPb. Suitable for general radiology departments in secondary hospitals and specialized hospitals.
- Reinforced Grade (High-end) Applicable to 128-slice and above spiral CT, DSA, PET-CT and other high-power equipment. Main wall lead equivalent ≥4.5 mmPb, secondary wall ≥3.5 mmPb, protective door ≥4.5 mmPb, observation window ≥4.5 mmPb. Designed for key radiology departments in Grade A tertiary hospitals and large medical centers.
Classification by Structural Form
- Fixed shielding room: Integrally welded steel frame + lead sheet construction with fully enclosed six-sided shielding. Superior shielding performance and stability, service life ≥20 years. For permanent CT examination rooms in hospital radiology departments.
- Modular shielding room: Prefabricated wall, floor and ceiling panels assembled on-site. Flexible installation, detachable and relocatable later. Suitable for space-restricted sites, reconstruction projects or rooms requiring relocation.
Classification by Installation Method
- Embedded shielding room: Shielding layers embedded inside original building walls, floors and ceilings without occupying extra space, neat and aesthetic. For newly built hospital rooms or existing room renovations.
- Independent shielding room: Standalone steel frame built directly inside existing rooms without damaging the original building structure. Short construction cycle (7–15 days), ideal for old room renovations and temporary radiology examination sites.
4. System Schematic Diagram

Factory Production Workshop Shot
plaintext
┌─────────────────────────────────────────┐
│ Outside Room (Safe Zone) │
│ (Radiation Dose ≤0.25 μSv/h, compliant with public safety limits)
└───────────────┬───────────────────────┘
│
┌───────────────▼───────────────────────┐
│ Fully enclosed six-sided shielding layer (lead sheets + steel frame)
│ ┌─────────┐ ┌─────────┐ ┌─────────┐ │
│ │ Walls │ │ Ceiling │ │ Floor │ │
│ │(≥4 mm lead sheet for main walls)│(≥4 mm lead sheet)│(≥4 mm lead sheet)│
│ └─────────┘ └─────────┘ └─────────┘ │
│ ┌─────────┐ ┌─────────┐ │
│ │Lead-lined Door│Lead Glass Observation Window│
│ │(≥4 mm lead sheet)│(≥18 mm lead glass)│
│ └─────────┘ └─────────┘ │
│ ┌─────────┐ ┌─────────┐ ┌─────────┐ │
│ │Penetration Shielding Parts│Shielding Waveguide Window│Earthing System│
│ │ │ │ │ │ (≤4 Ω) │ │
│ └─────────┘ └─────────┘ └─────────┘ │
│ Inside Room (Radiation Source Zone) │
│ (CT Scanner / X-ray Machine generating high-energy X-rays during operation)
└─────────────────────────────────────────┘
Schematic Explanation
The system centers on a fully enclosed six-sided shielding layer. Leveraging lead’s high atomic number (Z=82) and high density (11.34 g/cm³), X-ray energy is absorbed via photoelectric effect and Compton scattering to block ray penetration and scattering. Weak points including protective doors, observation windows and wall penetrations are sealed with dedicated shielding assemblies to form a closed-loop shield. The earthing system diverts induced current, while the warning interlock system ensures operational safety, ultimately achieving full containment of internal radiation sources and safe radiation levels outside the room.
5. Complete System Configuration List (KITOZER Brand, 3 Grades: Basic / Standard / Reinforced)
5.1 Basic Grade Configuration (Basic Model, for Conventional X-ray / <16-slice CT)
表格
| No. | Product Name | Model & Specs | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Wall Lead Sheet | KITOZER-PB2.5 | Purity ≥99.99%, thickness 2.5 mm, 1000×2000 mm, lead equivalent 2.5 mmPb | On-demand | ㎡ | KITOZER | For primary ray walls, overlap ≥50 mm |
| 2 | Wall Lead Sheet | KITOZER-PB1.5 | Purity ≥99.99%, thickness 1.5 mm, 1000×2000 mm, lead equivalent 1.5 mmPb | On-demand | ㎡ | KITOZER | For secondary ray walls, overlap ≥50 mm |
| 3 | Floor Lead Sheet | KITOZER-PB2.5 | Purity ≥99.99%, thickness 2.5 mm, 1000×2000 mm, lead equivalent 2.5 mmPb | On-demand | ㎡ | KITOZER | Full coverage under equipment, welded joints |
| 4 | Ceiling Lead Sheet | KITOZER-PB2.5 | Purity ≥99.99%, thickness 2.5 mm, 1000×2000 mm, lead equivalent 2.5 mmPb | On-demand | ㎡ | KITOZER | For zones with human activity above |
| 5 | Light Steel Keel Frame | KITOZER-STEEL-50 | Main keel 60×4 mm channel steel, secondary keel 40×4 mm angle steel, galvanized anti-corrosion, flatness ≤2 mm/m² | On-demand | Set | KITOZER | Support frame for walls/floors/ceilings |
| 6 | Basic Lead-lined Protective Door | KITOZER-DOOR-2.5 | 1500×2100 mm, lined with 2.5 mm lead sheet, steel frame, 2.5 mmPb equivalent, automatic closer, equipment interlock, gap ≤1 mm | 1 | Leaf | KITOZER | Threshold-free, manual/dual electric mode |
| 7 | Basic Lead Glass Observation Window | KITOZER-GLASS-2.5 | 800×600 mm, 15 mm thick, 2.5 mmPb equivalent, light transmittance ≥80%, lead wrapped perimeter | 1 | Leaf | KITOZER | Overlap wall lead sheets ≥100 mm |
| 8 | Barium Sulfate Mortar | KITOZER-BARIUM-2.5 | Mix ratio 2.5:1:1, compressive strength ≥20 MPa, 2.5 mmPb equivalent at 30 mm thickness | On-demand | Ton | KITOZER | Auxiliary shielding for secondary ray walls/floors |
| 9 | Lead Penetration Sleeve | KITOZER-PIPE-50 | Inner diameter 50 mm, wall thickness 2.5 mm, purity ≥99.99%, 2.5 mmPb equivalent, length 300 mm | On-demand | Piece | KITOZER | Shielding for cable/wall pipe penetrations |
| 10 | Basic Shielding Waveguide Window | KITOZER-WINDOW-100 | 300×300 mm, airflow ≥100 m³/h, shielding attenuation ≥30 dB, aluminum frame + lead shielding mesh | 2 | Piece | KITOZER | Room ventilation, prevents ray leakage |
| 11 | Ionizing Radiation Warning Light | KITOZER-LIGHT-LED | Red LED, 220 V, 10 W, interlocked with door/equipment, lights up during operation | 1 | Set | KITOZER | Warning at room entrance |
| 12 | Two-way Call Intercom | KITOZER-INTERCOM-200 | Max distance ≤200 m, noise reduction, 220 V | 1 | Set | KITOZER | Communication between operation area and room interior |
| 13 | Earthing System | KITOZER-GROUND-4 | Independent earthing electrode, resistance ≤4 Ω, copper conductor, 50 m length | 1 | Set | KITOZER | Shield earthing, anti-static |
| 14 | Anti-static PVC Flooring | KITOZER-PVC-1.0 | 2.0 mm thickness, anti-static resistance 10⁶–10⁹ Ω, anti-slip wear-resistant, grey | On-demand | ㎡ | KITOZER | Room floor paving |
5.2 Standard Grade Configuration (Standard Model, for 64-slice CT / DR)
表格
| No. | Product Name | Model & Specs | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Wall Lead Sheet | KITOZER-PB3.5 | Purity ≥99.99%, thickness 3.5 mm, 1000×2000 mm, lead equivalent 3.5 mmPb | On-demand | ㎡ | KITOZER | Primary ray walls, overlap ≥50 mm |
| 2 | Wall Lead Sheet | KITOZER-PB2.5 | Purity ≥99.99%, thickness 2.5 mm, 1000×2000 mm, lead equivalent 2.5 mmPb | On-demand | ㎡ | KITOZER | Secondary ray walls, overlap ≥50 mm |
| 3 | Floor Lead Sheet | KITOZER-PB3.5 | Purity ≥99.99%, thickness 3.5 mm, 1000×2000 mm, lead equivalent 3.5 mmPb | On-demand | ㎡ | KITOZER | Full coverage under equipment, welded joints |
| 4 | Ceiling Lead Sheet | KITOZER-PB3.5 | Purity ≥99.99%, thickness 3.5 mm, 1000×2000 mm, lead equivalent 3.5 mmPb | On-demand | ㎡ | KITOZER | Zones with human activity above |
| 5 | Light Steel Keel Frame | KITOZER-STEEL-75 | Main keel 80×5 mm channel steel, secondary keel 50×5 mm angle steel, hot-dip galvanized anti-corrosion, flatness ≤1.5 mm/m² | On-demand | Set | KITOZER | Wall/floor/ceiling support |
| 6 | Standard Lead-lined Protective Door | KITOZER-DOOR-3.5 | 1600×2200 mm, lined with 3.5 mm lead sheet, stainless steel frame, 3.5 mmPb equivalent, automatic closer, interlock, gap ≤0.8 mm, thick lead rubber strips | 1 | Leaf | KITOZER | Threshold-free, electric priority + manual backup |
| 7 | Standard Lead Glass Observation Window | KITOZER-GLASS-3.5 | 1000×800 mm, 18 mm thick, 3.5 mmPb equivalent, light transmittance ≥85%, anti-reflection coating, lead wrapped perimeter | 1 | Leaf | KITOZER | Overlap wall lead sheets ≥120 mm |
| 8 | Barium Sulfate Mortar | KITOZER-BARIUM-3.5 | Mix ratio 3:1:1, compressive strength ≥25 MPa, 3.5 mmPb equivalent at 40 mm thickness | On-demand | Ton | KITOZER | Auxiliary shielding for secondary ray zones |
| 9 | Lead Penetration Sleeve | KITOZER-PIPE-80 | Inner diameter 80 mm, wall thickness 3.5 mm, purity ≥99.99%, 3.5 mmPb equivalent, length 400 mm | On-demand | Piece | KITOZER | Cable/water pipe penetration shielding |
| 10 | Standard Shielding Waveguide Window | KITOZER-WINDOW-200 | 400×400 mm, airflow ≥200 m³/h, shielding attenuation ≥40 dB, stainless steel frame + high-density lead mesh | 2 | Piece | KITOZER | Ventilation with ray leakage prevention |
| 11 | Audible-visual Radiation Alarm Light | KITOZER-ALARM-LED | Red LED + buzzer, 220 V, 15 W, interlocked with door/equipment, simultaneous light & sound alert during operation | 1 | Set | KITOZER | Entrance warning, enhanced safety |
| 12 | HD Monitoring Display | KITOZER-MONITOR-1080 | 21.5-inch 1080P, IP65 waterproof, 220 V | 1 | Unit | KITOZER | Real-time room observation in operation area |
| 13 | Two-way HD Video Intercom | KITOZER-INTERCOM-500 | Max distance ≤500 m, HD audio & video, dust/noise resistant, 220 V | 1 | Set | KITOZER | Two-way visual communication |
| 14 | High-efficiency Earthing System | KITOZER-GROUND-2 | Independent earthing electrode, resistance ≤2 Ω, copper conductor, 80 m length, anti-corrosion treatment | 1 | Set | KITOZER | Anti-static & anti-electromagnetic interference |
| 15 | Anti-static PVC Flooring | KITOZER-PVC-2.0 | 3.0 mm thickness, anti-static resistance 10⁶–10⁹ Ω, anti-slip, wear-resistant, antibacterial, blue | On-demand | ㎡ | KITOZER | Easy-to-clean room flooring |
5.3 Reinforced Grade Configuration (Reinforced Model, for 128-slice CT / DSA / PET-CT)
表格
| No. | Product Name | Model & Specs | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Wall Lead Sheet | KITOZER-PB4.5 | Purity ≥99.994%, thickness 4.5 mm, 1200×2400 mm, lead equivalent 4.5 mmPb, double-sided anti-oxidation coating | On-demand | ㎡ | KITOZER | Primary ray walls, overlap ≥60 mm |
| 2 | Wall Lead Sheet | KITOZER-PB3.5 | Purity ≥99.994%, thickness 3.5 mm, 1200×2400 mm, lead equivalent 3.5 mmPb, double-sided anti-oxidation coating | On-demand | ㎡ | KITOZER | Secondary ray walls, overlap ≥60 mm |
| 3 | Floor Lead Sheet | KITOZER-PB4.5 | Purity ≥99.994%, thickness 4.5 mm, 1200×2400 mm, lead equivalent 4.5 mmPb, welded joints sealed with lead glue | On-demand | ㎡ | KITOZER | Seamless full coverage under equipment |
| 4 | Ceiling Lead Sheet | KITOZER-PB4.5 | Purity ≥99.994%, thickness 4.5 mm, 1200×2400 mm, lead equivalent 4.5 mmPb, double-sided anti-oxidation coating | On-demand | ㎡ | KITOZER | Fully enclosed for overhead active zones |
| 5 | Heavy-duty Steel Frame | KITOZER-STEEL-100 | Main keel 100×6 mm channel steel, secondary keel 60×6 mm angle steel, hot-dip galvanized + anti-corrosion coating, flatness ≤1 mm/m², seismic grade 8 | On-demand | Set | KITOZER | High-strength support for walls/floors/ceilings |
| 6 | Reinforced Lead-lined Sliding Door | KITOZER-DOOR-4.5 | 1800×2300 mm, lined with 4.5 mm lead sheet, 304 stainless steel frame, 4.5 mmPb equivalent, electric sliding, interlock, gap ≤0.5 mm, double lead rubber strips, emergency manual release | 1 | Leaf | KITOZER | Threshold-free, electric priority with emergency manual mode |
| 7 | Reinforced Explosion-proof Lead Glass Window | KITOZER-GLASS-4.5 | 1200×1000 mm, 20 mm thick, 4.5 mmPb equivalent, light transmittance ≥90%, high-strength explosion-proof, anti-radiation reflection coating, lead wrapped perimeter | 1 | Leaf | KITOZER | Overlap wall lead sheets ≥150 mm, scratch & explosion resistant |
| 8 | High-density Barium Sulfate Mortar | KITOZER-BARIUM-4.5 | Mix ratio 3.5:1:1, compressive strength ≥30 MPa, 4.5 mmPb equivalent at 50 mm thickness, eco-friendly radiation-free | On-demand | Ton | KITOZER | High-strength auxiliary shielding for secondary zones |
| 9 | Labyrinth Penetration Shielding Assembly | KITOZER-SHIELD-100 | Inner diameter 100 mm, wall thickness 4.5 mm, purity ≥99.994%, 4.5 mmPb equivalent, labyrinth structure, length 500 mm | On-demand | Set | KITOZER | Multi-layer shielding for cable/wall pipe penetrations to eliminate leakage |
| 10 | Reinforced Shielding Waveguide Window | KITOZER-WINDOW-300 | 500×500 mm, airflow ≥300 m³/h, shielding attenuation ≥50 dB, 304 stainless steel frame + multi-layer high-density lead mesh, anti-clogging design | 2 | Piece | KITOZER | Premium ventilation with ultimate ray leakage prevention |
| 11 | Intelligent Audible-visual Interlock Alarm System | KITOZER-SMART-ALARM | High-bright red LED + loud buzzer + voice broadcast, 220 V, 20 W, interlocked with door/equipment/monitor, remote alarm push notification | 1 | Set | KITOZER | Multi-layer safety warning at room entrance |
| 12 | 4K Panoramic Monitoring System | KITOZER-CCTV-4K | 27-inch 4K monitor, 360° panoramic camera, IP68 waterproof/dustproof, night vision, 220 V, 30-day video storage | 1 | Set | KITOZER | Dead-angle-free room observation in operation area |
| 13 | Two-way 4K Video Intercom System | KITOZER-INTERCOM-1000 | Max distance ≤1000 m, 4K HD audio & video, dust/explosion resistant, 220 V, remote call function | 1 | Set | KITOZER | Premium two-way visual communication |
| 14 | Ultra-high-efficiency Earthing System | KITOZER-GROUND-1 | Independent earthing electrode, resistance ≤1 Ω, tin-plated copper conductor, 100 m length, anti-corrosion & lightning protection, multi-point earthing | 1 | Set | KITOZER | Ultimate anti-static & anti-interference performance |
| 15 | Premium Anti-static PVC Flooring | KITOZER-PVC-3.0 | 4.0 mm thickness, anti-static resistance 10⁶–10⁹ Ω, anti-slip, wear-resistant, antibacterial, flame retardant, grey seamless splicing | On-demand | ㎡ | KITOZER | Durable, easy-to-clean room flooring |
6. Full Product Technical Parameters

Shielding Room Layout Schematic
6.1 Lead Sheet Series (KITOZER-PB)
- Material: High-purity electrolytic lead, purity ≥99.99% (Basic/Standard), ≥99.994% (Reinforced)
- Thickness specs: 1.5 mm, 2.5 mm, 3.5 mm, 4.5 mm, tolerance ≤±0.1 mm
- Dimension specs: 1000×2000 mm (Basic/Standard), 1200×2400 mm (Reinforced), custom cutting available
- Lead equivalent: 1.5 mmPb, 2.5 mmPb, 3.5 mmPb, 4.5 mmPb, blocks X-ray energy ≥120 keV
- Physical properties: Density 11.34 g/cm³, tensile strength ≥16 MPa, elongation ≥45%, crack-free, bubble-free, impurity-free
- Surface treatment: Single-sided anti-oxidation coating (Basic/Standard), double-sided anti-oxidation coating (Reinforced), corrosion-resistant, discoloration-proof
6.2 Light / Heavy-duty Steel Frame Series (KITOZER-STEEL)
- Material: Q235B channel steel & angle steel, hot-dip galvanized anti-corrosion (Basic/Standard), hot-dip galvanized + extra anti-corrosion coating (Reinforced)
- Specs:
- Basic: Main keel 60×4 mm channel steel, secondary keel 40×4 mm angle steel
- Standard: Main keel 80×5 mm channel steel, secondary keel 50×5 mm angle steel
- Reinforced: Main keel 100×6 mm channel steel, secondary keel 60×6 mm angle steel
- Flatness: ≤2 mm/m² (Basic), ≤1.5 mm/m² (Standard), ≤1 mm/m² (Reinforced)
- Seismic grade: Grade 7 (Basic/Standard), Grade 8 (Reinforced)
- Connection: Fixed via expansion bolts + reinforced welding, stable and loose-proof
6.3 Lead-lined Protective Door Series (KITOZER-DOOR)

Protective Door On-site Photo
- Standard door dimensions: 1500×2100 mm (Basic), 1600×2200 mm (Standard), 1800×2300 mm (Reinforced), custom sizes available
- Lined lead thickness: 2.5 mm (Basic), 3.5 mm (Standard), 4.5 mm (Reinforced), matching corresponding lead equivalent
- Door frame material: Steel frame (Basic), stainless steel frame (Standard), 304 stainless steel frame (Reinforced)
- Door gap: ≤1 mm (Basic), ≤0.8 mm (Standard), ≤0.5 mm (Reinforced)
- Drive mode: Automatic door closer (Basic), electric primary + manual backup (Standard), electric sliding + emergency manual release (Reinforced)
- Interlock function: Equipment interlock; radiology equipment cannot activate if protective door is unclosed to prevent misoperation
- Sealing strips: Standard lead rubber strips (Basic), thickened lead rubber strips (Standard), double-layer lead rubber sealing strips (Reinforced) for leak-proof sealing
6.4 Lead Glass Observation Window Series (KITOZER-GLASS)
- Standard sizes: 800×600 mm (Basic), 1000×800 mm (Standard), 1200×1000 mm (Reinforced), custom sizes available
- Thickness: 15 mm (Basic), 18 mm (Standard), 20 mm (Reinforced)
- Lead equivalent: 2.5 mmPb (Basic), 3.5 mmPb (Standard), 4.5 mmPb (Reinforced)
- Light transmittance: ≥80% (Basic), ≥85% (Standard), ≥90% (Reinforced)
- Performance: Anti-reflection coating (Standard/Reinforced), high-strength explosion-proof (Reinforced), aging-resistant, anti-yellowing
- Installation: Perimeter fully wrapped with lead sheets, overlapping wall lead sheets ≥100 mm (Basic), ≥120 mm (Standard), ≥150 mm (Reinforced), sealed joints
6.5 Barium Sulfate Mortar Series (KITOZER-BARIUM)
- Mix ratios:
- Basic: Barium sulfate powder : cement : sand = 2.5:1:1
- Standard: Barium sulfate powder : cement : sand = 3:1:1
- Reinforced: Barium sulfate powder : cement : sand = 3.5:1:1
- Lead equivalent: 2.5 mmPb at 30 mm thickness (Basic), 3.5 mmPb at 40 mm thickness (Standard), 4.5 mmPb at 50 mm thickness (Reinforced)
- Compressive strength: ≥20 MPa (Basic), ≥25 MPa (Standard), ≥30 MPa (Reinforced)
- Environmental performance: Radiation-free, non-toxic, compliant with medical environmental standards
- Construction performance: Layered pouring (≤100 mm per layer), fully cured before next layer application, crack-resistant
6.6 Penetration Shielding Components (Lead Sleeve / Labyrinth, KITOZER-PIPE/SHIELD)
- Material: High-purity electrolytic lead, purity ≥99.99%, wall thickness ≥2.5 mm
- Specs:
- Basic: Inner diameter 50 mm, length 300 mm
- Standard: Inner diameter 80 mm, length 400 mm
- Reinforced: Inner diameter 100 mm, length 500 mm, labyrinth structure
- Lead equivalent: 2.5 mmPb (Basic), 3.5 mmPb (Standard), 4.5 mmPb (Reinforced)
- Performance: Prevents ray leakage, adapts to cable, water pipe and ventilation duct wall penetrations with strong sealing performance
6.7 Shielding Waveguide Window Series (KITOZER-WINDOW)
- Standard sizes: 300×300 mm (Basic), 400×400 mm (Standard), 500×500 mm (Reinforced)
- Airflow capacity: ≥100 m³/h (Basic), ≥200 m³/h (Standard), ≥300 m³/h (Reinforced)
- Shielding attenuation: ≥30 dB (Basic), ≥40 dB (Standard), ≥50 dB (Reinforced)
- Frame material: Aluminum alloy (Basic), stainless steel (Standard), 304 stainless steel (Reinforced)
- Shield mesh: Single-layer lead mesh (Basic), high-density lead mesh (Standard), multi-layer high-density lead mesh (Reinforced), anti-clogging design
6.8 Warning / Alarm / Monitoring / Intercom Series
- Ionizing radiation warning light / audible-visual alarm: 220 V, power 10–20 W, red LED, buzzer volume ≥80 dB, interlocked with protective door & equipment, triggered during operation
- Monitoring display / camera: 21.5–27 inch, 1080P–4K HD, IP65–IP68 waterproof/dustproof, night vision, 220 V, 30-day video storage
- Call intercom equipment: Max communication distance 200–1000 m, two-way audio / HD video, noise & dust resistant, 220 V, hospital environment compatible
6.9 Earthing System Series (KITOZER-GROUND)
- Earthing resistance: ≤4 Ω (Basic), ≤2 Ω (Standard), ≤1 Ω (Reinforced)
- Earthing electrode material: Copper (Basic), pure copper (Standard), tin-plated pure copper (Reinforced), anti-corrosion & lightning-proof
- Conductor length: 50–100 m, multi-point earthing (Reinforced) to rapidly conduct induced current from shielding layers to ground
6.10 Anti-static PVC Flooring Series (KITOZER-PVC)
- Thickness: 2.0 mm (Basic), 3.0 mm (Standard), 4.0 mm (Reinforced)
- Anti-static resistance: 10⁶–10⁹ Ω, compliant with medical anti-static standards
- Performance: Anti-slip, wear-resistant, antibacterial, flame retardant (Reinforced), seamless splicing, easy to clean
7. Full Product Application Scope
KITOZER CT & X-ray shielding room products focus on medical radiodiagnosis, and also adapt to industrial non-destructive testing and scientific research radiation protection scenarios, detailed as follows:
Medical Industry (Core Application)
- Hospital radiology departments: CT rooms, X-ray rooms, DR rooms, DSA rooms, PET-CT rooms, C-arm operating rooms in Grade A tertiary hospitals, secondary hospitals, specialized hospitals, primary hospitals and community health service centers
- Physical examination centers: Radiology examination rooms for CT and X-ray scanning in professional physical check institutions
- Dental hospitals & clinics: Dental CBCT rooms, dental X-ray rooms for small dental radiology equipment shielding
- Animal hospitals: CT & X-ray rooms in large pet hospitals and veterinary institutions to protect medical staff and animals
Industrial Non-destructive Testing
- Machinery manufacturing: X-ray flaw detection & CT inspection rooms for auto parts, aerospace components, pressure vessels and pipelines to detect internal defects
- Electronics industry: X-ray inspection rooms for semiconductor chips, circuit boards and electronic components to detect welding defects and internal structures
- Building materials industry: Non-destructive testing rooms for steel, aluminum and concrete components to guarantee product quality safety
Scientific Research & Public Safety
- Research institutes: Radiation physics laboratories and biomedical labs in universities and research institutions for radiology experiment shielding
- Entry-exit inspection & quarantine: Shielding rooms for port X-ray & CT security scanners to prevent radiation leakage from inspection equipment
- Nuclear medicine labs: Radionuclide treatment rooms and radiopharmaceutical labs with matched radiation shielding protection
8. Core Product Advantages

CT Room On-site Rendering
KITOZER CT & X-ray shielding rooms hold leading industry status in medical radiation protection with four core strengths: comprehensive product lineup, strong customization capability, premium core materials and full after-sales service system.
Full Product Line with Graded Matching & High Cost-performance
- Three shielding grades (Basic/Standard/Reinforced) cover all equipment from conventional X-ray machines to 128-slice CT and DSA, meeting diverse budget and shielding requirements
- Standardized modular design reduces mass production costs, with superior pricing vs imported brands at identical shielding grades for outstanding cost-performance
Powerful Customization, Flexible Adaptation
- Customizable dimensions: Tailored design based on site length, width and height to fit narrow or irregular rooms
- Customizable structure: Fixed, modular, embedded and independent structures available for new construction, renovation and temporary sites
- Customizable functions: Optional add-ons including real-time radiation dose monitoring, remote monitoring, intelligent interlock, explosion-proof and fireproof features
- OEM/ODM processing service: Custom lead sheet cutting, protective door manufacturing and shielding component fabrication with strict drawing & parameter confidentiality
Premium Core Materials, Strong Stable Shielding & Long Service Life
- High-purity electrolytic lead sheets with purity ≥99.99%, free of bubbles/impurities, precise lead equivalent, ≥99.9% ray blocking efficiency
- Hot-dip galvanized steel frames for rust & corrosion resistance, service life ≥20 years; Reinforced grade adds dual anti-corrosion coating for humid & acid-alkali environments
- Special lead rubber sealing components with excellent aging resistance and elasticity for tight door gap sealing; labyrinth penetration assemblies eliminate ray leakage via multi-layer shielding
Strict Technical Standards Compliant with National Codes, Hassle-free Acceptance
- Designed & manufactured in full compliance with GBZ 130-2020, GBZ/T 180-2006 and other national standards; all products pass third-party authoritative testing with external radiation dose ≤0.25 μSv/h meeting public safety limits
- Key components (protective doors, observation windows, shielding layers) fully meet standard parameters, complete test reports provided to help hospitals smoothly pass environmental & health commission acceptance and obtain radiation safety & radiology diagnosis permits
Sufficient Stock, Short Delivery Cycle for Rapid Project Launch
- Core products (lead sheets, protective doors, lead glass, steel frames) kept in inventory; standard sizes available for same-day shipment
- Standard projects completed within 7–15 days from production to installation; customized projects delivered within 15–30 days, far faster than industry average for immediate commissioning
Complete Confidentiality Mechanism to Protect Client Data & Technology
- Strict client information confidentiality policy with non-disclosure agreements signed with all customers; no disclosure of project site drawings, technical parameters or procurement prices
- Exclusive production channels for OEM orders with encrypted document storage to prevent technical leakage
One-stop Service with Professional Team for Full-cycle Support
- Full-service workflow: On-site survey → solution design → manufacturing → on-site installation → commissioning & testing → after-sales maintenance, eliminating multi-party coordination
- Technical team with over 10 years of medical radiation protection experience, fully familiar with hospital requirements and acceptance standards for scientific, reasonable design
- Licensed installation teams execute standardized construction with tidy sites and controllable schedules; full site cleanup post-completion
9. Tender Control Parameters (Marked with *)
9.1 Lead Sheet Series (KITOZER-PB)
-
- Material: High-purity electrolytic lead, purity ≥99.99% (Basic/Standard), ≥99.994% (Reinforced)
-
- Thickness specs: 1.5 mm, 2.5 mm, 3.5 mm, 4.5 mm, thickness tolerance ≤±0.1 mm
-
- Lead equivalent: Corresponding thickness ≥1.5/2.5/3.5/4.5 mmPb, blocks X-ray energy ≥120 keV
-
- Density: 11.34 g/cm³, tensile strength ≥16 MPa
- Surface treatment: Anti-oxidation coating, corrosion & discoloration resistant
9.2 Steel Frame Series (KITOZER-STEEL)
-
- Material: Q235B channel steel & angle steel, hot-dip galvanized anti-corrosion (Basic/Standard), hot-dip galvanized + extra anti-corrosion coating (Reinforced)
-
- Main keel spec: ≥60×4 mm (Basic), ≥80×5 mm (Standard), ≥100×6 mm (Reinforced)
-
- Flatness: ≤2 mm/m² (Basic), ≤1.5 mm/m² (Standard), ≤1 mm/m² (Reinforced)
-
- Seismic grade: ≥Grade 7 (Basic/Standard), ≥Grade 8 (Reinforced)
9.3 Lead-lined Protective Door Series (KITOZER-DOOR)
-
- Customizable door dimensions, standard size ≥1500×2100 mm
-
- Lined lead thickness: ≥2.5 mm (Basic), ≥3.5 mm (Standard), ≥4.5 mm (Reinforced), matching corresponding lead equivalent
-
- Door gap: ≤1 mm (Basic), ≤0.8 mm (Standard), ≤0.5 mm (Reinforced)
-
- Interlock function: Equipped with equipment interlock; radiology equipment cannot activate if door is unclosed
-
- Drive mode: At minimum automatic door closer, emergency manual release function for Reinforced grade
9.4 Lead Glass Observation Window Series (KITOZER-GLASS)
-
- Customizable dimensions, standard size ≥800×600 mm
-
- Thickness: ≥15 mm (Basic), ≥18 mm (Standard), ≥20 mm (Reinforced)
-
- Lead equivalent: ≥2.5 mmPb (Basic), ≥3.5 mmPb (Standard), ≥4.5 mmPb (Reinforced)
-
- Light transmittance: ≥80% (Basic), ≥85% (Standard), ≥90% (Reinforced)
-
- Explosion-proof performance: High-strength explosion-proof (Reinforced), anti-reflection coating (Standard/Reinforced)
9.5 Barium Sulfate Mortar Series (KITOZER-BARIUM)
-
- Mix ratio: Barium sulfate powder : cement : sand ≥2.5:1:1 (Basic), ≥3:1:1 (Standard), ≥3.5:1:1 (Reinforced)
-
- Lead equivalent: ≥2.5 mmPb at 30 mm thickness (Basic), ≥3.5 mmPb at 40 mm thickness (Standard), ≥4.5 mmPb at 50 mm thickness (Reinforced)
-
- Compressive strength: ≥20 MPa (Basic), ≥25 MPa (Standard), ≥30 MPa (Reinforced)
-
- Environmental performance: Radiation-free, non-toxic, compliant with medical environmental standards
9.6 Shielding Waveguide Window Series (KITOZER-WINDOW)
-
- Standard size ≥300×300 mm, custom sizes available
-
- Airflow capacity: ≥100 m³/h (Basic), ≥200 m³/h (Standard), ≥300 m³/h (Reinforced)
-
- Shielding attenuation: ≥30 dB (Basic), ≥40 dB (Standard), ≥50 dB (Reinforced)
-
- Frame material: Aluminum alloy or higher grade, anti-rust & corrosion resistant
9.7 Earthing System Series (KITOZER-GROUND)
-
- Earthing resistance: ≤4 Ω (Basic), ≤2 Ω (Standard), ≤1 Ω (Reinforced)
-
- Earthing electrode material: Copper or higher grade, anti-corrosion & lightning-proof
9.8 Integral Shielding Room
-
- Overall external radiation leakage dose: ≤0.25 μSv/h, compliant with GBZ 130-2020 standard
-
- Three shielding grades available to match corresponding power radiology equipment
-
- Service life: ≥20 years, anti-corrosion, stable long-term performance
10. Full Product Solution Packages
10.1 Conventional X-ray / Small CT Room Solution (Basic Grade, Primary Hospitals / Community Centers)
- Pain points: Limited budget, compact site, low-power equipment (<16-slice CT / conventional X-ray), fast acceptance required, simple maintenance
- Core solution: Basic shielding configuration; primary walls 2.5 mm lead sheets, secondary walls 1.5 mm lead sheets, floors/ceilings 2.5 mm lead sheets; 2.5 mmPb standard protective door & observation window; auxiliary barium sulfate mortar shielding; basic warning light + simple intercom; independent earthing (≤4 Ω)
- Advantages: Low cost, 7-day fast installation, simple maintenance, acceptance-compliant, fits compact spaces
- Implementation workflow: On-site survey (1 day) → Solution design (2 days) → Production stocking (3 days) → On-site installation (3 days) → Commissioning & testing (1 day) → Acceptance & handover
10.2 64-slice CT / DR Room Solution (Standard Grade, Secondary Hospitals / Specialized Hospitals)
- Pain points: Moderate budget, medium-power equipment (64-slice CT / DR), high shielding requirements, stable durability & intelligent safety alerts required
- Core solution: Standard shielding configuration; primary walls 3.5 mm lead sheets, secondary walls 2.5 mm lead sheets, floors/ceilings 3.5 mm lead sheets; 3.5 mmPb electric/manual protective door & anti-reflection lead glass window; high-grade barium sulfate mortar; audible-visual alarm + HD monitoring + video intercom; high-efficiency earthing (≤2 Ω)
- Advantages: Strong shielding performance, stable durability, intelligent safety features, outstanding cost-performance, compatible with conventional large equipment
- Implementation workflow: On-site survey (1–2 days) → Solution design (2–3 days) → Production stocking (5–7 days) → On-site installation (5–7 days) → Commissioning & testing (2 days) → Acceptance & handover
10.3 128-slice CT / DSA / PET-CT Room Solution (Reinforced Grade, Tertiary Hospitals / Large Medical Centers)
- Pain points: Sufficient budget, high-power equipment (128-slice CT / DSA / PET-CT), extreme shielding requirements, full intelligent linkage & long-term stable operation needed
- Core solution: Reinforced shielding configuration; primary walls 4.5 mm high-purity lead sheets, secondary walls 3.5 mm high-purity lead sheets, floors/ceilings 4.5 mm high-purity lead sheets; heavy-duty seismic Grade 8 steel frame; 4.5 mmPb electric sliding protective door with emergency manual release & explosion-proof lead glass window (light transmittance ≥90%); high-density barium sulfate mortar; labyrinth penetration shielding assemblies; intelligent audible-visual interlock alarm + 4K panoramic monitoring + HD video intercom; ultra-high-efficiency multi-point earthing (≤1 Ω)
- Advantages: Ultimate shielding performance, stable intelligent linkage, long service life, compatible with high-power large CT equipment, elevates hospital service capacity
- Implementation workflow: On-site survey (2 days) → Solution design (3–5 days) → Production stocking (7–10 days) → On-site installation (7–10 days) → Commissioning & testing (3 days) → Acceptance & handover
10.4 Old Room Renovation Solution (All Grades Compatible)
- Pain points: Substandard original shielding, limited space, no demolition of original building allowed, short construction cycle to avoid disrupting hospital daily operation
- Core solution: Independent shielding room structure without wall/floor/ceiling demolition; modular assembly with Basic/Standard/Reinforced grades optional; on-site adaptive protective doors, observation windows and penetration assemblies; fast installation minimizing construction noise & dust
- Advantages: No structural demolition, 7–15 day fast construction, minimal operational disruption, fits old sites, acceptance-compliant
10.5 Temporary Radiology Examination Site Solution (Modular Shielding Room, All Grades Compatible)
- Pain points: Temporary physical examination, emergency medical service, mobile diagnosis requiring relocatable, rapidly assembled reusable spaces
- Core solution: Modular prefabricated shielding rooms assembled on-site; Basic/Standard/Reinforced grades optional; optional pulley base for easy mobility; fast disassembly & reusable construction
- Advantages: Flexible mobility, rapid assembly, recyclable, ideal for temporary scenarios, high cost-performance
11. Application Cases
11.1 Medical Industry Cases
Case 1: X-ray Room Project, Community Health Service Center, Guangdong Province (Basic Grade)
- Project overview: Implemented March 2024, 12 ㎡ site with conventional X-ray machine, limited budget, fast acceptance required
- Solution configuration: Basic grade; primary walls 2.5 mm lead sheets, secondary walls 1.5 mm lead sheets, floors/ceilings 2.5 mm lead sheets; basic protective door & lead glass window; simple warning light + basic intercom
- Project outcome: Installation & commissioning completed within 7 days, external radiation dose ≤0.2 μSv/h, smoothly passed local health commission & environmental authority acceptance, stable operation post-commissioning with low maintenance for daily radiology services
Case 2: 64-slice CT Room Project, Secondary Hospital, Jiangsu Province (Standard Grade)
- Project overview: Implemented June 2024, 25 ㎡ site with 64-slice spiral CT scanner, moderate budget, stable durability & intelligent safety required
- Solution configuration: Standard grade; primary walls 3.5 mm lead sheets, secondary walls 2.5 mm lead sheets, floors/ceilings 3.5 mm lead sheets; electric/manual standard protective door & anti-reflection lead glass window; audible-visual alarm + HD monitoring + video intercom
- Project outcome: Full delivery within 12 days, shielding performance fully compliant with standards, reliable intelligent interlock system for safe operation, zero equipment failures post-installation with high hospital recognition
Case 3: 128-slice CT Room Project, Grade A Tertiary Hospital, Beijing (Reinforced Grade)
- Project overview: Implemented September 2024, 35 ㎡ site with 128-slice spiral CT scanner, sufficient budget, ultimate shielding & full intelligent linkage required for long-term stable operation
- Solution configuration: Reinforced grade; primary walls 4.5 mm high-purity lead sheets, secondary walls 3.5 mm high-purity lead sheets, floors/ceilings 4.5 mm high-purity lead sheets; heavy-duty steel frame; reinforced electric sliding protective door & explosion-proof lead glass window; intelligent audible-visual interlock alarm + 4K panoramic monitoring
- Project outcome: Full delivery within 20 days, external radiation dose ≤0.15 μSv/h, shielding performance far exceeding national standards, seamless intelligent system linkage, stable operation compatible with long-duration high-power CT scanning, boosting hospital radiology diagnosis capacity
Case 4: Dental CBCT Room Project, Dental Hospital, Zhejiang Province (Basic Grade)
- Project overview: Implemented April 2024, compact 8 ㎡ site with dental CBCT unit, limited budget
- Solution configuration: Basic grade; primary walls 2.5 mm lead sheets, secondary walls 1.5 mm lead sheets, floors/ceilings 2.5 mm lead sheets; compact protective door & mini lead glass window; simple warning light
- Project outcome: Installation completed within 5 days, perfectly fitted narrow space, radiation dose compliant with standards, neat aesthetic design highly praised by hospital
11.2 Industrial & Scientific Research Cases
Case 5: X-ray Flaw Detection Room Project, Auto Parts Manufacturer, Shandong Province (Standard Grade)
- Project overview: Implemented May 2024, 20 ㎡ site with industrial X-ray flaw detector for auto part internal defect inspection
- Solution configuration: Standard grade; primary walls 3.5 mm lead sheets, secondary walls 2.5 mm lead sheets, floors/ceilings 3.5 mm lead sheets; standard protective door & lead glass window; audible-visual alarm + monitoring system
- Project outcome: Delivery completed within 10 days, stable compliant shielding performance adapting to high-intensity industrial flaw detection use, improving production quality inspection efficiency
Case 6: Radiation Physics Laboratory Project, University, Shanghai (Reinforced Grade)
- Project overview: Implemented July 2024, 30 ㎡ site for radiology scientific experiments requiring ultra-high shielding for high-energy rays
- Solution configuration: Reinforced grade; primary walls 4.5 mm high-purity lead sheets, secondary walls 3.5 mm high-purity lead sheets, floors/ceilings 4.5 mm high-purity lead sheets; heavy-duty steel frame; reinforced protective door & explosion-proof observation window; intelligent interlock + high-efficiency earthing
- Project outcome: Full delivery within 18 days, ultra-low external radiation leakage fully meeting scientific experiment shielding requirements, stable durable performance highly recognized by university research teams
12. Product Fault Troubleshooting & Maintenance
12.1 Common Faults, Inspection & Resolution
- Fault: Protective door fails to open/close smoothly or poor sealing
- Root causes: Aging cracked sealing strips, track foreign blockage, loose hinge screws, electric motor failure (electric doors)
- Resolution: ① Inspect sealing strips; replace with matching lead rubber strips if cracked to ensure tight contact ② Clear dust & debris from tracks with dry brush/compressed air for smooth operation ③ Tighten hinge screws and adjust door position for uniform gap ≤0.5 mm (Reinforced grade) ④ Cut power supply to inspect motor wiring for faulty electric motors; contact manufacturer for motor replacement if irreparable
- Fault: Cracked lead glass observation window or reduced light transmittance
- Root causes: External impact, sudden temperature fluctuation, surface dust/oil contamination, peeled anti-reflection coating
- Resolution: ① Cease use for minor cracks; contact manufacturer for inspection or lead glass replacement if necessary ② Wipe dust/oil with neutral detergent & soft cloth; avoid strong acid/alkali to retain light transmittance ≥85% ③ Contact manufacturer for recoating or replacement if anti-reflection coating peels
- Fault: Excessive radiation leakage detected during testing
- Root causes: Cracked lead sheet joints, loose penetration shielding assemblies, poor protective door sealing, faulty earthing system
- Resolution: ① Inspect lead sheet joints; re-weld & seal with lead glue for cracked areas to guarantee ≥50 mm overlap ② Tighten penetration shielding assemblies and re-seal labyrinth structures to eliminate ray leakage ③ Adjust door sealing and replace strips to ensure gap ≤0.5 mm ④ Test earthing resistance to meet standard (≤1 Ω for Reinforced grade); re-install earthing electrodes if resistance exceeds limit ⑤ Re-test radiation dose; resume operation only after compliance is confirmed
- Fault: Malfunctioning warning / alarm / monitoring system
- Root causes: Power outage, aging short-circuited wiring, damaged equipment, interlock failure
- Resolution: ① Check 220 V power supply and restart equipment ② Inspect wiring; replace aged short-circuited cables and re-secure connections ③ Contact manufacturer for repair or matching equipment replacement if hardware damaged ④ Inspect interlock wiring between protective door and equipment; test interlock sensitivity post-repair
- Fault: Abnormal earthing system (static accumulation / electromagnetic interference)
- Root causes: Corroded earthing electrodes, broken conductors, excessive earthing resistance
- Resolution: ① Test earthing resistance; replace with tin-plated copper electrodes and re-bury underground if resistance exceeds standard ② Inspect conductors; replace pure copper cables for broken sections with corrosion-free tight connections ③ Re-test earthing resistance monthly to maintain compliance
12.2 Routine Daily / Weekly / Monthly Maintenance
Daily Maintenance
- Inspect protective door: Smooth opening/closing, intact sealing strips, uniform gaps
- Check warning/alarm lights: Normal operation and sensitive interlock with door/equipment
- Clean observation window surface dust & oil to maintain clear visibility
- Inspect room environment: Temperature 18–28 ℃, humidity 40%–70%, no water accumulation or stacked debris
Weekly Maintenance
- Clear protective door track dust & foreign matter for smooth operation
- Test monitoring & intercom equipment: Clear video & audio, tight wiring connections
- Inspect shielding waveguide windows: Unclogged ventilation, intact shielding mesh
- Visual inspection of lead sheet surfaces: No corrosion, damage or cracked sealed joints
Monthly Maintenance
- Re-test earthing resistance with tester to meet standard (≤4 Ω Basic / ≤2 Ω Standard / ≤1 Ω Reinforced)
- Tighten all steel frame keel screws to guarantee structural stability
- Inspect penetration shielding assemblies for tight sealing without leakage
- Full interlock function test: Confirm equipment cannot activate with unclosed protective door
- Record maintenance data in Shielding Room Maintenance Log for filing
12.3 Quarterly / Semi-annual / Annual In-depth Professional Maintenance
Quarterly Maintenance (Performed by Professional Technicians)
- Full shielding performance scan with professional instruments on walls, floors, ceilings and doors/windows to locate attenuation abnormal zones
- Lead sheet corrosion inspection: Anti-corrosion treatment for mild corrosion; full sheet replacement for severe corrosion
- Electric protective door motor cleaning, lubrication and wiring insulation inspection to extend service life
- Calibration of monitoring & alarm equipment for accurate detection & sensitive alerts
Semi-annual Maintenance (Performed by Professional Technicians)
- Full replacement of aging protective door & observation window sealing strips for tight sealing
- Disassembly & deep cleaning of shielding waveguide mesh; reinstall after drying to retain ventilation & shielding performance
- Barium sulfate mortar wall inspection: Repair cracks or peeling areas to prevent ray leakage
- Third-party radiation leakage dose testing with official compliance report issued
Annual Maintenance (Professional Technicians + Third-party Testing Institute)
- Full disassembly inspection of protective doors, observation windows and penetration assemblies; replace all aged/damaged components
- Steel frame anti-corrosion treatment: Rust removal and re-coating for extended service life
- Third-party authoritative full testing of shielding performance, radiation leakage dose and earthing resistance with qualified report issued
- Maintenance summary report submitted to client + on-site training for operators covering daily maintenance & fault troubleshooting
13. Factory Strength & After-sales Service
13.1 Factory Strength
- Production scale: KITOZER operates a 15,000 ㎡ modern production base in Guangzhou, dedicated to R&D, manufacturing and sales of radiation shielding equipment. Annual output reaches 1,200 CT/X-ray shielding rooms, 5,000 lead-lined protective doors and 3,000 lead glass observation windows. Mass production ensures stable supply capacity and consistent product quality
- R&D capacity: 30-person professional R&D team with core engineers holding over 15 years of medical radiation protection experience, participating in national radiation protection standard formulation. Owns 8 invention patents, 25 utility model patents and 10 software copyrights, maintaining industry-leading technical innovation
- Production equipment: Imported German lead sheet cutting machines, laser welding machines, CNC bending machines and automatic anti-corrosion coating lines for automated precision manufacturing. Lead sheet cutting tolerance ≤±0.1 mm with firm crack-free welding for consistent product quality
- Quality control: Full-process strict quality management from raw material procurement (high-purity lead, premium steel) through processing, semi-finished & finished product testing to factory acceptance. All products pass ISO9001 Quality Management System, ISO14001 Environmental Management System and OHSAS18001 Occupational Health & Safety Management System certifications, with third-party authoritative testing compliance to GBZ 130-2020 national standards
- Supply chain advantages: Long-term strategic cooperation with domestic high-purity lead, steel and electronic component suppliers for stable premium raw material supply, reduced production costs and improved cost-performance
13.2 After-sales Service
- Warranty commitment: All KITOZER CT & X-ray shielding room products carry a 1-year warranty from acceptance date. Free repair & component replacement (including labor & travel fees) for non-human damage during warranty period; lifelong paid maintenance post-warranty with only component cost & basic labor fees charged, plus permanent technical support
- Response speed: 7×24-hour after-sales hotline with 2-hour initial fault response and phone troubleshooting guidance; on-site technician dispatch within 24 hours nationwide if remote guidance fails, 48 hours for remote regions to minimize equipment downtime
- Service network: 30 regional after-sales service centers covering North, East, South, Southwest, Northwest and Northeast China, with nearby technicians dispatched for fast on-site support
- Regular customer follow-up: Quarterly phone surveys to check product operation and resolve inquiries; semi-annual free on-site full performance inspection to identify hidden faults and provide maintenance recommendations for long-term stable operation
- Technical training: 1–2 days free on-site operator training upon project handover covering product structure, operating standards, daily maintenance, fault troubleshooting and safety precautions, plus printed training manuals for independent operation & maintenance
- Value-added services: Free product upgrade consultation, technical scheme optimization and compliance acceptance guidance to boost operational efficiency and smooth regulatory approval
14. Conclusion
As a core product in the medical radiation protection sector, KITOZER CT & X-ray shielding rooms fully comply with national standards, integrating advanced technology and premium raw materials to build a three-grade shielding system covering Basic, Standard and Reinforced tiers. It fully adapts to all radiation protection scenarios ranging from primary hospitals to tertiary medical centers, industrial flaw detection and scientific research labs.
Supported by five core strengths: precise shielding performance, stable durable quality, flexible customization, outstanding cost-performance and comprehensive after-sales service, our products have served over 1,000 medical institutions and industrial enterprises across 30 provincial-level regions nationwide with widespread customer recognition.
Moving forward, KITOZER will continue deepening the medical radiation protection industry, adhering to the philosophy of technological innovation, quality priority and service-oriented development. We will continuously optimize product performance, upgrade quality and improve service systems to deliver safer, more efficient radiation shielding solutions, support the safe development of medical radiodiagnosis and safeguard the health of medical staff, patients and the general public.
15. Search Keywords, SEO & Tags
15.1 Search Keywords (Core + Long-tail)
Core Keywords
CT shielding room, X-ray shielding room, lead-lined protective room, medical radiation shielding room, DR shielding room, DSA shielding room, PET-CT shielding room
Long-tail Keywords
- Basic grade: Small X-ray shielding room, primary hospital CT shielding room, community health service center X-ray protective room, CBCT shielding room
- Standard grade: 64-slice CT shielding room, secondary hospital X-ray shielding room, DR lead-lined protective room, industrial X-ray flaw detection shielding room
- Reinforced grade: 128-slice CT shielding room, tertiary hospital CT shielding room, DSA shielding room, PET-CT shielding room, high-energy radiation shielding room
General Keywords
Lead sheet shielding room, lead-lined protective door, lead glass observation window, radiation shielding engineering, medical X-ray protection, room radiation shielding, shielding room solution, KITOZER shielding room
15.2 Tags (Classification & Attribute Tags)
Classification Tags
#CTShieldingRoom #XRayShieldingRoom #MedicalRadiationShielding #LeadProtectiveRoom #DRShieldingRoom #DSAShieldingRoom #PETCTShieldingRoom
Attribute Tags
#KITOZER #RadiationProtectionExpert #3GradesOfShielding #CustomShieldingRoom #LeadSheetProtection #MedicalXRaySafety #RadiationShieldingEngineering