Data centers house dense electrical and electronic equipment and cannot use water-based sprinklers in IT halls without risking collateral damage. KITOZER designs clean-agent fire suppression systems aligned with NFPA 75, NFPA 2001, and local code requirements for server rooms, electrical rooms, and battery rooms.
Table of Contents
ToggleSystem Design
Use a two-stage detection: very-early smoke aspiration (VESDA-style) for pre-incident warning, and addressable photothermal detectors for confirmed activation. Suppress with clean gas such as FK-5-1-12 (Novec 1230) or FK-5-1-12 alternatives, or with inert gas (IG-55, IG-100). Design concentration to 5 to 6 percent for A-class flame, hold time 10 minutes in an enclosed room. Isolate HVAC, close dampers, and shut down power before discharge. Use pre-action water only in warehouse and cable trench areas.
Battery Room Specials
Lithium battery rooms require hydrogen detection and mechanical ventilation (minimum 12 air changes per hour) plus aerosol or water-mist suppression rated for lithium thermal runaway. VRLA rooms need acid spill containment and exhaust ventilation. KITOZER integrates fire alarm panels with the central BMS for alarm routing and audit logging.