Data center grounding must reach a resistance of 1 ohm or better before energizing any equipment. KITOZER installation crews drive copper-clad steel electrodes to 2.5m depth, weld exothermic bonds, and run a 40x4mm copper busbar ring around the room perimeter. Earth resistance is measured with the three-pole fall-of-potential method after 48 hours of stabilization. If measured value exceeds 1 ohm, add more electrodes or bentonite earth-enhancing salt. Never rely on building structural steel as the sole ground path.
Table of Contents
ToggleTest Procedure
Disconnect all down conductors during measurement, space current and potential probes at 20m and 61 percent of electrode distance, and repeat at three angles. KITOZER documentation includes the signed earth test sheet as part of handover.
Price