KITOZER Data Center Grounding Resistance Test

Low grounding resistance protects both people and sensitive IT equipment. KITOZER recommends an annual grounding test for every new or existing data room.

Test Method

Use the fall-of-potential method with a three-terminal ground resistance tester. Drive auxiliary current and potential rods at distances recommended by the instrument manual. Measure the main grounding busbar, UPS neutral ground, lightning protection ground, and equipment bonding grid separately. Target resistance for a standard data center is below 1 ohm. For lightning-sensitive sites the target can be below 4 ohms depending on local code. Also inspect bonding straps, busbar connections, and ground rod clamps for corrosion.

When To Re-test

Re-test after any civil work, after lightning strike events, and when measured resistance drifts more than 20 percent from the last record.