Table of Contents
ToggleProduct Overview
The KITOZER dense (sandwich) busway 1000 A is a compact enclosed busbar system used to carry large currents from low voltage switchgear to distribution boards in data centers, industrial plants, high rise buildings, and shopping malls. Copper conductors are stacked with insulation between phases in a sandwich arrangement, giving very low magnetic field, compact dimensions, and high short circuit withstand. The aluminum or steel housing provides mechanical protection and IP54 dust and water resistance. Plug in tap off boxes allow power to be tapped along the run for floor distribution, eliminating large cable trunks.
The sandwich construction places phase conductors A, B, C, and N directly adjacent with thin Class F insulation between them. This geometry reduces phase spacing from the typical 100 mm of open busway to less than 20 mm, cutting overall width to under 200 mm. The tight coupling also minimizes magnetic field radiation, which is important in data centers where electromagnetic interference could affect sensitive IT equipment. Conductors are tin plated copper to prevent oxidation and maintain low contact resistance. The housing is extruded aluminum or folded steel with a continuous gasket around every joint.
Technical Specifications
Rated current 1000 A, rated voltage 400 V three phase four wire plus PE. Conductor copper, tin plated. Insulation class F. Dielectric strength 3.5 kV for 1 minute. Peak withstand 50 kA, short time withstand 35 kA for 1 second. Enclosure IP54. Standard section length 2 m. Tap off boxes rated 63 A, 125 A, 250 A. Phase arrangement A-B-C-N stacked. Temperature rise 100 K. Losses per meter at rated current typically 250 W. Complies with IEC 61439-6, GB/T 8349.
Joint kits use bolted copper connectors with torque controlled bolts and a shared insulating cover. Tap off boxes are plug in units with fusible or molded case protection, rated 63 A, 125 A, or 250 A. Accessories include angle pieces for horizontal or vertical bends, offset sections, expansion joints for long runs, and fire barrier boxes that seal the busway where it passes through fire rated walls. Hangers and brackets are rated for the bus weight plus dynamic short circuit forces. The system is tested for temperature rise, short time current, and dielectric strength at the factory.
Application Scenarios
Dense busway is used in data center main power runs, high rise building vertical risers, industrial plant overhead distribution, shopping mall floor feeders, and convention center power. Sandwich construction allows wall or ceiling mounting with small clearance. Plug in tap off boxes supply floor distribution boards, UPS units, and large air conditioning units. Compared with cables, busway is easier to extend, has lower magnetic field, and requires less installation labor. Fire barrier boxes seal the run where it passes through walls.
In data centers, dense busway runs from the main switchboard to each UPS and floor distribution unit, with tap off boxes feeding server racks. In high rise buildings, it is the vertical riser carrying 1000 A from basement transformer to each floor distribution board. In industrial plants, it runs overhead to production lines with tap off boxes for machine tools. In shopping malls, it feeds floor lighting and HVAC units. In convention centers, it provides flexible power to exhibition booths. The compact size allows installation in suspended ceilings or shallow service risers.
Long vertical runs require expansion joints to absorb thermal movement, typically every 30 m. Fire barrier boxes seal the busway where it passes through fire rated walls or floors, maintaining the fire rating of the building. Feed in units connect the busway to the low voltage switchboard using flexible braids. Tap off boxes are available with fusible protection or molded case breakers, and can be added or relocated without de energizing the main bus when the design allows. The system is preferred over cable for high current runs because it reduces installation labor and provides a documented, inspected conductor system.
Advantages
Compact sandwich design saves space. Low magnetic field reduces electromagnetic interference. Copper conductors give low loss. Plug in taps allow flexible load addition. IP54 enclosure suits dust and splash environments. Standard 2 m sections with bolted joints speed installation. Fire rated barrier options. Five year warranty.
Installation and Maintenance
Support sections every 2 m with hangers or brackets. Maintain phase sequence and joint torque. Use joint kits supplied with each section. After installation, perform insulation test and contact resistance check. Maintenance annually: torque joints, inspect tap off boxes, clean enclosure. Every five years: infrared scan under load for hot joints. Keep tap off boxes closed when not in use. Do not exceed tap off rating.
Price
From $280 per meter including copper conductors, 2 m sections, and joint kits. Tap off boxes, fire barriers, and angle fittings are optional.
Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com