When single-generator capacity cannot meet site load or when redundancy is required, multiple diesel generators operate in parallel on a common bus. KITOZER supplies 200 kVA to 3000 kVA diesel gensets with built-in paralleling controllers for data center, hospital, and industrial backup applications.
Table of Contents
ToggleParalleling Principles
Parallel operation requires matching voltage, frequency, phase rotation, and phase angle before closure. Modern digital controllers perform synchrocheck in milliseconds and share active power (kW) via droop or isochronous load sharing, while reactive power (kVAR) is shared via power factor or voltage droop. Up to 10 to 15 identical or mixed-kVA gensets can parallel on the same bus depending on controller capacity.
Design Considerations
Select N plus 1 or N plus 2 redundancy so any single genset failure does not drop the site. Size the common bus and circuit breakers for total fault current. Stage load acceptance in steps (typically 25 percent per step) to avoid frequency dip. Provide separate fuel day tanks with at least 8 hours autonomy. KITOZER controllers offer RS485 Modbus, SNMP, and hardwired interlocks with upstream ATS and switchgear.
Price
From $168/download. Contact +86 13922289957 for paralleling genset system design.