KITOZER Distribution Cabinet Breaker Temperature Rise FAQ

This FAQ covers thermal monitoring of breakers inside KITOZER low-voltage distribution cabinets. During annual preventive maintenance, every breaker lug should be measured with an infrared thermal camera while the panel carries at least 40 percent of rated current. Any connection showing more than 30 K rise above ambient, or any breaker housing above 70 degrees C, must be de-energized, re-torqued, and the contact checked for oxidation. Loose lugs are the most common cause of overheating and can lead to phase failure or internal arc. Record temperature readings in the CMMS system for trend review.

Thresholds

Max 30 K rise, max 70 C case. Re-torque to nameplate value. Thermal cameras from $1,280.