A double-row (contained) micro module places two rows of cabinets face-to-face, creating an enclosed cold aisle between them. KITOZER configured a 17-cabinet double-row system with 3x 25.5 kW in-row units and a 180 kVA modular UPS.
Table of Contents
ToggleCooling
3x VCR025 in-row precision air conditioners (25.5 kW total cooling, >=5000 m3/h airflow), split-type with indoor and outdoor units.
Power
180 kVA modular UPS (6 slots, installed 4x 30 kVA power modules, hot-swappable, <=3U per module, <=35 kg). 120x 12V120Ah VRLA batteries for ~1 hour backup at 78 kW, on 3x 4-tier 2-column battery racks. Battery switch cabinet: 1x 500A/4P + 3x 250A/4P MCCB. Precision PDU: dual 250A/3P input.
Cabinets
17 EK-series server cabinets (600x1200x2000 mm), including frame, top, bottom, and airflow containment components.
Reference Price
Complete double-row contained micro module approximately $165,000 (market range $160,000-$230,000). Reference price only; final pricing after thermal and electrical survey. Source: KITOZER project library.
Guangzhou Lian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 139-2228-9957 | +86 185-2066-8845 | WhatsApp: +86 190-6853-4140 | gdlain.com