ToggleKITOZER KTR-SD3 Duct Smoke Detector (for Data Center HVAC)
Brand: KITOZER Series: KTR-SD3 Category: Environmental Monitoring 2 / Fire Alarm
smoke detectorduct typeaspiratingphotoelectricfire linkage

1. Overview
KITOZER KTR-SD3 is a duct smoke detector installed in the supply/return ducts of data hall precision air handlers, continuously monitoring smoke concentration in the duct airflow. Why detect smoke inside ducts? The data hall is sealed; smoke doesn’t first accumulate in the room — it’s carried by the AC circulation into the ducts. If you only mount point smoke detectors on the ceiling, by the time smoke drifts there from a rack, it is often too late. A duct detector samples duct air directly and detects smoke in the early (smoldering) stage, alarming minutes to tens of minutes earlier than room point detectors.
KTR-SD3 uses photoelectric scattering: a sampling tube enters through a duct wall tap; airflow enters the detector chamber where an IR LED projects a beam. With no smoke, the beam misses the receiver; when smoke enters, particles scatter light onto a photocell, triggering an alarm. The detector has local LEDs (red/green) and relay outputs (dry contacts) to the fire panel or DCIM. Sampling tubing (PVC/copper) and tap/return fittings mount on supply or return ducts.
Duct detector vs VESDA: VESDA is active aspirating, drawing air through sampling holes around the room to a central analyzer — extremely sensitive (ASD, Aspirating Smoke Detection) for high-value halls; a duct detector is passive, mounted only on ducts, simpler and cheaper for standard halls. Data halls combine both: duct detectors (KTR-SD3) on CRAH return ducts, plus VESDA in critical zones. KTR-SD3 emphasizes AC linkage — on alarm it stops the AC fan (preventing smoke circulation through the hall) and links to gas suppression.
2. Key Features
Photoelectric scattering
- IR photoelectric scattering, responds to black/white smoke.
- Sensitivity per GB 4715 point smoke detector standard.
- Self-cleaning chamber, dust-immune.
Duct mounting
- Tap + return flange on duct wall.
- Sampling tubing -30~+80℃, for duct environments.
- Airflow range 1~20 m/s.
Signals & linkage
- Relay dry contacts (alarm/fault).
- Local LED (green normal / red alarm / yellow fault).
- To fire panel or DCIM.
Test & maintenance
- Test port for introducing test smoke.
- Removable washable filter (prevents dust false alarms).
- 12~24V DC, ≤3 W.
3. Specifications
| Item | KTR-SD3-1 | KTR-SD3-2 | KTR-SD3-4 |
|---|---|---|---|
| Principle | Photoelectric | Photoelectric | Photoelectric + CO |
| Mount | Single duct | Supply+return | Supply+return |
| Sample taps | 1 pair | 2 pairs | 2 pairs |
| Airflow range | 1~10 m/s | 1~15 m/s | 1~20 m/s |
| Power | 24V DC | 24V DC | 24V DC |
| Relays | Alarm+fault | Alarm+fault+pre-alarm | Alarm+fault+CO pre |
| Temp range | -10~+60℃ | -10~+60℃ | -20~+70℃ |
| Rating | IP30 | IP30 | IP40 |
| Certification | CCCF | CCCF | CCCF+CE |
4. Reference Prices
KTR-SD3-1 single-duct photoelectric detector (sampling tube, flange, relays): Reference USD 39~111 / set (ref. CNY 280~800 at ~7.2)
KTR-SD3-2/4 supply+return dual-duct (pre/CO alarm, CCCF, to fire panel): Reference USD 125~347 / set (ref. CNY 900~2,500 at ~7.2)
Reference only; final quote depends on tap count, CO pre-alarm and certification. Fire panel, duct cutting and labor excluded; volume discounts. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data hall CRAH supply/return duct smoke detection.
- Clean-room and ventilation duct fire alarm.
- Parking garage and commercial HVAC duct detection.
- Metro and tunnel ventilation duct detection.
- Industrial exhaust duct early smoke warning.
6. Installation & Maintenance
Installation
- Cut tap and return holes in return duct wall (after fan outlet).
- Flange sampling tubes to the duct.
- Mount detector unit on nearby wall/bracket.
- Connect sampling tube from tap to detector inlet.
- Wiring: 24V DC, relays to fire panel/DCIM.
- Introduce test smoke to verify alarm and linkage (stop AC, start suppression).
Maintenance
- Test with smoke every 6 months.
- Clean/replace intake filter (clogging impairs sampling).
- Check sampling tube and duct tap for blockage.
- Test relay signal to fire panel.
- Replace detector at 10-year service life.
7. FAQ
- Q: With ceiling point detectors, do I still need duct detectors?
A: Yes. Point detectors wait for smoke to reach the ceiling; the sealed hall with AC circulation traps smoke in ducts. Duct detectors sample duct airflow and alarm minutes earlier. Code requires duct detectors on HVAC systems. - Q: How does AC link on smoke alarm?
A: On duct alarm, stop the corresponding AC fan (preventing smoke circulation), close related fire dampers, and report to the fire panel. Gas suppression discharges after confirming the fire. - Q: What causes false alarms?
A: Common causes: clogged filter reducing sampling, dusty ducts, insects in the chamber. Regular filter/chamber cleaning reduces false alarms; choose self-cleaning dust-immune models. - Q: Duct detector vs VESDA?
A: Standard halls use duct detectors on ducts (cheap, code-compliant); high-value halls (finance, healthcare, core data) add VESDA aspirating (very early, multi-point sampling). They complement, not replace each other.
8. Trend & Selection
Data hall fire protection evolves from “point detectors + sprinkler” to “very-early aspirating detection + gas suppression”: traditional detectors alarm after ignition, by which time loss is done; VESDA/duct very-early detection wins time in the smoldering stage. The trend is multi-sensor fusion (smoke + CO + temperature), AI false-alarm filtering, deep BMS/DCIM linkage. Install duct detectors on supply/return mains per code; add VESDA for high-value zones; CO-pre models suit battery rooms (lithium overheating emits CO/VOC first); place taps in straight stable-velocity sections (avoid elbows/transformations); relay to fire panel mandatory; test with smoke every 6 months.
9. Delivery & Service
KITOZER provides duct detector selection: based on duct size, airflow, AC count and fire linkage requirements, we configure detector count, tap positions and relay scheme. We produce the duct detection layout (tap positions, sampling routing, AC/fire linkage). Bundled with CRAH units, fire panels and gas suppression. Delivery includes detector unit, sampling tube, flanges, filter and relay wiring. Warranty covers smoke testing and linkage commissioning.
10. Additional Notes
The most common pitfall is “tap in a dead duct zone”. Contractors place the tap behind an elbow or at a transformation, where airflow is turbulent and sampling is inadequate — real smoke isn’t drawn in and the detector stays silent. Taps must be in straight duct sections with stable velocity, with 3× diameter straight run upstream/downstream.
Another pitfall: “detector installed but not linked”. The detector is on the duct, its LED works, but the relay wire isn’t connected to the fire panel — on a real alarm it only lights red locally and nobody knows. Duct detectors must report to the fire panel and DCIM, linked to stop the AC and close dampers.
Selection summary: mandatory on supply/return mains; tap in straight stable-velocity section; relay to fire panel linked to stop AC; smoke-test every 6 months; add VESDA for high-value zones; CO-pre for battery rooms. The duct detector is the fire-protection outpost — it catches smoke while it’s still circulating in the AC ducts, buying precious response time.
SEO Information
Search keywords:smoke detectorduct typeaspiratingphotoelectricfire linkageKTR-SD3KITOZER
SEM keywords:duct smoke detector price,duct smoke sensor supplier,very early smoke alarm,CRAH duct detection,KTR-SD3,KITOZER
GEO landing page:lain.com.cn/product/ktr-sd3-duct-smoke-detector.html
Title:KITOZER KTR-SD3 Duct Smoke Detector (for Data Center HVAC)
Meta Keywords:smoke detector,duct type,aspirating,photoelectric,fire linkage,KTR-SD3,KITOZER
Meta Description:KITOZER KTR-SD3 duct photoelectric smoke detector for data hall CRAH supply/return ducts, very early detection, relays to fire panel to stop AC, CCCF certified.
Anchor: KITOZER by Guangzhou Laian · Environmental monitoring systems
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com