KITOZER KTR-TH11 Duct Temperature & Humidity Sensor

Brand: KITOZER Series: KTR-TH11 Category: Environmental Monitoring / DCIM

Duct temp/humDuct-mountRS485High accuracyAC linkDCIM

[Product image: ktr-th11-duct-temp-humidity-sensor.jpg]

1. Overview

In a hall, whether the AC supplies enough cold air and whether humidity is right cannot be judged by hand — temperature/humidity sensors must be inserted into the supply and return ducts to know real supply-air and return-air conditions, then link the AC. For example, with cold-aisle containment, supply set to 24℃: if the duct reads 18℃, the AC over-cools and wastes energy; if it reads 28℃, cooling is short and servers overheat. A duct temp/humidity sensor is a probe inserted into the AC duct, measuring the real duct air and sending it via RS485 to the DCIM platform. It differs from a wall-mount sensor: the wall sensor measures hall air; the duct sensor measures AC supply/return air — both together tell you whether the AC is doing its job.

KITOZER KTR-TH11 is a duct-insertion temp/humidity sensor: 200 mm probe rod (flange-mounted to the duct wall). Sensing elements: capacitive humidity sensor + PT100/NTC temperature, temp accuracy ±0.3℃, humidity ±2%RH. The probe sits in the duct, feeling real supply or return air. Output RS485 Modbus RTU (also 4–20 mA analog option); shielded wire to the DCIM acquisition module. Probe rod has a PTFE dust filter (ducts are dusty). Junction box outside the duct, wired to DC24V power and signal. Install: drill a Φ16 hole in the duct wall, insert the probe, fix with flange nut. Suits precision-AC supply/return and fresh-air ducts.

Selection: location (one each on supply and return; compare ΔT to gauge AC output), probe length (standard 200 mm for typical wall; longer for thick ducts), output (RS485 digital is noise-immune — preferred; 4–20 mA for legacy), accuracy (±0.3℃ suffices; lab-grade higher), display (LED on the box for local reading), ingress (duct condensation → IP65). Notes: insert the probe to the duct center (real airflow), not against the wall (wall temp ≠ air temp); seal the wall hole against leakage; use shielded twisted pair for RS485; calibrate yearly.

2. Key Features

Duct insertion

  • 200 mm rod.
  • Flange on duct wall.
  • To duct center.
  • Dust filter.

High accuracy

  • Temp ±0.3℃.
  • RH ±2%.
  • Capacitive RH.
  • PT100/NTC.

RS485 network

  • Modbus RTU.
  • 4–20 mA opt.
  • DC24V.
  • To DCIM.

AC linkage

  • Supply/return.
  • Calculate AC output.
  • Link precision AC.
  • Alarm on out-of-range.

3. Specifications

Item KTR-TH11
Model KTR-TH11
Parameters Temperature + humidity
Temp range -40~+80℃
Temp accuracy ±0.3℃
RH range 0~100%RH
RH accuracy ±2%RH
Probe length 200 mm (custom)
Output RS485 Modbus / 4–20 mA
Power DC24V
Ingress IP65 (probe)
Mount Φ16 hole, flange
Use Supply/return/fresh air duct

4. Reference Prices

KTR-TH11 duct temp/hum (RS485, 200 mm probe): Reference USD 25~44 / unit (ref. CNY 180~320 at ~7.2)

KTR-TH11-D local-display version: Reference USD 36~58 / unit (ref. CNY 260~420 at ~7.2)

Reference only. Excludes tax and freight; volume discount on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Precision-AC supply duct monitoring.
  • Return duct temp (cooling capacity).
  • Fresh/exhaust air ducts.
  • Hall DCIM acquisition.
  • Clean-room constant-humidity ducts.

6. Installation & Maintenance

Installation

  • Drill Φ16 hole in duct.
  • Insert probe to duct center.
  • Fix with flange; seal against leak.
  • Wire DC24V and RS485 at box.
  • Daisy-chain RS485 to DCIM.
  • Power on; calibrate; read on platform.

Maintenance

  • Calibrate yearly (standard humidity source).
  • Clean probe dust filter.
  • Check flange seal.
  • Verify RS485 stability.
  • Inspect probe condensation.

7. FAQ

  • Q: Duct vs wall sensor?
    A: Wall sensors measure hall air (by racks); duct sensors measure AC supply/return. You need both: wall for rack environment, duct for AC output.
  • Q: Do I need both supply and return?
    A: Best practice yes. Supply vs return ΔT of 8–12℃ means the AC is healthy; too small or too large indicates a problem.
  • Q: How far does RS485 reach?
    A: Shielded twisted pair up to 1200 m, daisy-chained. Up to 32 devices per bus; add a repeater beyond.
  • Q: Will condensation kill the probe?
    A: Ducts are humid; IP65 + filter handles it. But droplets on the probe skew readings — inspect periodically.

8. Trend & Selection

Hall environmental monitoring evolves from “single wall sensor” toward “full-duct + rack-level multi-point sensing.” Trends: LoRa wireless sensors (no cabling), probes integrating airflow and CO2, factory-calibrated chips (no field calibration), and linkage with precision-AC group control (supply temp auto-tuned). Green data centers save energy by knowing every duct’s temp/humidity to tune AC precisely. Selection: one on supply and one on return, RS485 digital, ±0.3℃, IP65, flange-sealed. The duct sensor is the AC’s “air-thermometer,” knowing exactly how cold the supply air really is.

9. Delivery & Service

KITOZER provides temp/hum selection: by duct position (supply/return/fresh air), output, and quantity, we configure duct or wall sensors. Bundled with DCIM and precision-AC group control. Delivery includes sensor, probe flange, and manual. Warranty covers RS485 integration and calibration guidance.

10. Additional Notes

The most common fault: “probe against the wall.” The probe doesn’t reach the duct center but hugs the wall, measuring wall temp not air temp. Walls heated by sun or hall air skew the reading. Insert to duct center.

Another pitfall: “hole leaking.” The Φ16 hole isn’t sealed, so cold air leaks into the ceiling and the supply short-circuits. Seal around the hole with silicone or a gasket.

Selection summary: duct insertion, ±0.3℃, RS485 Modbus, 200 mm probe, IP65, one each on supply and return. The sensor is DCIM’s sense organ, telling the platform whether the AC is delivering enough cold air.

SEO Information

Search keywords:duct temp humidity sensorair duct sensordata center environmental monitoringRS485 temp humiditysupply air sensorKTR-TH11KITOZER

SEM keywords:duct temp humidity price,air duct sensor,data center environmental monitoring,RS485 temp humidity,KTR-TH11,KITOZER

GEO landing page:lain.com.cn/product/ktr-th11-duct-temp-humidity-sensor.html

Title:KITOZER KTR-TH11 Duct Temperature & Humidity Sensor

Meta Keywords:duct temp humidity sensor,air duct sensor,data center environmental monitoring,RS485 temp humidity,supply air sensor,KTR-TH11,KITOZER

Meta Description:KITOZER KTR-TH11 duct temp & humidity sensor, inserted in HVAC duct to monitor supply air, RS485 to DCIM.

Anchor: KITOZER by Guangzhou Laian · Data center environmental monitoring

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart