Uncalibrated temperature and humidity sensors produce false alarms and blind spots. KITOZER recommends a fixed calibration cycle for every environment monitoring sensor in a data center.
Table of Contents
ToggleRecommended Cycle
Temperature sensors: calibrate once per year against a traceable reference probe. Humidity sensors: calibrate every 6 months because RH sensing elements drift faster. Water leak cable and point sensors: visual test every 3 months and full loop test annually. Smoke detectors: functional test every 6 months by certified technician. Door contact and vibration sensors: check once per year during preventive visit.
Acceptance Tolerance
Temperature reading must stay within plus or minus 0.5 degrees Celsius of reference. Humidity must stay within plus or minus 3 percent RH. Out-of-tolerance sensors are replaced or recalibrated on the spot.