KITOZER
KITOZER

KITOZER EPS Emergency Power Supply 60kW Three Type Fire Rated

Product Overview

The KITOZER 60kW three-phase EPS emergency power supply is engineered for large fire-protected buildings where a single central unit must back up the entire fire electrical load. With 60kW continuous rating and 300 percent inrush capacity, it can start two 22kW fire pumps sequentially while carrying 15kW of continuous lighting and ventilation load. The unit is built to GB 17945 fire-rated standards and ships with a fire control interface that accepts start signals from the fire alarm panel and sends status back over dedicated hardwired contacts.

Technical Specifications

Rating: 60kVA / 60kW continuous, three phase four wire 380V / 220V. Overload: 125 percent for 10 minutes, 150 percent for 1 minute, 300 percent for 10 seconds. Input: 380V three phase, PFC greater than 0.95, THDi less than 5 percent. Output: pure sine wave, THD less than 3 percent, voltage regulation plus or minus 1 percent, frequency 50Hz plus or minus 0.5Hz. Battery: 12V 100Ah VRLA, 240 blocks in four strings, standard 90-minute backup, 2-hour and 4-hour options. Charger: 120A with temperature compensation. Protection: DC overcurrent, insulation monitoring, AC overvoltage, overload, short circuit, battery reverse, over-temperature, fan failure. Communication: Modbus TCP, SNMP, Web HMI, 32 dry-contact I/O. Display: 10-inch color touch HMI with 10,000-event log. Enclosure IP21 floor standing, four-section cabinet. Compliance GB 17945, GB 51348, CE.

Application Scenarios

The 60kW EPS is typically installed in super-tall office towers, large shopping malls, underground mega-parking structures, hospital main buildings, and convention centers. Loads include two fire pump motors up to 22kW, sprinkler and hydrant pump control panels, basement smoke extraction fans up to 30kW, stairwell pressurization fans, central emergency lighting distribution, fire elevator emergency circuits, fire command center equipment, and gas release system pre-action controls. It is also used as the dedicated fire-rated alternate power source for critical industrial processes.

Advantages and Features

KITOZER 60kW EPS includes a dedicated fire interface panel with isolated inputs for fire alarm panel start, remote start, and remote stop, plus isolated outputs for unit running, unit fault, battery low, and mains failure. The battery management system provides per-string and per-block monitoring, with automatic isolation of weak strings. The cabinet uses a separate battery compartment with forced ventilation and thermal isolation from the power electronics. Parallel redundant inverter configuration is available for 2N redundancy.

Installation and Maintenance

Confirm floor loading with structural engineer: the four-section cabinet with 90-minute battery weighs about 4,800 kilograms, and a 4-hour bank exceeds 10,000 kilograms. Use dedicated cable tray for battery and output circuits. Commissioning includes a 100 percent load bank test for 30 minutes, sequential pump-start demonstration, and fire alarm interface functional test. Maintenance: quarterly visual and terminal torque; annual battery conductance, contactor inspection, and charger calibration; every five years replace fans, DC capacitors, and contactor arc chutes. Keep logged discharge test reports on file for fire authority audit.

Price

From $17,800 per unit with 90-minute battery. Contact +86 13922289957 for runtime and redundancy options.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Scroll to Top