KITOZER EPS Emergency Power Supply: Fire Single Three-Phase vs UPS Backup Time

KITOZER EPS Emergency Power Supply: Fire & Building Backup Engineering Guide

KITOZER EPS (Emergency Power Supply) is a dedicated backup power system for fire-fighting equipment, emergency lighting, evacuation signage, elevators, fire pumps, smoke exhaust fans, and critical building loads. When mains power fails, EPS automatically switches to battery-inverter output within 0.1–0.25 seconds, providing 90–180 minutes of uninterrupted AC power. KITOZER covers 1 kVA to 500 kVA, single-phase lighting type and three-phase power type, with VRLA or LFP battery options, fire inspection system integration, and remote monitoring.

1. EPS Working Principle

Normal mode: Mains power feeds the load through a static bypass (ATS) using thyristor switches. Simultaneously, a PFC charger floats the battery bank at 2.25V/cell (VRLA) or 3.3V/cell (LFP). The inverter is idle but warm.

Outage mode: On mains failure detection (<20ms), ATS disconnects bypass and connects inverter output. The inverter starts from battery DC bus, producing pure sine wave AC at 220V/380V 50Hz. Transfer time: ≤0.1s (lighting), ≤0.25s (power).

Return mode: When mains returns stable for 5 minutes, system switches back to bypass and resumes battery charging.

2. EPS Classification

Type Output Power Range Typical Loads Transfer Time
Lighting single-phase 220V 1P 0.5–30 kVA Emergency lights, signage ≤0.25s
Power three-phase 380V 3P 5–500 kVA Fire pumps, fans, elevators ≤0.25s
Hybrid 220V+380V 10–100 kVA Mixed lighting+power ≤0.25s

3. EPS vs UPS: Critical Differences

Item EPS UPS
Primary purpose Fire/emergency building power IT/data center loads
Backup duration 90–180 minutes standard 5–30 minutes (then generator)
Transfer time 0.1–0.25 s 0 ms (online double-conversion)
Battery capacity Large (long runtime) Small (short runtime)
Efficiency (bypass) >95% 95–96% (online)
Standard GB 17945, GB 51309 GB 7260, IEC 62040
Cost per kVA Lower Higher
Enclosure Standalone cabinet Rack/tower

4. KITOZER EPS Product Line

Model Power Type Input/Output Reference Price
KZ-EPS-1K 1 kVA Lighting 1P 220V/220V $850
KZ-EPS-3K 3 kVA Lighting 1P 220V/220V $1,700
KZ-EPS-10K 10 kVA Hybrid 220/380V $4,900
KZ-EPS-30K 30 kVA Power 3P 380V/380V $12,000
KZ-EPS-50K 50 kVA Power 3P 380V/380V $19,000
KZ-EPS-100K 100 kVA Power 3P 380V/380V $39,000
KZ-EPS-200K 200 kVA Power 3P 380V/380V $72,000
KZ-EPS-500K 500 kVA Power 3P 380V/380V $180,000

5. Backup Time Calculation

Formula: Battery capacity (Ah) = Load power (W) × Backup time (h) ÷ (DC bus voltage × Inverter efficiency × DOD).

Example: 10 kVA EPS, 8 kW actual load, 90 minutes backup. DC bus = 192V (16×12V VRLA). Inverter efficiency = 0.9. DOD = 0.8.

Ah = 8000 × 1.5 ÷ (192 × 0.9 × 0.8) = 12000 ÷ 138.2 = 86.8 Ah → select 2 parallel strings of 12V/100Ah.

For 180 minutes: double the battery capacity → 4 parallel strings of 12V/100Ah.

6. Battery Options

VRLA (Valve-Regulated Lead Acid): 12V/65Ah, 100Ah, 120Ah, 150Ah, 200Ah. Float life 5–8 years at 25°C. Standard choice. Temperature compensated charging.

LFP (Lithium Iron Phosphate): 48V/100Ah rack modules. Life 10–15 years. 60% smaller footprint. Higher upfront cost but lower TCO. BMS included.

7. Internal Structure

  • Cabinet: 2200×800×600mm standard, cold-rolled steel, RAL 9005/7035.
  • ATS static switch: Thyristor-based, <0.1s transfer, zero-break for lighting.
  • Charger: Three-phase PFC, power factor >0.99, current-limited.
  • Inverter: IGBT SPWM, THDu <3%, overload 120% for 10min.
  • Monitor: 7-inch LCD, RS485/Modbus, Ethernet, dry contacts.
  • Battery cabinet: Separate or integrated, steel racks, ventilation.

8. Installation Requirements

Level floor with channel steel foundation. Front clearance ≥1m, rear ≥0.8m. Input and output cables in separate trays. PE grounding resistance <4Ω. Ambient 0–40°C, humidity ≤90% non-condensing. Battery room requires ventilation (hydrogen dilution) and temperature control 20–25°C.

9. Maintenance SOP

  • Monthly: Visual inspection, LCD status check, battery voltage reading.
  • Quarterly: 5-minute test discharge, check charger float voltage, terminal torque.
  • Annually: Full-load discharge test, battery internal resistance measurement, contactor/relay check, firmware update.
  • Every 3 years: Battery capacity test. Every 5–8 years: replace VRLA batteries.

10. EPS + Generator Coordination

EPS covers the first 90–180 minutes. Diesel generator starts in 10–15 seconds and takes over long-duration backup. The system automatically transfers between EPS and generator. This combination provides unlimited runtime for critical facilities.

11. Compliance Standards

GB 17945-2010 “Fire emergency lighting and evacuation indicating system”; GB 51309-2018 “Technical standard for fire emergency lighting”; GB 50016 “Code of design on building fire protection”; GB 50052 “Power supply systems design code”; GB/T 14048.

12. FAQ (60 Questions)

Q1: EPS or UPS for fire systems? A: EPS per GB 17945. UPS for IT only.

Q2: Standard backup time? A: 90 minutes. Customizable 30/60/120/180 minutes.

Q3: Transfer time? A: ≤0.1s lighting, ≤0.25s power.

Q4: Can EPS drive motors? A: Yes, power-type three-phase EPS for pumps/fans/elevators.

Q5: Battery type? A: VRLA standard; LFP optional.

Q6: Battery life? A: VRLA 5–8 yr; LFP 10–15 yr.

Q7: How many batteries needed? A: Depends on DC bus voltage and runtime. See calculation.

Q8: EPS noise? A: <55 dB at 1m (fanless models).

Q9: Efficiency? A: Bypass mode >95%; inverter mode 90–92%.

Q10: Communication? A: RS485/Modbus, Ethernet, SNMP, dry contacts.

Q11: Does it integrate with fire alarm? A: Yes, dry contact input from fire alarm panel triggers forced output.

Q12: What is fire inspection? A: Auto periodic test discharge to verify battery health without blackout.

Q13: Can I expand later? A: Yes, add battery strings for longer runtime.

Q14: Single or three-phase? A: Lighting single-phase; motor loads three-phase.

Q15: What is kVA vs kW? A: kVA = apparent power; kW = real. PF=0.9 typically.

Q16: Overload capacity? A: 120% for 10 min, 150% for 1 min.

Q17: Surge capacity? A: 3× rated for 10 seconds (motor starting).

Q18: Input voltage range? A: 380V ±15%, 50Hz ±5%.

Q19: Output THD? A: <3% (linear load), <5% (non-linear).

Q20: Display? A: 7-inch LCD showing voltage/current/frequency/battery/status.

Q21: Alarm types? A: Inverter fault, battery low, overload, overtemp, charger fault.

Q22: Remote monitoring? A: Web browser, SNMP, email/SMS alarm.

Q23: Installation? A: Floor-mounted, hardwired input/output.

Q24: Cable size? A: Based on current; consult KITOZER engineering.

Q25: Grounding? A: PE <4Ω, isolated neutral option.

Q26: Operating temp? A: 0–40°C; battery room 20–25°C optimal.

Q27: Humidity? A: ≤90% non-condensing.

Q28: Altitude? A: ≤1000m standard; derate above.

Q29: Warranty? A: 3 years, batteries 2 years.

Q30: Certification? A: CCC fire certification, CE, ISO 9001.

Q31: Lead time? A: 15–30 days depending on size.

Q32: Can it be outdoor? A: IP54 outdoor cabinet version available.

Q33: What is bypass? A: Direct mains feed path when inverter not active.

Q34: What is maintenance bypass? A: Isolation switch for servicing without load outage.

Q35: Can EPS share UPS battery? A: No, separate systems.

Q36: What happens if battery fails? A: Alarm triggers; load loses backup but mains bypass continues.

Q37: How often test? A: Monthly visual, quarterly test discharge, annual full load.

Q38: Battery replacement? A: Every 5–8 years VRLA; hot-swap while on bypass.

Q39: What is float voltage? A: 2.25V/cell VRLA; 3.35V/cell LFP.

Q40: Equalization charge? A: Periodic 2.35V/cell to balance cells.

Q41: Can it charge while discharging? A: Charger charges battery during mains; inverter discharges during outage.

Q42: What is DC bus? A: Battery voltage feeding inverter (192V/240V/384V typical).

Q43: Number of batteries? A: DC bus ÷ 12V per cell. 192V = 16×12V.

Q44: Parallel strings? A: Up to 4 parallel strings for high capacity.

Q45: Fusing? A: DC fuses on each string; AC MCB on output.

Q46: Fire rating? A: Cabinet steel ≥1.5mm; battery room fire-rated enclosure optional.

Q47: Vented or sealed? A: Sealed VRLA; no ventilation ducting needed beyond basic.

Q48: Hydrogen risk? A: VRLA low gas emission; still require ventilation per code.

Q49: Can LFP replace VRLA? A: Yes, with BMS; smaller and longer life.

Q50: What is SOH? A: State of Health; battery capacity vs new. Replace at <80%.

Q51: Can I monitor individual cells? A: Add KITOZER battery monitoring system.

Q52: What if mains returns during discharge? A: System waits 5 min stable, then returns to bypass and charges.

Q53: Generator coordination? A: Set transfer delay 0–600s to wait for generator.

Q54: Is EPS required by code? A: Yes, for commercial buildings, hospitals, metros, high-rises per GB 51309.

Q55: What loads must be on EPS? A: Emergency lighting, evacuation signs, fire pumps, smoke fans, elevators, control circuits.

Q56: Can non-critical loads share EPS? A: No, dedicated emergency circuit only.

Q57: What if overload? A: Alarm + automatic shed non-critical outputs (if designed).

Q58: Remote reboot? A: Not typically; EPS is always-on backup.

Q59: Dimensions? A: Depends on kVA. 10kVA ~800×600×2000mm; 100kVA ~1000×800×2200mm plus battery cabinet.

Q60: Contact? A: Tel/WeChat +86 13922289957, +86 18520668845; WhatsApp +86 19068534140.