The KITOZER 70 degrees Celsius DN500 fire damper is a galvanized steel blade damper installed in HVAC ducts that penetrate fire-rated walls or floors. When duct air temperature reaches 70 degrees Celsius, the fusible link melts, a spring closes the blade, and the damper seals the duct to prevent smoke and flame from spreading between compartments. The damper ships with a mounting flange, fusible link, and a microswitch that sends a closed signal to the building management system.
Without fire dampers, a fire in one room could travel through the HVAC duct to every floor of the building in minutes. The damper acts as a passive barrier, closing automatically when heat reaches it, without any power or control signal. The fusible link is a small alloy solder that melts at 70 degrees Celsius, releasing the spring-loaded blade. The microswitch confirms the closed position to the BMS, so building operators know if a damper has tripped. KITOZER supplies the damper rectangular or round, in all common duct sizes.
Technical Specifications
Size 500 x 320 mm rectangular or DN500 round, activation temperature 70 degrees Celsius fusible link, blade galvanized steel 1.5 mm, frame galvanized steel 2 mm, seal intumescent or silicone, leakage class C at 1000 Pa, actuation spring return, microswitch SPDT, operating voltage 24V or 220V, CCCF certified, GB 15930, maximum working temperature 70 degrees Celsius ambient, weight 18 kg. Optional motorized actuator for remote test.
The frame is 2 mm galvanized steel, formed into a rectangular or round section with mounting flanges. The blade is 1.5 mm galvanized steel, with an intumescent seal around the perimeter that expands when heated to fill gaps. The fusible link is a small alloy piece rated at 70 degrees Celsius, held in a spring clip. When the link melts, the spring rotates the blade 90 degrees to the closed position. The microswitch is a SPDT contact that changes state when the blade closes, wired to the BMS. The damper is leakage class C at 1000 Pa, which means less than 200 m3/h leakage per square meter.
Application Scenarios
This fire damper is installed wherever supply or return air ducts cross fire-rated walls, floors, or shaft enclosures, including commercial buildings, hospitals, shopping malls, underground parking, and industrial plants. The 70 degrees Celsius rating is standard for general HVAC ducts. For exhaust ducts handling grease or hot process air, KITOZER offers 150 degrees Celsius kitchen grease dampers and 280 degrees Celsius smoke exhaust dampers. KITOZER also provides rectangular and round dampers in all common duct sizes, as well as custom sizes for non-standard shafts.
For a typical office tower, dampers are installed at every wall penetration on each floor, typically 10 to 20 per floor. For a hospital, additional dampers protect operating rooms and isolation rooms. For an underground parking garage, dampers separate ventilation zones. KITOZER also offers motorized dampers that can be tested remotely from the BMS, eliminating the need to manually access each ceiling cavity. The motorized version is preferred for large buildings where manual testing would require weeks of access.
Key Advantages
The galvanized steel frame survives decades in conditioned ductwork without painting, and the intumescent seal expands when heated to provide a tight smoke seal. The spring return closes the damper within seconds of link melting, even if fan power is lost. The microswitch confirms closed position to the BMS, which is required by modern building codes. KITOZER ships each damper with a factory calibration certificate and mounting templates, simplifying installation on site.
The fusible link is replaceable, so after a test the damper can be reset without replacing the whole unit. The galvanized frame resists corrosion in damp underground ducts. The damper is fully compatible with standard duct flanges, so it drops into existing ductwork. KITOZER provides a 5-year warranty on the frame and a 1-year warranty on the fusible link and microswitch. The CCCF certificate covers the complete damper range.
Installation and Maintenance Recommendations
Install the damper within 200 mm of the fire wall penetration, and seal the annular gap with fire-rated mortar. Leave at least 200 mm clearance on the actuator side for inspection and link replacement. Test the damper quarterly by manually pushing the test lever and confirming the blade closes and the microswitch changes state. Replace the fusible link every 5 years, or immediately after any activation. Do not paint over the fusible link or blade, and keep the damper accessible from a walkway rather than burying it inside a ceiling cavity.
After installation, label the damper with its location number on the BMS drawing, so maintenance staff can identify it during testing. Keep a spare fusible link and a spare microswitch on site. Test the microswitch annually by measuring continuity with a multimeter. If the damper is installed in a dusty duct, inspect the blade annually for dust buildup, which can prevent full closure. KITOZER recommends a 10-year overhaul that includes replacing the spring and inspecting the frame for corrosion.