KITOZER Fire Gas Cylinder Pressure Test Procedure

KITOZER fire gas suppression commissioning service covers pneumatic tightness test and simulated discharge test for clean agent systems such as FM200, Novec 1230, and IG541. Before charging with clean agent, our technicians pressurize the piping network with dry nitrogen to 1.1 times the design pressure, hold for 5 minutes, and verify pressure drop within tolerance. After gas charging, we run a simulated nozzle test to confirm solenoid actuation, valve release, pressure switch signal, and alarm panel integration.

Test Steps

1. Close cylinder valve and isolate nozzle outlets with blind flanges. 2. Pressurize piping with dry nitrogen to 1.15 times working pressure. 3. Hold 5 minutes, record pressure drop. 4. Vent and inspect for leaks with soap solution. 5. Perform simulated discharge with solenoid actuation. 6. Verify pressure switch signal and alarm panel logic.

Compliance

Testing follows NFPA 2001 and local fire authority requirements. A signed test report is issued to the customer for handover acceptance.