KITOZER fire suppression gas pressure test procedure guide describes how to perform piping integrity tests for clean agent systems such as FM-200, Novec, and IG-541 before cylinder charging. A leak in the piping network means the gas will not reach the protected room at design concentration during a fire event.
Table of Contents
ToggleTest Procedure
Prep: isolate cylinders, install blind flanges at nozzle ends. Step one: dry air or nitrogen pressurize to 50 percent of nominal working pressure, hold 5 minutes, check joints with soapy water. Step two: raise to 100 percent working pressure, hold 3 minutes, record pressure drop. Step three: drop below 50 percent, hold 10 minutes for leakage rate acceptance. Step four: vent slowly, drain condensate. Acceptance: pressure loss below 0.05MPa over 10 minutes at test pressure. Never use oxygen or compressed air with oil contamination. Witness test with fire authority representative.
Price
From $500 per room pressure test. Contact +86 13922289957 for fire system commissioning.