KITOZER
KITOZER

KITOZER Fire Pump Inspection Cabinet 45kW Auto Periodic Test

Product Overview

The KITOZER 45kW fire pump periodic inspection cabinet is a dedicated control unit that runs fire pumps at low speed on a scheduled basis to prevent long idle periods from seizing bearings, corroding impellers, or blocking pipework. Instead of running the pump at full speed and causing water hammer, the inspection cabinet uses a variable frequency drive to run the pump at a reduced speed for a set duration, then returns to standby. This satisfies fire code requirements for periodic pump testing while avoiding unnecessary water discharge and pipe stress.

Technical Specifications

Suitable motor: 45kW three phase 380V. Inspection drive: 45kW VFD, output 0 to 50Hz adjustable, default 30Hz low-speed run. Inspection duration: adjustable 2 to 10 minutes per cycle. Inspection interval: adjustable 7 to 90 days, default 7 days. Full-speed start: direct-on-line or star-delta bypass contactor. Input: 380V three phase plus neutral, 50Hz. Protection: motor overcurrent, overload inverse time, phase loss, overvoltage, undervoltage, earth fault, VFD fault, pump over-temperature. Indicators: HMI showing inspection status, next inspection date, fault history. Communication: RS485 Modbus, optional Ethernet. Dry contacts: running, fault, inspection active, remote start. Enclosure IP42 floor standing. Compliance GB 27898, GB 50974, CE.

Application Scenarios

The inspection cabinet is installed alongside the main fire pump controller in pump rooms of commercial buildings, industrial plants, underground parking garages, and high-rise towers. It pairs with sprinkler pumps, hydrant pumps, and jockey pumps that may sit idle for months between fire events. Building owners and property managers use it to satisfy local fire authority requirements for weekly or monthly pump testing without the labor cost and water damage risk of manually starting pumps at full speed.

Advantages and Features

KITOZER inspection cabinets automatically switch to full-speed pump operation the moment a fire alarm signal arrives, regardless of whether a low-speed inspection cycle is in progress. The VFD gradually ramps speed up and down, eliminating water hammer and pipe stress. The HMI logs every inspection cycle with timestamp, duration, and current drawn, producing a report that can be exported for fire authority audit. A manual bypass allows technicians to force a full-speed test on demand.

Installation and Maintenance

Mount the cabinet adjacent to the main pump controller in a clean, dry pump room. Route motor cables through separate conduit from control wiring to reduce noise. Commissioning requires setting the inspection speed to match the minimum pump speed that still provides lubrication flow, typically 25 to 30Hz. Verify that a fire alarm signal immediately overrides the inspection cycle. Maintenance: quarterly visual inspection and contactor torque; annual VFD fan filter cleaning, motor insulation test, and calibration of current sensors; every five years replace VFD DC bus capacitors and cooling fans.

Price

From $2,880 per cabinet including 45kW VFD. Contact +86 13922289957 for pump-specific sizing.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com