KITOZER
KITOZER

KITOZER Fire Suppression: Gas Cylinder Pressure Test Flow

Pre-commissioning of a KITOZER clean-agent fire suppression system requires a full nitrogen pneumatic test before agent fill. Section 1 of the pipework is pressurized to 1.5 times working pressure using dry nitrogen, held for 5 minutes, and checked with ultrasonic leak detector. Section 2 is the nozzle and branch line at 1.1 times working pressure for 3 minutes. Any pressure drop beyond 0.5 percent triggers joint rework. Never use compressed air or oxygen for the test because of oil-contamination risk.

Table of Contents

Acceptance Criteria

Record gauge readings at start, midpoint, and end. Piping then undergoes an 80 percent blowdown purge. KITOZER suppression skids ship with FM-200 or NOVEC 1230 agent options and include pressure test certificates.

Price

From $8,500 for 90L FM-200 cylinder set. Contact +86 13922289957 for suppression design.