Every clean-agent fire suppression piping network must pass a pressure test before the gas cylinder is connected. KITOZER recommends a two-stage test. First, a low-pressure air leak test at 0.35 MPa for 10 minutes, using soapy water on every joint to locate bubbles. Second, a high-pressure strength test at 1.5 times the system design pressure, typically 6.7 MPa for Novec or FM200 systems, held for 5 minutes with visible pressure gauge. Pressure drop during the hold must not exceed 1 percent of the test value. After the test, vent the air slowly, dry the piping with nitrogen, and install the cylinder only after inspection sign-off. Never use oxygen for pressure testing, because oil residue can ignite violently.
Table of Contents
ToggleStages
0.35 MPa air soap test, then 6.7 MPa hold 5 min, under 1 percent drop. KITOZER FM200 system from $4,800.