KITOZER FN12-12 10kV Load Break Switch With Fuse Combination

Product Overview

The KITOZER FN12-12 is a 10kV high voltage load break switch combined with a backup current-limiting fuse, installed inside ring main units and compact switchgear to protect distribution transformers. The switch breaks normal load currents using a sealed arc chute with three-position open-closed-earthing function, while the associated fuse clears short-circuit currents in less than 10 milliseconds. A mechanical trip linkage between the fuse striker and the switch ensures that when a fuse blows, the switch opens all three phases simultaneously, preventing single-phasing of the protected transformer.

The switch is built around a robust spring mechanism that provides fast, consistent opening and closing regardless of the operator handle speed. The three positions, closed, open, and earthed, are clearly visible through a front window, and a padlock provision allows each position to be locked. The fuse mounting holder is designed for quick replacement, with a spring-loaded contact that ensures good electrical contact even after many years of service. The arc chute is sealed and contains the arc products safely within the panel.

Technical Specifications

Rated voltage 12kV, rated current 630A, frequency 50Hz, rated load break current 630A, rated short-time withstand current 20kA for 4 seconds, rated peak making current 50kA. Fuse combination unit rated current up to 100A, back-up breaking current 50kA. Three-position positions closed, open, earthed. Arc chute sealed with SF6 gas or vacuum interrupter option.

Operating mechanism spring type, manual standard, motorized optional. Mechanical endurance 5,000 load break operations. Mounted in KYN28A or RMU cubicle. The fuse striker trip operates at 40N force, opening all three poles within 20ms. Auxiliary contact 4NO plus 4NC for position indication. Optional motor drive allows remote switching from SCADA, and a shunt trip coil allows remote electrical tripping.

Typical Applications

FN12-12 is used in 10kV ring main units, kiosk substations, and transformer feeder panels that directly protect 10kV/0.4kV distribution transformers from 100kVA to 1250kVA. It is also installed in capacitor bank feeder panels where the switch must interrupt capacitive current, and in industrial plant feeder loops that require a visible three-position isolation point.

The motorized variant supports remote switching from a SCADA or distribution automation master station, making it suitable for unmanned substations and underground cable vaults. In residential subdivision substations, the fuse-switch combination directly protects each distribution transformer, eliminating the need for a separate circuit breaker panel. In industrial plants, it feeds production line transformers and allows quick isolation for maintenance without shutting down the upstream bus.

Key Advantages

The fuse-switch combination provides the economy and fast fault clearing of fuses plus the load-break and visible isolation of a switch, in a single compact device. The three-position design gives a clearly visible open gap and a locked earth position, simplifying maintenance procedures.

The striker-linked three-phase tripping prevents single-phasing, which is the leading cause of motor and transformer damage caused by blown primary fuses. KITOZER offers a full range of matched current-limiting fuses rated from 6A to 100A to suit every transformer size. A five-year warranty covers the switch mechanism and fuse holder. The common mounting interface allows the FN12 to be retrofitted into existing KYN28A and RMU cubicles.

Installation and Maintenance

Mount the switch in the panel bay and torque the primary busbar connectors to the specified value. Fit the fuses only after all other wiring is complete, and check the striker reset pin before closing the switch. After a fuse operation, investigate the cause before replacing the fuse; do not simply reset the switch and re-energize.

Inspect the arc chute every five years, and exercise the spring mechanism once a year. Keep spare fuses on site, stored in their original packaging to avoid mechanical damage. When replacing fuses, use only KITOZER-matched fuses with the correct current rating and breaking capacity; mismatched fuses can cause failure to clear or nuisance blowing. Test the striker trip annually by manually actuating the striker pin and verifying that all three poles open.