ToggleProduct Overview
The KITOZER gas extinguishing control panel is the brains of a standalone gaseous fire suppression system, supervising detection loops, evacuation delays, release circuits, and safety interlocks for a single protected zone. The panel accepts two independent detector circuits, a manual release button, and an abort switch, and applies a two-out-of-two voting logic to prevent accidental discharge from a single detector fault. When fire is confirmed, the panel sounds the internal buzzer, activates the external alarm horn and strobe, starts a 30-second evacuation countdown, and finally triggers the solenoid release on the agent cylinder. A built-in abort input allows trained personnel to cancel release during the countdown if the alarm proves false. The panel is housed in a red steel enclosure with a front-door key switch, LCD status display, and LED indicators for power, fire, fault, discharge, and delay. It is suitable for HFC-227ea, IG541, Novec 1230, CO2, and aerosol systems.
Technical Specifications
The panel operates on 220 VAC 50 Hz with a built-in 24 VDC 7 Ah sealed lead-acid battery backup, providing at least 24 hours standby and 5 minutes of alarm operation. Two detection loops are supervised at 24 VDC, each supporting up to 20 conventional detectors with end-of-line 4.7 kohm resistors. The release circuit is rated 1 A at 24 VDC, supervised with 10 kohm end-of-line resistors, and drives one solenoid actuator. Additional outputs include one alarm relay, one fault relay, and one discharge relay, all SPDT at 30 VDC 2 A. The evacuation delay is field-adjustable from 0 to 60 seconds, and pre-discharge warning duration is programmable. Enclosure is 360 by 300 by 100 mm, IP30, red powder-coated. Operating temperature is 0 to 40 degrees Celsius, and the panel is certified to EN 12094-1 and GB 16806 standards.
Applications
The 1-zone gas extinguishing panel is used in small server rooms, electrical switchgear rooms, archive vaults, transformer bays, telecommunications cabinets, and industrial control rooms protected by a single gas cylinder or cabinet unit. For larger projects with multiple protected rooms, KITOZER offers 2-zone and 4-zone expandable panels. The panel can also be integrated with the building fire alarm system via the alarm and fault relay contacts, so the central monitoring station receives a signal whenever the gas zone activates.
Advantages and Features
KITOZER gas panels offer four practical benefits. First, the two-out-of-two voting logic dramatically reduces false discharges, which is critical because a single unwanted gas discharge can cost tens of thousands of dollars in downtime and refill. Second, the integrated abort switch allows trained staff to stop release during the countdown, preventing accidental activation during maintenance. Third, the built-in battery backup ensures the panel still works during a mains outage, when fire risk is often highest. Fourth, the clear LED and LCD interface makes it easy for building staff to interpret status without specialized training. KITOZER also provides English, Chinese, and bilingual firmware options for international projects.
Installation and Maintenance Recommendations
Mount the panel at eye level near the room exit, not inside the protected volume, so occupants can see the countdown before leaving. Route detection and release wiring in separate conduits to prevent inductive coupling from triggering the release loop. Connect the abort switch and the manual release button on the outside of the protected door, clearly labeled. During commissioning, disconnect the solenoid wiring and run a full functional test: simulate detector 1 alarm, confirm delay starts; simulate detector 2 alarm, confirm discharge output energizes at the end of delay; press abort during delay, confirm release cancels. Record all results in the commissioning log. Test the battery quarterly by disconnecting mains and verifying the panel runs on battery for 30 minutes. Replace the battery every 4 years. Price starts from $180 per panel.
Ordering and Factory Support
KITOZER supplies gas release panels in 1-zone, 2-zone, and 4-zone configurations, each with a matching battery charger, end-of-line resistors, and a wall mounting bracket. The factory ships each panel with a wiring diagram, a commissioning checklist, and a 2-year warranty. For larger projects, KITOZER can supply a complete gas release package including detectors, manual release buttons, abort switches, sounder strobes, and warning signs, all pre-wired to a common specification. Spare control boards and power supplies are stocked locally for fast replacement. KITOZER also offers a bilingual firmware option, with LCD text in English, Chinese, or both, making the panel suitable for international projects where operators speak different languages. The factory also supplies a complete set of warning signs, abort buttons, and door contacts as part of the gas release package, so the installer has every accessory needed on site. KITOZER also offers a 3-year warranty and a technical hotline for commissioning support, ensuring the release logic is correctly programmed before the protected area is handed over.