KITOZER
KITOZER

KITOZER Gas Fire Suppression System Total Flooding Overview

Product Overview

The KITOZER gas fire suppression system is a total-flooding clean-agent solution designed to protect enclosed risks such as data center server rooms, electrical switch rooms, UPS rooms, battery rooms, control rooms, archives, museums, libraries, and telecommunication hubs. Unlike sprinkler water systems, clean gas agents extinguish fires within 10 to 60 seconds without leaving residue, preventing secondary water damage to sensitive electronics. KITOZER engineers design each project based on protected volume, ceiling height, leakage area, and agent type, providing cylinder sizing, nozzle layout, piping isometrics, and hydraulic calculations. The system is approved under NFPA 2001, ISO 14520, and local fire codes.

System Components

A complete KITOZER gas suppression system includes: steel cylinder groups with valves and pressure gauges, selector valves for multiple zones, high-pressure Schedule 40 steel piping, spray nozzles, electric actuators, manual release heads, pressure switches, a gas release control panel with two-stage detection, smoke and heat detectors, door holders, alarm bells, strobe lights, and abort switches. The cylinders are filled with the selected clean agent: IG541 inert gas, HFC-227ea (HFC-227ea), FK-5-1-12 (Novec 1230 / FK-5-1-12), or CO2 for non-occupied spaces.

Design and Engineering

KITOZER performs hydraulic calculations per NFPA 2001 using pipe sizing software, ensuring agent discharge concentration reaches design level within 10 seconds and holds for 10 minutes (20 minutes for deep-seated fires). We calculate enclosure leakage area, pressure venting requirements, nozzle pressure at each outlet, and cylinder bank size. Each project includes a design drawing, bill of materials, pressure vent calculation, and a commissioning checklist. KITOZER also provides as-built drawings and training for the customer fire team.

Applications

The system protects data centers, server rooms, electrical switchgear rooms, UPS and battery rooms, process control rooms, telephone exchanges, broadcast studios, server storage libraries, archive vaults, museum galleries, chemical laboratories, and paint spray booths. It is the standard choice where water damage would be catastrophic or where occupied spaces require rapid, residue-free fire control.

Key Advantages

First, clean agent leaves no residue, no cleanup. Second, fast discharge within 10 seconds suppresses fire before equipment damage. Third, multiple agents match occupancy and environment. Fourth, multi-zone selector valves protect several rooms from one cylinder bank. Fifth, integrated detection and release logic. Sixth, global certification. Seventh, low maintenance: cylinders are inspected every 5 years, hydrotest every 12 years.

Installation and Maintenance

Installation requires certified fire suppression contractors: cylinders bolted to steel frames, piping threaded or grooved, nozzles aimed per drawing, detectors aligned, and control panel wired. Commissioning includes a gas discharge simulation using compressed air or nitrogen, detector walk test, abort switch test, and a final acceptance witnessed by the fire authority. Maintenance: quarterly visual inspection of cylinder pressure and nozzle condition, annual detector and panel test, 5-year cylinder inspection, 12-year hydrostatic test. KITOZER supplies refills and spare parts globally.

Price

From $8,500 per small room system (one 100-liter cylinder, 4 nozzles, control panel, detectors). Contact +86 13922289957 for a free design proposal based on room dimensions.