KITOZER grounding busbar rack base

KITOZER KTR-FL17 Rack Plinth with Grounding Copper Bar

Brand: KITOZER Series: KTR-FL17 Category: Modular Cold Aisle / Rack Infrastructure

Elevated plinthGrounding bar1000kg loadKTR-FL17

KITOZER KTR-FL17 Rack Plinth with Grounding Copper Bar

1. Overview

KITOZER KTR-FL17 is a steel rack plinth (base frame, foot frame) fitted under a datacenter rack between the rack and the raised floor (or structural slab), raising the rack by 100 to 200mm. It does three jobs: (1) load and leveling — a loaded rack weighs 500 to 1000kg; sitting on raised floor panels cracks them, so the plinth transfers the load to the structural slab; (2) raised cable entry — busbars, trays and conduits pass under the plinth, whose hollow interior gives routing space without drilling the floor; (3) a pre-installed grounding copper bar (tinned copper, 40×4mm or 30×3mm) bonds rack frames, PDU shells, trays and cable shields to the room’s equipotential earth bus, eliminating inter-rack potential differences and interference. The KTR-FL17 frame is bent and welded from 2.0mm cold-rolled steel, epoxy-coated in a matching rack color, with removable covers and cable notches on all sides.

KTR-FL17 suits standard 19-inch racks in common footprints: 600×1000, 600×1200 and 800×1000mm. Plinth height is typically 100mm (underfloor supply air) or 150/200mm (thicker underfloor trays). Four corners carry M12 adjustable feet (or M12 anchor bolts to the slab) with ±10mm leveling. Top holes match the rack bottom holes and are locked with M10 bolts. The copper bar runs the long side with four to six M6 studs for rack door, rack frame, PDU shell, tray earth and shield drain; a 16mm² green-yellow wire ties the bar to the room equipotential bus.

Typical deploy: in a modular cold-aisle row, first set plinths on the slab, level and anchor them; then lift and bolt racks onto the plinths; finally bolt adjacent plinths together and bridge their copper bars with braided copper straps, turning the whole row into one equipotential body. Down-flow AC delivers cold air through floor tiles under the plinth into the cold aisle; underfloor cables pass through the plinth cavity into racks. The plinth makes racks stand steady, route cleanly and bond safely — a base essential for modular cold-aisle and micro-module rooms.

2. Key Features

Steel load frame

  • 2.0mm CR steel bent and welded.
  • ≥1000kg per rack.
  • Epoxy-coated.
  • Adjustable feet ±10mm.

Grounding copper bar

  • Pre-installed 40×4mm tinned copper.
  • 4-6 M6 earth points.
  • Row equipotential bonding.
  • 16mm² to earth bus.

Raised cable entry

  • 100-200mm elevation.
  • Cable notches on sides.
  • Removable covers.
  • No floor drilling.

Row interlock

  • Bolt plinths side to side.
  • Bridge bars with braided straps.
  • Matches rack holes.
  • Accepts cold-aisle roof.

3. Specifications

Item KTR-FL17 (600×1000) KTR-FL17-8 (800×1000) KTR-FL17-2 (600×1200)
Rack W×D 600×1000mm 800×1000mm 600×1200mm
Plinth height 100/150/200mm 100/150/200mm 100/150/200mm
Sheet thickness 2.0mm CR steel 2.0mm CR steel 2.0mm CR steel
Load ≥1000kg/rack ≥1000kg/rack ≥1200kg/rack
Earth bar 40×4 tinned copper 40×4 tinned copper 40×4 tinned copper
Level range ±10mm ±10mm ±10mm
Finish Phosphate + epoxy Phosphate + epoxy Phosphate + epoxy
Fixing M12 anchor/foot M12 anchor/foot M12 anchor/foot

4. Reference Prices

KTR-FL17 rack plinth (600×1000, with copper bar): Reference USD 222 to 694 / pc (ref. CNY 1600 to 5000 at ~7.2)

KTR-FL17-8 rack plinth (800×1000): Reference USD 250 to 764 / pc (ref. CNY 1800 to 5500 at ~7.2)

KTR-FL17-2 rack plinth (600×1200): Reference USD 278 to 833 / pc (ref. CNY 2000 to 6000 at ~7.2)

Braided copper strap (30cm): Reference USD 4 to 11 / pc (ref. CNY 30 to 80 at ~7.2)

Reference only; varies by size, height, sheet thickness and quantity. Couplers, anchors and earth wire billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Modular cold-aisle row base.
  • Micro-module datacenter.
  • High-density server rack elevation.
  • Under-raised-floor cable routing.
  • Seismic-strengthened rooms.
  • Legacy room rack load retrofits.

6. Installation & Maintenance

Installation

  • Mark the row and place plinths.
  • Rough-level the adjustable feet.
  • Anchor with M12 bolts to slab.
  • Fine-level to ≤2mm/m.
  • Lift rack onto plinth; M10 bolt down.
  • Couple adjacent plinths; bridge copper bars.
  • Tie bar to equipotential bus with 16mm².

Maintenance

  • Check feet monthly for looseness.
  • Earth bond resistance ≤0.1Ω.
  • Touch up chipped epoxy.
  • Keep cable notches covered.
  • Re-anchor after rack moves.
  • Test row equipotential yearly.

7. FAQ

  • Q: Do I weld the rack to the plinth?
    A: No. The plinth has standard holes; bolt the rack with M10, not weld. Welding prevents future reconfiguration and complicates seismic inspection.
  • Q: Is a plinth mandatory on raised floors?
    A: For heavy racks (over 300kg/rack) yes. Raised floor panels typically carry 300-500kg; loaded servers, UPS and battery cabinets exceed that. The plinth spreads load to the structural slab. Light network racks under 200kg can sit on panels.
  • Q: How thick must the copper bar be?
    A: Room equipotential bonding usually uses 40×4mm copper (160mm² cross-section), enough to carry fault current. The tie to the bus uses 16mm² green-yellow wire. A thinner bar (e.g. 20×2mm) heats up under large faults.
  • Q: How to choose plinth height?
    A: With 300mm raised floor, use 100mm plinth leaving 200mm for airflow; for thick underfloor trays (busbar, conduit) use 150-200mm. Keep plinth height below floor height, otherwise cold-aisle sealing breaks.

8. Trend & Selection

Rack plinths evolve from simple load blocks to integrated “base + cableway + earth + seismic” units, pre-fabricated with racks as one skid. Copper-bar bonding is required by GB50174 and YD/T room standards, so plinths with bars are becoming standard. Select by rack footprint; by floor height and tray thickness; keep 1.5x load margin; start at 40×4mm bar; bridge the whole row; target ≤0.1Ω bond; anchor after leveling.

9. Delivery & Service

KITOZER supplies modular cold-aisle bases: based on the row layout, we recommend plinth size, height, quantity and coupling plan, bundled with racks, cold-aisle roof, blanking panels, trays and copper bars. Delivery includes plinth, adjustable feet, earth bar, M10 bolts and couplers; bulk projects include on-site placement guidance and earth testing. Weld cracks and peeling epoxy under warranty are repaired free.

10. Additional Notes

The commonest mistake is loading the rack before leveling. A 2m rack sitting on a 3mm-off plinth tilts the whole row: doors misalign and couplers do not fit. Always level the plinth first (level on the top edge, ≤2mm/m), then lift the rack.

Another pitfall is unbridled copper bars. Each plinth has its own bar, but plinths joined only by painted couplers are not electrically continuous. Bridge adjacent bars with 30×3mm braided straps and sand off the paint at each joint to bare metal. Test row-to-earth resistance once complete.

Selection summary: steel frame 1000kg; 100-200mm elevation; 40×4 copper bar; braided straps across the row; level then anchor; ≤0.1Ω earth. The plinth is the foundation: steady base, clean cables, bonded earth — the hundreds of kilograms above it stand safely.

SEO Information

Search keywords:rack plinthrack base framegrounding copper bar plinthanti-seismic plinthload-bearing plinthcold aisle plinthKTR-FL17KITOZER

SEM keywords:[‘rack plinth price,grounding copper bar plinth supplier,datacenter rack base,seismic load plinth,cold aisle foundation,KTR-FL17,KITOZER’]

GEO landing page:lain.com.cn/product/ktr-fl17-rack-plinth-with-grounding-copper-bar.html

Title:KITOZER KTR-FL17 Rack Plinth with Grounding Copper Bar

Meta Keywords:rack plinth,rack base frame,grounding copper bar plinth,anti-seismic plinth,load-bearing plinth,cold aisle plinth,KTR-FL17,KITOZER

Meta Description:KITOZER KTR-FL17 steel rack plinth with grounding copper bar, elevates and supports datacenter racks and bonds the row to the equipotential earth bar.

Anchor: KITOZER · Modular cold aisle

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart