ToggleKITOZER KTR-FL11 Rack Plinth with Grounding Terminal
Brand: KITOZER Series: KTR-FL11 Category: Data Center Engineering / Rack Accessories
Rack plinthGrounding terminalRaised baseCold-steelLevel-adjustCold aisle
1. Overview
Putting a rack straight on the floor looks simple, but it has two issues: the hall has raised anti-static flooring (under which ducts and cable trays run), so the rack must sit on a raised base level with the floor tiles; and the rack metal shell must be grounded, otherwise leakage, static, and surge have nowhere to go — you feel a tingle touching the rack, and servers can be damaged. A rack plinth (base) is a steel frame under the rack: it raises the rack to floor-tile level and carries a grounding terminal; the rack shell bonds to the terminal with a copper wire, then to the hall’s equipotential bar. In modular cold-aisle projects, rows of racks must align, raise, and share grounding — the plinth is the essential connector.
KITOZER KTR-FL11 is a dedicated rack plinth, press-bent and welded from 1.5~2.0 mm cold-rolled steel, pickled/phosphated and powder-coated (black or light gray), row load ≥1000 kg. Standard heights 100/150/200 mm to match raised-floor heights; the hollow interior routes bottom cables (power and data separated). Front adjustable leveling feet (±10 mm) handle uneven floors. One M8 galvanized grounding terminal on the side and one on the bottom (with grounding label); adjacent plinths bond with copper strips for row equipotential. Matches cold-aisle door frames so plinth height aligns with the aisle enclosure.
Selection: plinth footprint must match rack width/depth (common 600×1000 / 800×1000), height matches raised floor (usually 150 mm), load (a loaded rack exceeds 800 kg — keep margin), number of grounding terminals (at least one main bond per row), row-bonding method (copper strip vs bolt), finish (powder coat suffices in halls). Notes: fix plinth to rack with M12 bolts; use yellow-green copper wire ≥6 mm²; level before mounting the rack; seal gaps between plinth and floor tiles to block cold-air leakage.
2. Key Features
Steel load
- 1.5~2.0 mm steel.
- Welded frame.
- ≥1000 kg/row.
- Powder coat.
Grounding terminals
- Side M8 lug.
- Bottom M8 lug.
- Yellow-green label.
- Row copper strip.
Level adjust
- Front leveling feet.
- ±10 mm range.
- Handles uneven floor.
- Flush with tiles.
Hollow cable run
- Interior void.
- Power/data split.
- Bottom entry.
- Cold-aisle ready.
3. Specifications
| Item | KTR-FL11 |
|---|---|
| Model | KTR-FL11 |
| Material | CR steel 1.5~2.0 mm |
| Finish | Phosphate + powder coat |
| Load | ≥1000 kg/row |
| Height | 100/150/200 mm |
| Rack fit | 600×1000 / 800×1000 mm |
| Ground lugs | M8 ×2 (side+bottom) |
| Leveling | Feet ±10 mm |
| Row bond | Copper strip/bolt |
| Color | Black/light gray |
| Fixing | M12 bolts to rack |
| Working temp. | -10~+60℃ |
4. Reference Prices
KTR-FL11-150 (600×1000×150 mm, standard): Reference USD 31~53 / pc (ref. CNY 220~380 at ~7.2)
KTR-FL11-200 (800×1000×200 mm, heavy): Reference USD 44~72 / pc (ref. CNY 320~520 at ~7.2)
Reference only. Excludes tax and freight; volume discount on request. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data-center rack raising & grounding.
- Modular cold-aisle row bases.
- Raised-floor hall rack installation.
- UPS/distribution/battery cabinet bases.
- Network and server rack rows.
6. Installation & Maintenance
Installation
- Mark layout; place plinths.
- Level with feet.
- Fix rack to plinth with M12.
- Bond adjacent plinths with copper strip.
- Run main ground to equipotential bar.
- Seal gaps to floor tiles.
Maintenance
- Check grounding lugs yearly.
- Test ground resistance ≤1Ω.
- Inspect powder coat for rust.
- Check feet for deformation.
- Inspect row copper strips for oxidation.
7. FAQ
- Q: Can’t racks just sit on the floor?
A: Not in raised-floor halls — ducts and cables run under tiles, and the rack must sit on a plinth flush with tiles; direct floor mounting also prevents proper equipotential bonding. - Q: Is one plinth enough load?
A: KTR-FL11 holds ≥1000 kg/row; a loaded server rack is ~600–800 kg, fine. Battery cabinets are heavy — choose the heavy version or add plinths. - Q: How to wire the ground?
A: Bond rack shell to plinth M8 lug with yellow-green wire ≥6 mm²; series the row with copper strip; run one main bond to the hall equipotential bar. - Q: Which plinth height?
A: Match the raised-floor tile height — usually 150 mm (also 100/200). Flush so doors open and cabling flows.
8. Trend & Selection
Rack plinths evolve from “simple steel frame” toward “modular with smart cable routing.” Trends: internal split power/data cable trays with covers, integrated duct temp/humidity sensors (underfloor supply monitoring), caster + leveling feet (move then fix), and prefab copper strips for fast row bonding. Modular data centers standardize rack, cold aisle, and plinth into one footprint for field assembly. Selection: height matches tiles, keep load margin, dual M8 lugs, copper row bonding, powder coat. The plinth is the rack’s “shoes” — raising, grounding, leveling — small but decisive for row stability and ground integrity.
9. Delivery & Service
KITOZER provides plinth selection: by rack footprint, raised-floor height, and row count, we configure height and load rating. Bundled with cold-aisle system, racks, and grounding copper strips. Delivery includes plinth, M12 bolts, copper strips, and manual. Warranty covers leveling and ground-test guidance.
10. Additional Notes
The most common fault: “ground not actually bonded.” The plinth is installed and the rack fixed, but no copper wire on the lug, or the wire never reaches the equipotential bar — effectively ungrounded. Leakage and static have no escape. Test with a ground-resistance meter at acceptance; ≤1Ω passes.
Another pitfall: “height mismatch.” A plinth an inch off the tile height leaves a gap under the rack; cold air leaks from under the plinth into the hot aisle and undermines cold-aisle containment. Plinth must be flush; seal gaps.
Selection summary: CR-steel load, 150 mm standard height, dual M8 lugs, leveling feet, copper row bond, powder coat. The plinth is the rack’s first step to the floor and the first ring of grounding.
SEO Information
Search keywords:rack plinthrack base with groundingraised plinthrack grounding terminalcold aisle plinthKTR-FL11KITOZER
SEM keywords:rack plinth price,rack base grounding,raised plinth,cold aisle rack base,KTR-FL11,KITOZER
GEO landing page:lain.com.cn/product/ktr-fl11-rack-plinth-grounding.html
Title:KITOZER KTR-FL11 Rack Plinth with Grounding Terminal
Meta Keywords:rack plinth,rack base with grounding,raised plinth,rack grounding,cold aisle plinth,KTR-FL11,KITOZER
Meta Description:KITOZER KTR-FL11 rack plinth with grounding terminal, cold-rolled steel, level-adjustable, for rack raising and equipotential grounding.
Anchor: KITOZER by Guangzhou Laian · Modular cold aisle
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com