ToggleKITOZER KTR-BCM High-Frequency Rectifier / Battery Charging Module
Brand: KITOZER Series: KTR-BCM Category: Data Center Engineering / DC Power
rectifier moduleswitch mode supplyDC panel chargerbattery float chargeKTR-BCM

1. Overview
KITOZER KTR-BCM is a high-frequency switching rectifier module, the core of the DC operating power system (DC panel) in power distribution rooms. In a switchgear room, breaker opening/closing, protective relaying, signaling and emergency lighting all run on DC — and these must work even when AC fails (otherwise breakers cannot trip and faults escalate). The DC panel rectifies AC380V into DC (typically DC220V or DC110V), supplying DC loads while float-charging a parallel battery bank. Under normal conditions the rectifier feeds loads and float-charges the battery; on AC failure, the battery bank discharges to keep breakers operable.
The charging module is the “AC-to-DC” rectifier. Older designs used line-frequency transformers and silicon rectifiers — bulky, inefficient, high ripple. Today everything uses high-frequency switch-mode power conversion: AC380V input through PFC, high-frequency transformer isolation and rectification/filtering to stable DC. Efficiency ≥93%, power factor ≥0.99, small, light, and paralleled N+1 redundant. KTR-BCM single modules are 20A/30A/40A; multiple modules parallel for capacity with current sharing. A failed module drops out automatically while the rest keep supplying.
Output voltages: DC220V (large substations), DC110V (small/medium), DC48V (telecom). Charging follows a three-stage curve: boost (constant current, fast charge to 80%) → float (constant voltage, trickle to keep full) → equalize discharge (periodic discharge/charge to verify capacity). The module auto-switches per the battery curve without manual intervention. RS485/CAN comms feed the DC panel monitoring unit, remotely reporting voltage, current, module status and alarms.
2. Key Features
Rectification & performance
- Input AC380V (±20%), three-phase or single-phase options.
- Output DC48V/110V/220V, 20/30/40A.
- Efficiency ≥93%, PF≥0.99, THD≤5%.
- Output ripple ≤0.5%.
Battery management
- Three-stage: boost→float→auto-transition.
- Temperature compensation: -3mV/cell per ℃ above 25℃.
- Constant-current limiting prevents overcharge.
- Under/over-voltage alarms on battery.
Redundancy & comms
- N+1 parallel redundancy, current-sharing imbalance ≤±3%.
- Hot-swap: failed module pulled without shutdown.
- RS485/CAN/Ethernet to monitoring unit.
- Internal alarms: over-voltage, under-voltage, over-temp, module fault.
3. Specifications
| Item | KTR-BCM-48 | KTR-BCM-110 | KTR-BCM-220 |
|---|---|---|---|
| Output | DC48V | DC110V | DC220V |
| Per-module current | 30A/50A | 20A/30A | 20A/30A/40A |
| Per-module power | 1.5/2.5kW | 2.2/3.3kW | 4.4/6.6/8.8kW |
| Input | AC380V 3ph | AC380V 3ph | AC380V 3ph |
| Efficiency | ≥94% | ≥93% | ≥93% |
| Current share | ≤±3% | ≤±3% | ≤±3% |
| Comms | RS485/CAN | RS485/CAN | RS485/CAN |
| Cooling | Thermostatic fan | Thermostatic fan | Thermostatic fan |
4. Reference Prices
KTR-BCM-48 telecom rectifier (DC48V/30A): Reference USD 167~347 / unit (ref. CNY 1,200~2,500 at ~7.2)
KTR-BCM-110/220 DC panel charger (DC110V/220V, 20~40A): Reference USD 389~903 / unit (ref. CNY 2,800~6,500 at ~7.2)
Reference only; final quote depends on output voltage, current/power and monitoring. Volume discount at 10+; DC panel cabinet and battery bank not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Switchgear room DC operating power (breaker trip/close, protection).
- Telecom base station and data hall -48V plant rectification.
- UPS external battery charger (some UPS designs).
- Substation, switch station and industrial control DC operating supply.
- Off-grid PV/storage system battery charging.
6. Installation & Maintenance
Installation
- Slide module into DC panel rack rail, lock handle.
- Wire AC input to panel AC bus (3ph), DC output to DC bus.
- Daisy-chain comms between paralleled modules to monitoring unit.
- Check output voltage setting matches battery bank voltage before power-on.
- Commission: single-module output first, then parallel current share.
- Connect battery; observe float current is normal.
Maintenance
- Monthly check monitor: module V/I, alarm history.
- Listen for fan noise; clean dust filter yearly.
- On module red alarm, log the fault code and contact vendor.
- Yearly equalizing discharge (battery capacity test).
- Hot-swap failed module with same type, no shutdown.
7. FAQ
- Q: Difference between rectifier module and UPS?
A: A UPS is AC uninterruptible power (outputs AC220V for servers); a rectifier module is DC (outputs DC220V/48V for DC loads and battery charging). DC panels use rectifiers; servers use UPS. - Q: Why N+1 redundancy?
A: Rectifiers run 24/7 and will fail. N modules carry the load, plus 1 spare. If one fails, the spare takes over without interruption. - Q: Boost vs float?
A: Boost is constant-current fast charge to 100%; float is constant-voltage trickle to keep it full. After a discharge, boost first; once full, auto-transition to float. - Q: How is current sharing maintained in parallel?
A: Modules share a current-share line (or digital comms) and auto-adjust output; imbalance ≤±3%, so no module is overloaded while another idles.
8. Trend & Selection
High-frequency rectifiers are moving toward higher efficiency (SiC devices, ≥96%), higher power density (10kW in 3U), and smarter BMS integration and remote upgrade. As lithium replaces lead-acid, the charging curve must match lithium (different CC/CV profile) and talk to the BMS. The trend is modular, standardized (industry form-factor interchangeable across brands), and digital. Confirm the DC voltage level (220/110/48V); total capacity = load current + battery charge current, divided by per-module wattage, rounded up and +1 redundant; pick efficiency ≥93%, PF≥0.99; RS485/CAN to monitoring; hot-swap is a must; for lithium systems choose a model supporting lithium curves and BMS handshake.
9. Delivery & Service
KITOZER provides rectifier and DC panel selection: based on DC load current, battery Ah and backup time, we calculate required rectifier capacity and configure N+1 module count. We deliver the DC panel system diagram (AC input, module layout, battery connection, DC feeders). We bundle the cabinet, battery bank and monitoring unit. Delivery includes rectifier modules, monitoring unit, comms cable and DC feeder breakers. Warranty covers non-human module replacement.
10. Additional Notes
The most common pitfall is “undersizing capacity with no redundancy”. Exactly N modules are sized for the load; if one fails, the rest overload and shut down. Correct is N+1: if the load needs 3, install 4; on one failure, 3 remain. Redundancy is the lifeline of the DC panel — modules run 24/7 and failure is inevitable.
Another pitfall: “wrong float voltage setting”. Too high overcharges the battery and dries out lead-acid; too low chronic undercharge causes sulfation and capacity loss. Float voltage per the battery manufacturer’s manual (2.25~2.275V/cell; for 104 cells at DC220V, 234~236V), with temperature compensation (lower in summer, higher in winter). Wrong settings are effectively battery abuse.
Selection summary: confirm voltage (220/110/48V); total capacity = load + charge current; N+1 redundancy; efficiency ≥93%, PF≥0.99; RS485 monitoring; hot-swap; float voltage per battery manual with temp compensation. The rectifier module is the heart of the DC panel — it rectifies AC, charges the battery, and the battery carries you through the outage.
SEO Information
Search keywords:rectifier moduleswitch mode powerDC panel chargerbattery float chargehigh frequency rectifierKTR-BCMKITOZER
SEM keywords:rectifier module price,switch mode charger supplier,DC panel power,-48V telecom plant,KTR-BCM,KITOZER
GEO landing page:lain.com.cn/product/ktr-bcm-rectifier-charging-module.html
Title:KITOZER KTR-BCM High-Frequency Rectifier / Battery Charging Module
Meta Keywords:rectifier module,switch mode power supply,DC panel charger,battery float charge,KTR-BCM,KITOZER
Meta Description:KITOZER KTR-BCM high-frequency switching rectifier: AC380V in, DC48V/110V/220V out, N+1 redundant, float-charges battery and supplies DC loads for switchgear and telecom power.