Table of Contents
Toggle1. System Overview
The KITOZER high voltage switchgear system is core medium-voltage power distribution equipment covering 3.6kV ~ 40.5kV. It integrates circuit breakers, relay protection, measurement & control, communication and condition monitoring functions. It is applied to power transmission, generation and distribution for power switching, control, protection and metering, ensuring safe and stable operation of power grids and equipment.
Adopting a metal-clad enclosed structure, the system strictly implements the “Five Prevention” interlock functions:
- Prevent accidental closing/opening of circuit breakers
- Prevent opening/closing disconnectors under load
- Prevent earthing wire connection to live equipment
- Prevent closing circuit breakers with earthing wires connected
- Prevent access to live compartments
It features high reliability, safety and maintainability. Customizable design is available according to load levels and environmental conditions for conventional industry, new energy (photovoltaic/wind power/energy storage), data centers, rail transit, municipal construction and other scenarios.

KITOZER High Voltage Switchgear
2. System Composition
The system consists of four major parts: primary main circuit, secondary control & protection circuit, cabinet structure and intelligent monitoring modules.
Primary Main Circuit (High Voltage Section)
Vacuum circuit breaker (core switching device), disconnector/earthing switch, current transformer (CT), voltage transformer (PT), lightning arrester, main busbar, branch busbar, cable terminal, contact system, insulating components (epoxy resin / eco-friendly gas).
Secondary Control & Protection Circuit (Low Voltage Section)
Microcomputer protection device, measurement & control unit, intelligent control device, power quality monitoring meter, temperature & humidity controller, heating & dehumidifier, indicator lights/buttons, terminal block, communication interface (RS485 / Ethernet).
Cabinet Structure
Cold-rolled steel / aluminized zinc steel cabinet divided into circuit breaker compartment, busbar compartment, cable compartment, relay & instrument compartment and top small busbar compartment; equipped with pressure relief windows, ventilation heat dissipation holes, earthing devices, mechanical interlocks, door locks & hinges.
Intelligent Monitoring Modules
Wireless temperature measuring sensors (contacts / busbars), partial discharge monitoring unit (ultrasonic / UHF), arc flash protection sensor, SF6 gas monitor (eco-friendly type), optional video surveillance.
3. System Classification
3.1 Classification by Circuit Breaker Installation Type
- Draw-out type (handcart type, KYN series): Circuit breakers installed on extractable handcarts with strong interchangeability, high power supply reliability and convenient maintenance. Main models: KYN28A-12 (12kV), KYN61-40.5 (40.5kV).
- Fixed type (XGN/GG series): Fixed-mounted circuit breakers with simple and economical structure, suitable for small power distribution systems. Main models: XGN2-10, GG-1A.
- Ring main unit (HXGN series): Compact design fitted with load switches/fuses for ring network power supply and terminal power distribution. Main model: HXGN12-12.

High Voltage Switchgear General Layout Drawing
3.2 Classification by Voltage Level
- Medium voltage 12kV: Mainstream power distribution grade covering industry, construction and new energy power stations.
- Medium voltage 24kV: High-density load scenarios (data centers, large factories).
- Medium voltage 40.5kV: Regional power distribution, small & medium power plants and new energy booster stations.
3.3 Classification by Insulation Medium
- Air Insulated Switchgear (AIS): Conventional cabinets with air as insulation medium, low cost for standard environments.
- Solid Insulated Switchgear (SIS): Busbars and switching components encapsulated with epoxy resin, isolated from moisture/dust with service life ≥30 years, ideal for high-pollution/high-humidity scenarios.
- Eco-friendly Gas Insulated Switchgear (GIS): C4F7N/CF3I low GWP gas replaces SF6 with equivalent insulation and arc extinction performance, greenhouse effect less than 1% of SF6, the preferred option for green low-carbon scenarios.
3.4 Classification by Functional Purpose
- Incoming cabinet: Power supply access equipped with main circuit breakers and differential protection.
- Outgoing cabinet: Load distribution fitted with feeder circuit breakers, overcurrent & instantaneous protection.
- Bus coupler cabinet: Busbar connection with Busbar Transfer (BZT) function, charging protection and anti-false closing logic.
- PT cabinet: Voltage monitoring, metering and overvoltage protection equipped with voltage transformers and lightning arresters.
- Metering cabinet: Electric energy metering with high-precision CT/PT and energy meters.
- Capacitor cabinet: Reactive power compensation to improve power factor.
- Station Transformer Cabinet: Station power conversion fitted with dry-type transformers.
4. System Schematic Diagrams
4.1 Primary System Schematic (12kV Single Busbar Sectionalized)
4.2 Secondary Control & Protection Schematic (Incoming Cabinet Example)
- Three-phase power supply → CT → Microcomputer protection device → Circuit breaker trip coil
- PT → Protection device → Voltage monitoring / Overvoltage protection
- Intelligent control device → Closing & opening control, status display, temperature & humidity monitoring
- Communication interface → SCADA/EMS system for remote monitoring and data uploading

On-site Installation of High Voltage Switchgear
5. Full System Configuration List (Basic / Standard / High-End, Brand: KITOZER)
5.1 Low-Grade Configuration List (Basic Type, 12kV/630A/20kA)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | High Voltage Switchgear (Incoming Cabinet) | KYN28A-12-J | Rated voltage:12kV; Rated current:630A; Short-time withstand current:20kA/4s; Peak withstand current:50kA; Protection class:IP4X; Dimension:800×1500×2200mm | 1 | Set | KITOZER | Air insulated, cold-rolled steel plate |
| 2 | High Voltage Switchgear (Outgoing Cabinet) | KYN28A-12-C | Rated voltage:12kV; Rated current:630A; Short-time withstand current:20kA/4s; Peak withstand current:50kA; Protection class:IP4X; Dimension:800×1500×2200mm | 2 | Set | KITOZER | Air insulated, cold-rolled steel plate |
| 3 | High Voltage Switchgear (PT Cabinet) | KYN28A-12-PT | Rated voltage:12kV; PT ratio:10/0.1kV; Protection class:IP4X; Dimension:800×1500×2200mm | 1 | Set | KITOZER | Air insulated, cold-rolled steel plate |
| 4 | Vacuum Circuit Breaker | VS1-12/630-20 | Rated voltage:12kV; Rated current:630A; Short-circuit breaking current:20kA; Mechanical life:10,000 times, handcart type | 3 | Set | KITOZER | For incoming/outgoing cabinets |
| 5 | Current Transformer | LZZBJ9-10 600/5A | Rated voltage:10kV; Ratio:600/5A; Accuracy class:0.5/10P10; Rated burden:10VA | 6 | Set | KITOZER | 2 sets each for incoming/outgoing cabinets |
| 6 | Voltage Transformer | JDZJ-10 10/0.1/0.1kV | Rated voltage:10kV; Ratio:10/0.1/0.1kV; Accuracy class:0.5/3P; Rated burden:30VA | 3 | Set | KITOZER | Dedicated for PT cabinet |
| 7 | Zinc Oxide Lightning Arrester | HY5WZ-17/45 | Rated voltage:17kV; Continuous operating voltage:13.6kV; Residual voltage:45kV; Nominal discharge current:5kA | 3 | Set | KITOZER | For PT/incoming cabinets |
| 8 | Microcomputer Protection Device | KZ-100 | Protection functions: overcurrent, instantaneous trip, zero-sequence, overvoltage, undervoltage; Communication:RS485; Accuracy:±0.5% | 3 | Set | KITOZER | For incoming/outgoing/PT cabinets |
| 9 | Intelligent Control Device | KZ-C10 | Closing/opening control, status display, temperature & humidity monitoring, heating & dehumidification; Communication:RS485 | 4 | Set | KITOZER | 1 set per cabinet |
| 10 | Temperature & Humidity Controller | KZ-WS | Temperature range:-20℃~+60℃; Humidity range:0~100% RH; Heating/dehumidification output | 4 | Set | KITOZER | 1 set per cabinet |
| 11 | Heating & Dehumidifier | KZ-JR | Power:100W; Voltage:AC220V, anti-condensation | 4 | Set | KITOZER | 1 set per cabinet |
| 12 | Main Busbar | TMY-60×6 | Material:copper; Size:60×6mm; Rated current:1250A | 10 | Meter | KITOZER | Tin-plated pure copper |
| 13 | Earthing Switch | JN15-12 | Rated voltage:12kV; Rated short-time withstand current:20kA/4s; Mechanical life:2,000 times | 4 | Set | KITOZER | 1 set per cabinet |
| 14 | Mechanical Interlock Device | KZ-L10 | “Five Prevention” interlock, dual mechanical & electrical locking | 4 | Set | KITOZER | 1 set per cabinet |
5.2 Medium-Grade Configuration List (Standard Type, 12kV/1250A/31.5kA, Intelligent Upgrade)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | High Voltage Switchgear (Incoming Cabinet) | KYN28A-12-JS | Rated voltage:12kV; Rated current:1250A; Short-time withstand current:31.5kA/4s; Peak withstand current:80kA; Protection class:IP5X; Dimension:1000×1800×2400mm; Aluminized zinc steel plate | 1 | Set | KITOZER | Air insulated, intelligent monitoring |
| 2 | High Voltage Switchgear (Outgoing Cabinet) | KYN28A-12-CS | Rated voltage:12kV; Rated current:1250A; Short-time withstand current:31.5kA/4s; Peak withstand current:80kA; Protection class:IP5X; Dimension:1000×1800×2400mm; Aluminized zinc steel plate | 3 | Set | KITOZER | Air insulated, intelligent monitoring |
| 3 | High Voltage Switchgear (Bus Coupler Cabinet) | KYN28A-12-ML | Rated voltage:12kV; Rated current:1250A; Short-time withstand current:31.5kA/4s; Peak withstand current:80kA; Protection class:IP5X; Dimension:1000×1800×2400mm; Aluminized zinc steel plate | 1 | Set | KITOZER | Air insulated, intelligent monitoring |
| 4 | High Voltage Switchgear (PT Cabinet) | KYN28A-12-PTS | Rated voltage:12kV; PT ratio:10/0.1kV; Protection class:IP5X; Dimension:800×1800×2400mm; Aluminized zinc steel plate | 1 | Set | KITOZER | Air insulated, intelligent monitoring |
| 5 | Vacuum Circuit Breaker | VS1-12/1250-31.5 | Rated voltage:12kV; Rated current:1250A; Short-circuit breaking current:31.5kA; Mechanical life:15,000 times, handcart electric operation | 5 | Set | KITOZER | For incoming/outgoing/bus coupler cabinets |
| 6 | Current Transformer | LZZBJ9-10 1250/5A | Rated voltage:10kV; Ratio:1250/5A; Accuracy class:0.2S/10P20; Rated burden:15VA | 10 | Set | KITOZER | 2 sets each for incoming/outgoing/bus coupler cabinets |
| 7 | Voltage Transformer | JDZJ-10 10/0.1/0.1kV | Rated voltage:10kV; Ratio:10/0.1/0.1kV; Accuracy class:0.2S/3P; Rated burden:50VA | 3 | Set | KITOZER | Dedicated for PT cabinet |
| 8 | Zinc Oxide Lightning Arrester | HY5WZ-17/45 | Rated voltage:17kV; Continuous operating voltage:13.6kV; Residual voltage:45kV; Nominal discharge current:10kA | 3 | Set | KITOZER | For PT/incoming cabinets |
| 9 | Microcomputer Protection Device | KZ-200 | Protection functions: differential, overcurrent, instantaneous trip, zero-sequence, overvoltage, undervoltage, breaker failure; Communication:Ethernet/RS485; Accuracy:±0.2% | 5 | Set | KITOZER | For incoming/outgoing/bus coupler/PT cabinets |
| 10 | Intelligent Control Device | KZ-C20 | Closing/opening control, status display, temperature & humidity monitoring, heating & dehumidification, wireless temperature measurement reception; Communication:Ethernet/RS485 | 6 | Set | KITOZER | 1 set per cabinet |
| 11 | Wireless Temperature Measuring Sensor | KZ-TW | Measuring range:-50℃~+125℃; Accuracy:±0.5℃; Transmission distance:≥50m; Service life of battery:≥5 years | 24 | Piece | KITOZER | For circuit breaker contacts / busbar lap joints |
| 12 | Partial Discharge Monitoring Unit | KZ-JF | Monitoring mode:Ultrasonic + UHF; Sensitivity:≤10pC; Communication:Ethernet; Adjustable early warning & alarm thresholds | 6 | Set | KITOZER | 1 set per cabinet |
| 13 | Arc Flash Protection Sensor | KZ-HG | Response time:≤1ms; Monitoring angle:180°; Communication:Ethernet; Fault location | 6 | Piece | KITOZER | For circuit breaker / busbar compartments |
| 14 | Power Quality Monitoring Meter | KZ-PQ | Monitored parameters:voltage/current/frequency/power/harmonics; Accuracy:0.2S class; Communication:Ethernet | 6 | Set | KITOZER | 1 set per cabinet |
| 15 | Temperature & Humidity Controller | KZ-WS | Temperature range:-20℃~+60℃; Humidity range:0~100% RH; Heating/dehumidification output; Communication:RS485 | 6 | Set | KITOZER | 1 set per cabinet |
| 16 | Heating & Dehumidifier | KZ-JR | Power:150W; Voltage:AC220V, anti-condensation with temperature control | 6 | Set | KITOZER | 1 set per cabinet |
| 17 | Main Busbar | TMY-80×8 | Material:copper; Size:80×8mm; Rated current:2000A | 15 | Meter | KITOZER | Tin-plated pure copper with insulation coating |
| 18 | Earthing Switch | JN15-12 | Rated voltage:12kV; Rated short-time withstand current:31.5kA/4s; Mechanical life:3,000 times, electric operation | 6 | Set | KITOZER | 1 set per cabinet |
| 19 | Mechanical Interlock Device | KZ-L20 | “Five Prevention” interlock, dual mechanical & electrical locking with electric interlock | 6 | Set | KITOZER | 1 set per cabinet |
| 20 | Intelligent Communication Gateway | KZ-GW | Protocol conversion:IEC61850/Modbus-RTU/Profinet; Interfaces:4×Ethernet / 2×RS485; Data encryption | 1 | Set | KITOZER | System data aggregation |
5.3 High-Grade Configuration List (Premium Type, 40.5kV/3150A/40kA, Eco-Friendly Intelligent)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | High Voltage Switchgear (Incoming Cabinet) | KYN61-40.5-JG | Rated voltage:40.5kV; Rated current:3150A; Short-time withstand current:40kA/4s; Peak withstand current:100kA; Protection class:IP55; Dimension:1200×2000×2600mm; Eco-friendly gas insulated (C4F7N) | 1 | Set | KITOZER | Eco-friendly gas insulated, intelligent monitoring |
| 2 | High Voltage Switchgear (Outgoing Cabinet) | KYN61-40.5-CG | Rated voltage:40.5kV; Rated current:3150A; Short-time withstand current:40kA/4s; Peak withstand current:100kA; Protection class:IP55; Dimension:1200×2000×2600mm; Eco-friendly gas insulated (C4F7N) | 4 | Set | KITOZER | Eco-friendly gas insulated, intelligent monitoring |
| 3 | High Voltage Switchgear (Bus Coupler Cabinet) | KYN61-40.5-MLG | Rated voltage:40.5kV; Rated current:3150A; Short-time withstand current:40kA/4s; Peak withstand current:100kA; Protection class:IP55; Dimension:1200×2000×2600mm; Eco-friendly gas insulated (C4F7N) | 1 | Set | KITOZER | Eco-friendly gas insulated, intelligent monitoring |
| 4 | High Voltage Switchgear (PT Cabinet) | KYN61-40.5-PTG | Rated voltage:40.5kV; PT ratio:35/0.1kV; Protection class:IP55; Dimension:1000×2000×2600mm; Eco-friendly gas insulated (C4F7N) | 1 | Set | KITOZER | Eco-friendly gas insulated, intelligent monitoring |
| 5 | Vacuum Circuit Breaker | ZN85-40.5/3150-40 | Rated voltage:40.5kV; Rated current:3150A; Short-circuit breaking current:40kA; Mechanical life:20,000 times, handcart electric/spring operation | 6 | Set | KITOZER | For incoming/outgoing/bus coupler cabinets |
| 6 | Current Transformer | LZZBJ9-35 3000/5A | Rated voltage:35kV; Ratio:3000/5A; Accuracy class:0.2S/10P20; Rated burden:20VA; Insulation level:40.5kV | 12 | Set | KITOZER | 2 sets each for incoming/outgoing/bus coupler cabinets |
| 7 | Voltage Transformer | JDZJ-35 35/0.1/0.1kV | Rated voltage:35kV; Ratio:35/0.1/0.1kV; Accuracy class:0.2S/3P; Rated burden:50VA; Insulation level:40.5kV | 3 | Set | KITOZER | Dedicated for PT cabinet |
| 8 | Zinc Oxide Lightning Arrester | HY5WZ-51/134 | Rated voltage:51kV; Continuous operating voltage:40.8kV; Residual voltage:134kV; Nominal discharge current:20kA; Insulation level:40.5kV | 3 | Set | KITOZER | For PT/incoming cabinets |
| 9 | Microcomputer Protection Device | KZ-300 | Protection functions: differential, overcurrent, instantaneous trip, zero-sequence, overvoltage, undervoltage, breaker failure, reclosing; Communication:IEC61850/Ethernet; Accuracy:±0.1%; Dual power redundancy | 6 | Set | KITOZER | For incoming/outgoing/bus coupler/PT cabinets |
| 10 | Intelligent Control Device | KZ-C30 | Closing/opening control, status display, temperature & humidity monitoring, heating & dehumidification, wireless temperature measurement reception, partial discharge data display; Communication:IEC61850/Ethernet, touch screen | 7 | Set | KITOZER | 1 set per cabinet |
| 11 | Wireless Temperature Measuring Sensor | KZ-TW-G | Measuring range:-50℃~+150℃; Accuracy:±0.3℃; Transmission distance:≥100m; Service life of battery:≥8 years, high temperature resistance | 28 | Piece | KITOZER | For circuit breaker contacts / busbar lap joints / cable terminals |
| 12 | Partial Discharge Monitoring Unit | KZ-JF-G | Monitoring mode:Ultrasonic + UHF + High-frequency current; Sensitivity:≤5pC; Communication:IEC61850/Ethernet; AI algorithm early warning; Positioning accuracy:≤30cm | 7 | Set | KITOZER | 1 set per cabinet |
| 13 | Arc Flash Protection Sensor | KZ-HG-G | Response time:≤0.5ms; Monitoring angle:360°; Communication:IEC61850/Ethernet; Fault location + partition tripping | 7 | Piece | KITOZER | For circuit breaker / busbar / cable compartments |
| 14 | SF6 / Eco-Friendly Gas Monitor | KZ-QT | Monitored gas:C4F7N/SF6; Concentration range:0~100%; Accuracy:±1%; Leakage alarm; Communication:Ethernet | 7 | Set | KITOZER | 1 set per cabinet |
| 15 | Power Quality Monitoring Meter | KZ-PQ-G | Monitored parameters:voltage/current/frequency/power/harmonics/transient/flicker; Accuracy:0.1S class; Communication:IEC61850/Ethernet, waveform recording function | 7 | Set | KITOZER | 1 set per cabinet |
| 16 | Temperature & Humidity Controller | KZ-WS-G | Temperature range:-40℃~+70℃; Humidity range:0~100% RH; Heating/dehumidification output; Communication:IEC61850/Ethernet, dual-circuit control | 7 | Set | KITOZER | 1 set per cabinet |
| 17 | Heating & Dehumidifier | KZ-JR-G | Power:200W; Voltage:AC220V/DC220V, anti-condensation with temperature/humidity control, corrosion resistance | 7 | Set | KITOZER | 1 set per cabinet |
| 18 | Main Busbar | TMY-100×10 | Material:copper; Size:100×10mm; Rated current:4000A; Silver-plated pure copper with insulation coating and heat shrink protection | 20 | Meter | KITOZER | Dedicated for eco-friendly gas insulated cabinets |
| 19 | Earthing Switch | JN15-40.5 | Rated voltage:40.5kV; Rated short-time withstand current:40kA/4s; Mechanical life:5,000 times, electric/spring operation with position monitoring | 7 | Set | KITOZER | 1 set per cabinet |
| 20 | Mechanical Interlock Device | KZ-L30 | “Five Prevention” interlock, triple mechanical + electrical + intelligent locking with electric interlock and status monitoring | 7 | Set | KITOZER | 1 set per cabinet |
| 21 | Intelligent Communication Gateway | KZ-GW-G | Protocol conversion:IEC61850/Modbus-RTU/Profinet/DNP3; Interfaces:8×Ethernet / 4×RS485 / 2×Optical fiber; Data encryption + redundant backup, edge computing | 2 | Set | KITOZER | System data aggregation + redundancy |
| 22 | Intelligent Monitoring Platform | KZ-MP | Functions: real-time monitoring, fault early warning, data analysis, report generation, remote operation & maintenance, video linkage; Deployment: local / cloud, multi-level user authority management | 1 | Set | KITOZER | System management center |
6. Full Product Technical Parameters

Finished High Voltage Switchgear Workshop
6.1 Cabinet Parameters of High Voltage Switchgear
- Rated voltage: 3.6kV, 7.2kV, 12kV, 24kV, 40.5kV
- Rated current: 630A, 1000A, 1250A, 1600A, 2000A, 2500A, 3150A, 4000A
- Rated short-time withstand current (Icw): 20kA, 25kA, 31.5kA, 40kA (4s)
- Rated peak withstand current (Ipk): 50kA, 63kA, 80kA, 100kA
- Protection class: IP4X (Basic), IP5X (Standard), IP55 (Premium)
- Cabinet material: Cold-rolled steel (Basic), Aluminized zinc steel (Standard), Stainless steel (Premium)
- Dimension (Width × Depth × Height, mm): 12kV: 800/1000×1500/1800×2200/2400 40.5kV: 1200×2000×2600
- Insulation level: 12kV: Power frequency withstand voltage 42kV/1min, Lightning impulse withstand voltage 75kV (peak) 40.5kV: Power frequency withstand voltage 95kV/1min, Lightning impulse withstand voltage 185kV (peak)
- Environmental conditions: Temperature: -15℃~+40℃ (Basic), -40℃~+70℃ (Premium) Humidity: Daily average ≤95% RH, Monthly average ≤90% RH Altitude: ≤1000m (Standard), reinforced insulation required for altitude>1000m Pollution class: Class III (Standard), Class IV (High pollution)
6.2 Vacuum Circuit Breaker Parameters (VS1/ZN85 Series)
- Rated voltage: 12kV (VS1), 40.5kV (ZN85)
- Rated current: 630A ~ 3150A
- Rated short-circuit breaking current: 20kA, 25kA, 31.5kA, 40kA
- Rated short-circuit making current: 2.5 times breaking current (peak value)
- Mechanical life: 10,000 times (Basic), 15,000 times (Standard), 20,000 times (Premium)
- Operating mechanism: Electromagnetic (Basic), Spring (Standard), Electric/Spring (Premium)
- Opening & closing time: Opening ≤0.06s, Closing ≤0.1s
6.3 Transformer Parameters (CT/PT)

Primary Circuit Schematic Drawing
Current Transformer (LZZBJ9 Series)
- Rated voltage: 10kV, 35kV
- Ratio: 200/5A ~ 3000/5A
- Accuracy class: 0.5/10P10 (Basic), 0.2S/10P20 (Standard/Premium)
- Rated burden: 10VA ~ 20VA
Voltage Transformer (JDZJ Series)
- Rated voltage: 10kV, 35kV
- Ratio: 10/0.1/0.1kV, 35/0.1/0.1kV
- Accuracy class: 0.5/3P (Basic), 0.2S/3P (Standard/Premium)
- Rated burden: 30VA ~ 50VA
6.4 Microcomputer Protection Device Parameters (KZ-100/200/300)
Protection Functions
- Basic: Overcurrent, Instantaneous trip, Zero-sequence, Overvoltage, Undervoltage
- Standard: Plus differential protection, breaker failure protection, reclosing
- Premium: Plus transient protection, harmonic protection, frequency protection
Measurement Accuracy
±0.5% (Basic), ±0.2% (Standard), ±0.1% (Premium)
Communication Interfaces
RS485 (Basic), Ethernet + RS485 (Standard), IEC61850 + Ethernet (Premium)
Operating Power Supply
AC220V/DC220V, dual power redundancy (Premium)
6.5 Intelligent Monitoring Module Parameters
Wireless Temperature Measuring Sensor (KZ-TW)
- Measuring range: -50℃~+125℃ (Basic), -50℃~+150℃ (Premium)
- Accuracy: ±0.5℃ (Basic), ±0.3℃ (Premium)
- Transmission distance: ≥50m (Basic), ≥100m (Premium)
- Battery service life: ≥5 years (Basic), ≥8 years (Premium)
Partial Discharge Monitoring Unit (KZ-JF)
- Monitoring mode: Ultrasonic + UHF (Standard), Ultrasonic + UHF + High-frequency current (Premium)
- Sensitivity: ≤10pC (Standard), ≤5pC (Premium)
- Communication: Ethernet (Standard), IEC61850 + Ethernet (Premium)
Arc Flash Protection Sensor (KZ-HG)
- Response time: ≤1ms (Standard), ≤0.5ms (Premium)
- Monitoring angle: 180° (Standard), 360° (Premium)
- Communication: Ethernet (Standard), IEC61850 + Ethernet (Premium)
7. Full Product Application Scope

Internal Busbar Layout of Switchgear
7.1 Industrial Sector
- Manufacturing: Automobile manufacturing, iron & steel metallurgy, chemical industry, textile, food processing factory power distribution workshops, production line power supply, motor control
- Mining & Energy: Coal mines, metal mines, photovoltaic power stations, wind farms, energy storage power stations, hydropower booster stations & distribution rooms
- Data Centers: IDC computer rooms, cloud computing center high voltage power distribution, UPS front-end power supply, backup power switching
7.2 Construction & Municipal Engineering
- Commercial Buildings: Large shopping malls, office buildings, hotels, exhibition centers high voltage power distribution rooms, emergency power supply systems
- Residential & Public Facilities: High-rise residential quarters, hospitals, schools, stadiums, airports, railway stations, subway power distribution systems
- Municipal Projects: Urban power grid renovation, substation construction, street lighting power distribution, water supply & drainage pump station power supply
7.3 New Energy Sector
- Photovoltaic Power Stations: Centralized / distributed photovoltaic booster stations, 12kV/35kV combiner boxes, inverter front-end power distribution
- Wind Farms: Onshore / offshore wind farm 35kV booster stations, wind turbine box transformer high-voltage side protection, collector line power distribution
- Energy Storage Power Stations: Lithium battery energy storage system 12kV/35kV high voltage power distribution, PCS front-end protection, grid-connected interface equipment
7.4 Transportation Sector
- Rail Transit: Subway, light rail, high-speed railway traction substations, step-down substations, signal system power supply
- Ports & Terminals: Container terminals, bulk cargo terminals high voltage power distribution, crane power supply, port lighting systems
8. Full Product Advantages

Intelligent Central Monitoring Platform
8.1 Core Functional Features
- High Safety: Fully enclosed metal structure with “Five Prevention” interlock design, arc isolation and pressure relief devices to prevent misoperation and arc fault spread
- High Reliability: Self-developed high-quality core components, modular design, anti-vibration & anti-interference performance suitable for harsh environments; intelligent monitoring early warning to eliminate hidden dangers in advance and reduce failure rate
- High Intelligence: Integrated microcomputer protection, measurement & control, communication and condition monitoring (temperature measurement / partial discharge / arc flash), supporting remote monitoring, operation & maintenance and fault diagnosis, applicable to smart power grids and unattended scenarios
- Eco-Friendly & Energy Saving: Premium models adopt eco-friendly gas insulation to replace SF6, low-loss design reduces energy consumption and carbon emissions; oil-free equipment avoids oil pollution
- Flexible Customization: Custom design & production according to user voltage level, current capacity, short-circuit parameters, functional requirements (intelligent / eco-friendly / explosion-proof) and environmental conditions (high temperature / low temperature / humid / polluted)
8.2 Customization & OEM/ODM Capacity
- Custom Design: Support non-standard dimensions, special functions (explosion-proof / anti-corrosion / high temperature resistance), special voltage/current parameter customization; adapt to old equipment renovation and special scenarios (offshore / plateau / high pollution)
- OEM/ODM Processing: Provide OEM labeling, drawing processing and complete set assembly services; produce strictly in accordance with customer standards and brand requirements to guarantee consistent quality; full-process confidentiality to protect customer intellectual property and commercial secrets
- Fast Delivery: Standardized modules + flexible production lines, mainstream 12kV models in stock for spot supply; customized models shorten production cycle to respond quickly to urgent customer demands
8.3 Technical & Quality Advantages
- Self-Developed Core Technology: Master core technologies of high voltage switches, intelligent protection and condition monitoring with over 50 patents; continuous technical iteration, product performance reaches international advanced level
- Strict Quality Control: Raw material incoming inspection, full-process production inspection, factory type test (insulation / voltage withstand / short-circuit / temperature rise); certified by ISO9001 quality system, national 3C certification and type test certification, complying with national standards GB/T 3906, DL/T 404 etc.
- Full-Range Parameter Coverage: Voltage 3.6kV~40.5kV, current 630A~4000A, short-circuit current 20kA~40kA, covering all medium-voltage power distribution scenarios; three grades (Basic/Standard/Premium) matching different budgets and functional demands
9. Product Bid Winning Parameters (Marked with *)

Workshop Stock of High Voltage Switchgear
9.1 Cabinet Bid Winning Parameters
-
- Rated voltage: 3.6kV ~ 40.5kV (selected on demand)
-
- Rated current: 630A ~ 4000A (selected on demand)
-
- Rated short-time withstand current: ≥20kA (4s)
-
- Protection class: ≥IP4X (Basic), ≥IP5X (Standard), ≥IP55 (Premium)
-
- Insulation level: 12kV ≥42kV/1min (power frequency), ≥75kV (lightning impulse); 40.5kV ≥95kV/1min (power frequency), ≥185kV (lightning impulse)
-
- Cabinet material thickness: Cold-rolled steel ≥2mm, Aluminized zinc steel ≥2mm, Stainless steel ≥1.5mm
9.2 Vacuum Circuit Breaker Bid Winning Parameters
-
- Rated short-circuit breaking current: ≥20kA
-
- Mechanical life: ≥10,000 times (Basic), ≥15,000 times (Standard), ≥20,000 times (Premium)
-
- Opening & closing time: Opening ≤0.06s, Closing ≤0.1s
9.3 Microcomputer Protection Device Bid Winning Parameters
-
- Measurement accuracy: ≥±0.5% (Basic), ≥±0.2% (Standard), ≥±0.1% (Premium)
-
- Communication interfaces: Standard RS485, Standard/Premium equipped with Ethernet, Premium supports IEC61850
-
- Protection functions: At least overcurrent, instantaneous trip and zero-sequence protection; Standard/Premium must include differential and breaker failure protection
9.4 Intelligent Monitoring Module Bid Winning Parameters

On-Site Arrangement of Switchgear Row
-
- Wireless temperature measurement accuracy: ≥±0.5℃ (Basic), ≥±0.3℃ (Premium)
-
- Partial discharge sensitivity: ≤10pC (Standard), ≤5pC (Premium)
-
- Arc flash protection response time: ≤1ms (Standard), ≤0.5ms (Premium)
10. Full Product Solutions
10.1 Power Distribution Solution for Industrial Enterprises
Pain Points
Large load fluctuation, high short-circuit risk, dense equipment, difficult maintenance, strict power supply reliability requirements
Solution Configuration
12kV/24kV KYN28A series switchgear equipped with differential protection, arc flash protection, wireless temperature measurement and partial discharge monitoring; single busbar sectionalized or double busbar connection with bus coupler automatic transfer; intelligent monitoring platform for remote operation, maintenance and fault early warning
Solution Advantages
High-reliability power supply with complete protection configuration; intelligent monitoring eliminates hidden dangers in advance to reduce shutdown risks; modular design facilitates maintenance and adapts to harsh industrial environments
10.2 Booster Station Solution for New Energy Power Stations
Pain Points
Large voltage fluctuation, high harmonic content, harsh environments (high temperature/humidity/sandstorm), unattended operation, strict grid connection requirements
Solution Configuration
35kV KYN61 series eco-friendly gas insulated switchgear with IEC61850 communication, harmonic protection, frequency protection and grid-connected interface; single busbar or single busbar sectionalized connection, PT cabinet for voltage monitoring and grid connection; intelligent monitoring platform + edge computing for remote monitoring and grid data upload
Solution Advantages
Eco-friendly gas insulation adapts to harsh environments; intelligent protection & monitoring meets grid connection standards; unattended design cuts operation & maintenance costs; high insulation level resists overvoltage impact
10.3 High Voltage Power Distribution Solution for Data Centers
Pain Points
Extremely high power supply reliability requirement (99.999%), high load density, strict power quality demand, fast emergency switching
Solution Configuration
12kV KYN28A series premium intelligent switchgear with dual power redundancy, differential protection, arc flash protection and power quality monitoring; double busbar or ring connection with fast bus coupler transfer; intelligent monitoring platform + video linkage for real-time monitoring and fault location; automatic backup power transfer with switching time ≤0.5s
Solution Advantages
Dual power redundancy realizes zero power failure; fast fault isolation & switching reduces outage risks; power quality monitoring stabilizes precision equipment operation; intelligent operation & maintenance minimizes manual intervention
10.4 Power Distribution Solution for Rail Transit
Pain Points
Severe vibration, strong electromagnetic interference, humid environments, large load fluctuation, strict safety standards
Solution Configuration
12kV/35kV reinforced KYN series switchgear with anti-vibration design, electromagnetic shielding and moisture-proof heating & dehumidification; single busbar sectionalized connection with separated power supply for traction and power loads; intelligent protection & monitoring adapted to vibration environments; “Five Prevention” interlock to guarantee operation safety
Solution Advantages
Reinforced structure resists vibration and electromagnetic interference; moisture-proof design adapts to underground humid environments; safety interlock prevents misoperation; high reliability ensures uninterrupted rail transit power supply
11. Product Application Cases
11.1 10MW Photovoltaic Power Station 35kV Booster Station Project
Project Overview
Located in Northwest China with high temperature and heavy sandstorm; 10MW photovoltaic power station requiring 35kV booster station for grid connection, unattended operation
Equipped Products
KYN61-40.5 eco-friendly gas insulated switchgear (1 incoming cabinet, 2 outgoing cabinets, 1 PT cabinet), ZN85-40.5 vacuum circuit breaker, KZ-300 microcomputer protection, wireless temperature measurement, partial discharge monitoring, intelligent monitoring platform
Project Outcomes
Stable equipment operation adapting to high temperature and sandstorm environments; intelligent monitoring detected 2 insulation hidden dangers in advance to avoid failures; unattended operation reduced O&M costs by 60%; smooth grid connection with annual power generation of 15 million kWh
11.2 12kV Power Distribution Workshop Project for Automobile Manufacturer
Project Overview
Large automobile manufacturer in East China, power distribution workshop power supply with total load 12,000kVA, multiple motors and production lines, high power supply reliability requirements
Equipped Products
KYN28A-12 intelligent switchgear (2 incoming cabinets, 8 outgoing cabinets, 1 bus coupler cabinet, 1 PT cabinet), VS1-12 vacuum circuit breaker, KZ-200 microcomputer protection, arc flash protection, wireless temperature measurement, intelligent monitoring platform
Project Outcomes
Dual power supply + bus coupler automatic transfer achieves power supply reliability of 99.99%; arc flash protection quickly isolates faults to avoid equipment damage; intelligent monitoring early warning improves maintenance efficiency by 50%; guarantees uninterrupted production line operation, reducing annual shutdown losses by over ten million RMB
11.3 12kV High Voltage Power Distribution Project for Large Data Center
Project Overview
Large IDC data center in South China with total load 20,000kVA, dual-circuit high voltage power distribution and strict power quality requirements
Equipped Products
KYN28A-12 premium intelligent switchgear (4 incoming cabinets, 12 outgoing cabinets, 2 bus coupler cabinets, 2 PT cabinets), VS1-12 vacuum circuit breaker, KZ-300 microcomputer protection, power quality monitoring, wireless temperature measurement, partial discharge monitoring, intelligent monitoring platform
Project Outcomes
Dual-circuit redundant power supply realizes zero power outage; power quality monitoring & conditioning stabilizes server operation; intelligent operation & maintenance shortens fault location time by 80%; fully meets high-reliability requirements of data centers and gains high customer recognition
12. Common Product Faults & Maintenance Procedures
12.1 Common Faults & Troubleshooting
Circuit Breaker Faults
- Phenomenon: Fails to close/open, trips immediately after closing, mechanical jamming
- Root Causes: Faulty operating mechanism, insufficient energy storage, unlocked interlock, protection activation, mechanical wear
- Solutions: Inspect operating mechanism and energy storage circuit, release interlock, reset protection device, lubricate mechanical parts; replace circuit breaker if severely damaged
Overheating Faults
- Phenomenon: Excessively high temperature of contacts/busbars, infrared temperature measurement alarm, accelerated insulation aging
- Root Causes: Poor contact, overload, poor heat dissipation, excessive ambient temperature
- Solutions: Power off to inspect contact connections, fasten bolts and remove oxide layers; reduce load and improve ventilation; enhance heat dissipation or derate operation under high temperature
Insulation Faults
- Phenomenon: Partial discharge, insulation breakdown, earth fault, flashover discharge
- Root Causes: Insulation aging, dampness, pollution, gas leakage (eco-friendly type), overvoltage impact
- Solutions: Power off to clean and dry insulation components; replace aged insulation parts; inspect and replenish leaked gas; install lightning arresters to suppress overvoltage
Secondary Circuit Faults
- Phenomenon: Protection misoperation/rejection, abnormal measurement & control, communication interruption, indicator light failure
- Root Causes: Loose wiring, oxidized terminals, power supply fault, damaged protection device, faulty communication module
- Solutions: Inspect and fasten wiring & terminals, clean oxidation; check secondary power supply; reset or replace protection/communication devices; eliminate interference on communication lines
12.2 Daily Maintenance Regulations
Daily Inspection (Remote + On-Site)
- Remote: Monitor voltage, current, temperature, partial discharge and switch status via monitoring platform for abnormal alarms
- On-Site: Inspect cabinet appearance, indicator lights, meters, abnormal noise/odor/condensation and reliable earthing
Weekly Maintenance
- Clean cabinet surface and ventilation openings to remove dust and debris
- Check normal operation of heating & dehumidifiers and temperature & humidity controllers
- Fasten secondary circuit terminals to prevent loosening
Monthly Maintenance
- Infrared temperature measurement: Detect temperature of circuit breaker contacts, busbars and cable terminals, record and analyze data
- Mechanical inspection: Check operating mechanisms of circuit breakers, disconnectors and earthing switches, lubricate moving parts and verify reliable interlock
- Protection device: Calibrate protection setting values, check action records and test communication status
Annual Overhaul (Power Cut Required)
- Circuit breaker: Disassemble and inspect contacts, arc extinguishing chambers and operating mechanisms; clean, polish and lubricate; test mechanical characteristics (opening/closing time, stroke)
- Insulation components: Full cleaning and drying; inspect aging, cracks and damage, replace if necessary
- Transformer: Test insulation resistance, transformation ratio and polarity, calibrate accuracy
- Earthing system: Test earthing resistance to ensure ≤0.5Ω, verify reliable earthing connections
- Intelligent monitoring: Calibrate temperature/partial discharge/arc flash sensors, test alarm and linkage functions
13. Factory Strength & After-Sales Service
13.1 Factory Strength
- Production Scale: Modern production base covering 50,000㎡ land area and 30,000㎡ building area; multiple flexible production lines with annual output of 10,000 sets high voltage switchgear and 20,000 sets vacuum circuit breakers
- R&D Team: Over 100 professional R&D personnel including 30 senior engineers and 5 doctors; focus on R&D of high voltage switches, intelligent protection and condition monitoring with over 50 patents
- Production Equipment: Imported German CNC punching machines, laser cutting machines, bending machines, spraying production lines, vacuum epoxy casting equipment and automatic assembly lines; 80% automation rate guarantees product precision and consistent quality
- Testing Center: National-level testing laboratory equipped with insulation voltage withstand test bench, short-circuit test device, temperature rise test equipment, partial discharge detector and mechanical characteristic tester; 100% factory type test for all products to ensure qualification
- Qualification Certifications: ISO9001 quality management system, ISO14001 environmental management system, OHSAS18001 occupational health & safety system certification; products pass national 3C certification, type test certification and CQC certification, complying with national standards GB/T 3906, DL/T 404 etc.
13.2 After-Sales Service System
Service Commitment
- Warranty Period: 3-year full product warranty, 5-year warranty for core components (circuit breakers, protection devices); free maintenance and component replacement within warranty, free technical support
- Response Time: 24-hour national service hotline, response within 1 hour; solution provided within 2 hours; on-site arrival within 4 hours for provincial capitals, 8 hours for prefecture-level cities, 24 hours for remote areas
- Lifelong Service: Lifelong maintenance service after warranty, discounted supply of original spare parts, regular return visits, technical upgrade and renovation service
Service Network
6 regional service centers, 30 provincial service outlets and over 100 authorized service stations nationwide; over 200 professional after-sales engineers with strict training and assessment and rich on-site experience
Service Contents
- Installation & Commissioning: Free on-site installation guidance, commissioning and technical training to ensure normal equipment commissioning
- Technical Training: Operation, maintenance and fault handling training for customers via online + offline courses to ensure skilled operation of customer staff
- Spare Parts Support: National spare parts warehouse with sufficient stock of common spare parts for fast delivery; original direct supply of core components to guarantee compatibility and quality
- Upgrade & Renovation: Provide product technical upgrade, intelligent transformation and old equipment replacement services to meet subsequent customer demands
14. Conclusion
With core advantages of high safety, high reliability, intelligence, eco-friendliness, energy saving and flexible customization, KITOZER high voltage switchgear system fully covers all medium-voltage power distribution scenarios of 3.6kV~40.5kV, providing stable and reliable power distribution guarantee for industry, construction, new energy, transportation and other fields. The company possesses strong R&D, production, testing and after-sales service capacity, strictly controls product quality and continuously iterates technology to help customers achieve safe, efficient, intelligent and low-carbon power operation & maintenance targets. In the future, KITOZER will further deepen the medium-voltage power distribution sector, continuously optimize product performance, upgrade service quality and contribute to the development of global power industry.
15. Search Keywords, SEO & Tags
15.1 Search Keywords
High voltage switchgear, 12kV high voltage switchgear, 35kV high voltage switchgear, KYN28A-12, KYN61-40.5, vacuum circuit breaker, microcomputer protection device, intelligent high voltage switchgear, eco-friendly gas insulated switchgear, new energy booster station switchgear, industrial power distribution switchgear, data center high voltage distribution cabinet, KITOZER high voltage switchgear, high voltage switchgear solution, high voltage switchgear configuration list
15.2 SEO Titles
- Core Title: KITOZER High Voltage Switchgear System Solution | 12kV/35kV Intelligent Eco-Friendly Power Distribution Equipment
- Long-Tail Title: High Voltage Switchgear Dedicated for Industry / New Energy / Data Center | Customized Medium-Voltage Power Distribution Solution
15.3 Tags
#HighVoltageSwitchgear #12kVSwitchgear #35kVSwitchgear #KYN28A #KYN61 #VacuumCircuitBreaker #MicrocomputerProtection #IntelligentPowerDistribution #EcoFriendlyGasInsulated #NewEnergyBoosterStation #IndustrialPowerDistribution #DataCenterPowerDistribution #KITOZER #PowerDistributionSolution