1. Overview
KITOZER KTR-OS39 is a horizontal double-in double-out high-efficiency oil separator used in data center precision air conditioners, chillers and air-cooled heat pumps to separate lubricating oil from compressor discharge gas. Hot high-pressure refrigerant leaving the compressor carries atomized oil; if not separated, it forms an oil film on condenser tubes, lowering heat exchange and causing compressor oil starvation. KTR-OS39 sits between compressor discharge and condenser, separating oil droplets by centrifugal impingement plus mesh filtration, then returning oil via a return line to the crankcase.
KTR-OS39 uses a horizontal vessel with symmetric twin inlets and twin outlets. Gas enters symmetrically, spins inside the shell, and oil droplets are flung to the wall and collected in a bottom sump. Compared with single-in single-out vertical separators, the horizontal double-port design has a shorter flow path, lower pressure drop and larger gas capacity, suited to parallel compressor racks. A bottom float valve returns oil automatically when the sump reaches a set level. An internal stainless steel mesh layer catches fine oil mist for over 99% separation efficiency.
In data center cooling, the oil separator is often overlooked: falling heat exchange, rising oil consumption and high discharge temperature frequently trace back to a failed or undersized separator. KTR-OS39 is supplied in volume for precision AC units, magnetic-bearing chillers and screw chillers, keeping refrigeration systems running stably.
2. Key Features
Horizontal double-port design
- Symmetric twin inlets for swirl separation.
- Twin outlets, low pressure drop, high flow.
- Suited to parallel compressor racks.
Dual separation mechanism
- Centrifugal impingement + stainless mesh.
- Efficiency ≥99%.
- Reduces discharge oil carry-over.
Automatic oil return
- Bottom sump + float valve.
- Returns oil to crankcase on level.
- Less manual intervention.
Temperature & pressure rated
- Shell pressure 4.5 MPa.
- For R22/R410A/R134A refrigerants.
- Horizontal mount saves vertical height.
3. Specifications
| Item | KTR-OS39-1 | KTR-OS39-2 | KTR-OS39-3 |
|---|---|---|---|
| Port size (in/out) | 2×22mm/2×22mm | 2×28mm/2×28mm | 2×35mm/2×35mm |
| Gas flow (m³/h) | 80~120 | 150~220 | 260~380 |
| Efficiency (%) | ≥99 | ≥99 | ≥99 |
| Design pressure (MPa) | 4.5 | 4.5 | 4.5 |
| Oil return | Float auto | Float auto | Float auto |
| Refrigerant | R22/R410A/R134A | R22/R410A/R134A | R22/R410A/R134A |
| Mounting | Horizontal | Horizontal | Horizontal |
| Shell material | Steel copper-plated | Steel copper-plated | Steel copper-plated |
4. Reference Prices
KTR-OS39-1 separator (22mm double-port, float valve): Reference USD 94~136 / unit (ref. CNY 680~980 at ~7.2)
KTR-OS39-2 separator (28mm double-port, float valve): Reference USD 146~219 / unit (ref. CNY 1,050~1,580 at ~7.2)
KTR-OS39-3 separator (35mm double-port, float valve): Reference USD 233~344 / unit (ref. CNY 1,680~2,480 at ~7.2)
Reference only; by port size, gas flow and refrigerant. Installation and welding materials excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Precision AC discharge lines.
- Screw / magnetic-bearing chillers.
- Air-cooled heat pump VRF systems.
- Cold storage and process refrigeration.
- Parallel compressor oil-gas separation.
6. Installation & Maintenance
Installation
- Place between compressor discharge and condenser.
- Mount horizontally with arrow in gas direction.
- Connect twin inlets to compressor discharge (parallel racks).
- Connect twin outlets to condenser line.
- Run bottom return line to crankcase oil return port.
- Nitrogen-purge while welding to avoid oxide scale.
- Evacuate, pressure-test, charge and trial-run.
Maintenance
- Check float valve return flow regularly.
- Monitor abnormal oil consumption.
- Inspect welds and joints for oil leaks.
- Clean return capillary at seasonal service.
- Drain sump oil after long shutdowns.
- Track discharge temp and condensing pressure.
7. FAQ
- Q: Horizontal vs vertical?
A: Choose vertical for single compressors with space; choose horizontal double-port for parallel racks, large flow and low headroom. - Q: What does 99% efficiency mean?
A: Discharge oil carry-over drops from several percent to below one per mille, cutting oil-film heat loss. - Q: Float valve keeps spraying oil?
A: Clean a stuck float or blocked capillary; replace the shell if the mesh is damaged. - Q: Can I reverse the mount?
A: No — the shell has a flow arrow; reversal destroys the swirl and efficiency collapses.
8. Trend & Selection
Oil separation moves from vertical single-port to horizontal double-port high-efficiency mesh designs, especially for magnetic-bearing variable-frequency compressors that demand low pressure drop and high efficiency. Select by compressor displacement (derated for parallel racks), confirm refrigerant and design pressure, choose double-port for parallel units, plan return-line space, and nitrogen-purge welds.
9. Delivery & Service
KITOZER selects oil separators by compressor model, displacement, refrigerant and piping layout, confirming port size and shell dimensions. We provide interface drawings. Delivery includes separator, float valve, return fitting and manual. Warranty covers install guidance and commissioning.
10. Additional Notes
The common pitfall is matching only the pipe diameter without checking gas flow. The diameter fits but capacity is undersized; at high load the gas velocity is too fast for droplets to separate, and oil carry-over returns. Size by rated displacement with a 1.2~1.5× margin for parallel units.
Another pitfall is a reversed or un-bent return line. The return line must run from the lowest bottom point with a U-trap to prevent refrigerant gas flooding the crankcase. The return bore should not be smaller than the crankcase port.
Selection summary: size by displacement with margin; choose double-port for parallel racks; bottom auto return; nitrogen-purge welds; track oil use and discharge temp. The oil separator is the cooling system’s lung — it keeps the oil in, so the compressor never runs dry.