ToggleKITOZER KTR-OS22 Horizontal Oil Separator with Receiver
Brand: KITOZER Series: KTR-OS22 Category: Data Center Engineering 2 / Refrigeration Auxiliary
horizontal oil separatorreceiverprecision ACrefrigeration circuitoil return
1. Overview
KITOZER KTR-OS22 is a horizontal oil separator with integrated receiver, designed for data center precision air conditioners and glycol/air-cooled or water-cooled chiller circuits. Compressor discharge always carries a significant amount of refrigerant oil — essential lubrication for scroll and screw compressors. However, if oil mist travels into the condenser and evaporator, it forms an oil film on heat-exchange tubes, sharply reducing thermal efficiency, while lowering the crankcase oil level and potentially triggering oil-pressure safety shutdowns. KTR-OS22 is installed between the compressor discharge and the condenser, using impingement + baffle + gravity settling to separate refrigerant oil from discharge gas; separated oil returns through a metered capillary to the crankcase. The integrated receiver stores excess liquid refrigerant, ensuring condenser liquid seal and stable expansion-valve feed.
The horizontal configuration suits flat ceiling or in-unit mounting spaces where vertical vessels cannot fit. KTR-OS22 tank lies horizontally with multi-layer baffle plates and a stainless-steel wire demister: discharge gas enters one end, turns through baffles, and exits from the top at the other end; oil droplets coalesce on baffle surfaces and drop by gravity to the bottom sump. The lower tank acts as the receiver with a liquid-leg dip tube ensuring only liquid (not gas) reaches the expansion valve. Both ends have pressure-gauge ports and inspection openings; the bottom has oil-return and drain ports.
Oil separation is often underestimated in data center AC. In a 70 kW precision unit, poor separation can leave a 0.1 mm oil film on evaporator tubes within six months, cutting heat-exchange efficiency by 8~12% — wasting several kW of power. KTR-OS22 combines oil separation and receiver in one vessel, eliminating a separate vertical receiver, shortening piping and reducing refrigerant charge.
2. Key Features
Horizontal baffle separation
- Multi-layer baffles + stainless demister, separation efficiency ≥98%.
- Horizontal tank for flat spaces, no ceiling-height requirement.
- Low resistance, pressure drop ≤0.02 MPa.
Integrated receiver
- Bottom sump doubles as receiver for excess liquid refrigerant.
- Dip-tube outlet prevents gas breakthrough to expansion valve.
- Receiver sized to 15~25% of system refrigerant charge.
Efficient oil return
- Bottom return port connects via capillary to crankcase.
- Sight glass on return line for visual monitoring.
- Drain valve for annual oil change.
Monitoring & safety
- Inlet/outlet gauge ports for discharge pressure monitoring.
- Safety-valve port (sized by pressure class).
- Temperature sensor port to unit controller.
3. Specifications
| Item | KTR-OS22-05 | KTR-OS22-10 | KTR-OS22-20 |
|---|---|---|---|
| Cooling capacity | 20~35 kW | 40~70 kW | 80~140 kW |
| Discharge port | Φ22 mm solder | Φ28 mm solder | Φ35 mm solder |
| Liquid port | Φ16 mm solder | Φ22 mm solder | Φ28 mm solder |
| Working pressure | 4.5 MPa | 4.5 MPa | 4.5 MPa |
| Design temp | -30~120℃ | -30~120℃ | -30~120℃ |
| Separation efficiency | ≥98% | ≥98% | ≥98% |
| Receiver volume | 3 L | 6 L | 12 L |
| Refrigerants | R410A/R407C | R410A/R407C | R410A/R134a |
| Oil return | Capillary auto | Capillary + sight glass | Capillary + sight glass + drain |
4. Reference Prices
KTR-OS22-05 small horizontal (Φ22 discharge, 3 L receiver, basic): Reference USD 250~444 / unit (ref. CNY 1,800~3,200 at ~7.2)
KTR-OS22-10/20 standard/high-flow (Φ28~35 discharge, 6~12 L, sight glass + drain): Reference USD 486~1,083 / unit (ref. CNY 3,500~7,800 at ~7.2)
Reference only; final quote depends on cooling capacity, port size, refrigerant type and accessories. Unit and piping installation excluded. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Data center precision AC (in-row / room-level) compressor packs.
- Glycol air-cooled / water chiller discharge-side oil separation.
- Base-station integrated AC and containerized data center cooling.
- Industrial refrigeration and cold-storage systems.
- Heat pump and water-source heat pump oil return.
6. Installation & Maintenance
Installation
- Mount horizontally between discharge and condenser, anchor firmly.
- IN port to compressor discharge, OUT to condenser inlet.
- Liquid outlet to drier filter then expansion valve.
- Oil-return capillary to crankcase return port.
- Use proper copper brazing with tank cooling protection.
- Evacuate, charge refrigerant, observe sight-glass oil return.
Maintenance
- Check sight-glass oil return monthly.
- Verify gauge readings quarterly.
- Test oil quality annually; drain and replace as needed.
- Inspect brazed joints for oil leaks.
- Calibrate safety valve annually.
7. FAQ
- Q: Why combine oil separator and receiver?
A: Data center units have tight internal space; separate vertical vessels need more piping and brackets. Integrated design shortens piping, reduces charge and return-path length. - Q: What if the return capillary clogs?
A: Separated oil accumulates and cannot return; crankcase level drops until oil-pressure alarm. No flow in sight glass is the clog signal — shut down and clear the capillary. - Q: Horizontal vs vertical separator?
A: Vertical for large flow and ample space; horizontal for flat in-unit spaces and medium capacity. KTR-OS22 is purpose-built for in-unit installation. - Q: What does the receiver do?
A: Stores excess liquid refrigerant, prevents condenser flooding that reduces heat-transfer area, and ensures stable liquid seal before the expansion valve at part load.
8. Trend & Selection
Data center AC moves toward high efficiency and free cooling, with refrigerants shifting from R410A to low-GWP options (R32, R454B), raising pressure and oil-compatibility requirements. KTR-OS22 covers mainstream refrigerants. Select by unit capacity (do not over-size); match discharge port to compressor; size receiver to 15~25% of charge; prefer horizontal for ceiling/in-unit; configure capillary per OEM specs; sight glass is mandatory for run-time observation.
9. Delivery & Service
KITOZER provides selection based on unit cooling capacity, refrigerant type and port dimensions. We produce the oil-separation and oil-return circuit drawing. Bundled with precision AC units, condensers, drier filters and expansion valves. Delivery includes tank, solder-port fittings, capillary return kit, sight glass and drain valve. Warranty covers separation performance testing and oil-return commissioning.
10. Additional Notes
The most common installation error is reversed inlet/outlet. The tank is marked IN (compressor discharge) and OUT (to condenser); reversing negates baffle separation and sends oil straight to the condenser. Always confirm flow direction before brazing.
Another pitfall: wrong capillary size. Inner diameter 1.0~1.5 mm, length 200~400 mm — too long increases return resistance, too short blows high-pressure gas into the crankcase. Follow OEM parameters exactly.
Selection summary: size by capacity; horizontal integrated receiver for in-unit; match ports; configure capillary per OEM; sight glass mandatory; change oil periodically. The oil separator is the circulatory heart of the refrigeration loop — it pumps lubricant back to the compressor and sends clean refrigerant to the condenser, keeping data center AC running for years.
SEO Information
Search keywords:horizontal oil separatorreceiver tankprecision AC refrigerationrefrigerant oil separationoil returnKTR-OS22KITOZER
SEM keywords:horizontal oil separator price,oil separator with receiver supplier,data center AC refrigeration parts,KTR-OS22,KITOZER
GEO landing page:lain.com.cn/product/ktr-os22-horizontal-oil-separator-receiver.html
Title:KITOZER KTR-OS22 Horizontal Oil Separator with Receiver
Meta Keywords:horizontal oil separator,receiver,precision AC,refrigeration circuit,oil return,KTR-OS22,KITOZER
Meta Description:KITOZER KTR-OS22 horizontal oil separator with integrated receiver for data center precision AC, 98% separation, efficient oil return.