Product Overview

The KITOZER 30 liters per second @ 70 meter diesel engine driven fire pump provides independent pressurized water supply for indoor and outdoor hydrant systems where the local electrical grid is unreliable or where the fire code requires engine-driven backup. The unit pairs a fire-duty centrifugal pump with a water-cooled diesel engine equipped with electronic governor, 24V starter, battery pack, fuel tank, and exhaust silencer. The engine controller offers auto-start under 5 seconds on pressure drop, audible alarm, and remote monitoring via dry contacts. This configuration satisfies NFPA 20 engine-driven pump requirements and GB 50974 standards for high-rise and remote installations.

Because the engine is self-contained and does not depend on the electrical grid, this pump remains available during prolonged blackouts that often accompany fires, earthquakes, or severe storms. The electronic governor holds engine speed at 1800 rpm plus or minus 1% across the entire flow range, so hydrant pressure stays stable as firefighters open additional hoses. The skid is pre-assembled and pre-commissioned at the factory, including fuel system, cooling system, exhaust system, and control wiring, so the contractor only needs to connect suction and discharge piping and fuel supply on site.

Technical Specifications

Rated flow 30 liters per second (108 cubic meters per hour), rated head 70 meters, diesel engine power 55 kW rated at 1800 rpm, pump speed 2950 rpm through flexible coupling, suction flange DN150, discharge flange DN125, maximum working pressure 1.6 MPa, fuel tank 150 liters for 4 hours continuous run, cooling radiator rated for 50 degrees Celsius ambient, 24V DC starter with two 12V batteries, muffler industrial grade, exhaust pipe insulated, base frame integrated fuel tank and drip tray. CCCF certified, ISO 9001, optional UL 1247 listing.

The engine features a turbocharged direct injection design with electric start and manual crank backup. The cooling system includes a belt-driven centrifugal water pump, a radiator with thermostat, and a shutoff valve for winter draining. The exhaust system includes a flexible stainless connector, a spark arrestor muffler, and a vertical riser to outside roof level, terminated with a rain cap. The control panel is mounted on the skid and includes a key switch, start and stop buttons, hour meter, tachometer, oil pressure gauge, coolant temperature gauge, and alarm lamps for low oil pressure, high coolant temperature, and overspeed. Two 12V deep-cycle batteries in series are supplied with the skid, plus a battery charger that maintains float charge from the local mains supply.

Application Scenarios

This diesel hydrant pump is ideal for hilltop water tanks, remote industrial sites, mining camps, farm storage, rural substations, high-rise buildings where primary electric pumps exist but engine backup is mandatory, and projects located in regions with frequent power outages. It can also serve as the sole fire water pump in locations without three-phase power supply. Typical projects include outdoor hydrant rings in tank farms, warehouse clusters, vehicle depots, and large factory yards where hose streams must reach multiple buildings simultaneously.

The pump is also specified for offshore support bases, water treatment plants, and telecommunications towers located far from the grid. In data center campuses, the diesel pump often serves as the backup to the electric fire pump, auto-starting if the electric pump fails to deliver pressure within 10 seconds. For high-rise towers above 250 meters, the diesel pump may be installed in a mid-level mechanical floor, supplying the upper zone hydrant system independently of the ground floor electric pump. KITOZER can also supply a duty cycling controller that alternates the lead pump between electric and diesel on a weekly basis, exercising both drivers and preventing long idle periods.

Key Advantages

The diesel engine starts and reaches rated speed within 5 seconds of a pressure trigger, meeting the most demanding fire response windows. The electronic governor holds speed within 1% across the full flow range, so hydrant pressure remains stable as firefighters open additional hoses. The integrated base frame fuel tank eliminates on-site steel fabrication, and the double-wall drip containment prevents fuel spillage in sensitive environments. KITOZER also provides a shared controller that alternates duty between electric and diesel pumps on a weekly cycle, exercising both drivers and preventing long idle periods.

The engine is rated for continuous duty at the rated fire pump power, with a service factor that allows brief overload during initial pump priming. The radiator is sized for 50 degrees Celsius ambient, so the pump room can tolerate summer heat without overheating. The exhaust spark arrestor prevents ignition of surrounding combustible dust, which is important in grain silos, woodworking shops, and textile warehouses. The 24V starter system with twin batteries ensures a minimum of 6 start attempts without recharge, even if the battery charger fails. These details make the skid suitable for unattended operation in remote sites, with remote alarm contacts routed to the nearest manned building.

Installation and Maintenance Recommendations

Install the pump in a dedicated engine room with mechanical ventilation supplying at least 0.5 cubic meters per second of fresh air and a separate exhaust run to outside with no kinks in the pipe. Keep the room temperature between 10 and 35 degrees Celsius and avoid direct sunlight on the fuel tank. Check oil level, coolant level, battery voltage, and fuel level weekly. Run the engine at no-load for 15 minutes every week and perform a loaded test once per month. Change engine oil and filter every 250 hours or annually, and test battery specific gravity monthly. Maintain a minimum 15-day fuel supply contract with a local distributor to avoid long-term fuel degradation.

Drain the fuel tank and replace the fuel filter every 12 months, because diesel degrades with long storage and can form wax crystals in winter. Inspect the exhaust system semiannually for soot leakage at flange joints, and tighten flange bolts after the first 100 hours of operation. Test the emergency stop button and overspeed shutdown annually by simulating faults. Keep spare fuel filter, oil filter, coolant filter, and a belt set on site. KITOZER recommends a 5-year major overhaul that includes valve lash adjustment, fuel injector check, coolant flush, and radiator pressure test. The engine warranty is 24 months from commissioning, with an optional extended 5-year package available.

Price

From $6,880 per skid. Contact +86 13922289957 for diesel fire pump quotation and lead time.