KITOZER Immersion Liquid Cooling Cabinet Integrated Solution

Table of Contents

1. System Overview

The KITOZER immersion liquid cooling cabinet system is an integrated liquid cooling heat dissipation solution developed for new-generation high-density computing power scenarios. It completely breaks through the bottlenecks of traditional air cooling heat dissipation technology. Servers, GPUs, storage and other IT equipment are fully immersed in high-insulation, high-thermal-conductivity and chemically stable special cooling liquid. Heat-generating components conduct efficient heat exchange directly with the cooling liquid, which instantly and efficiently removes heat from equipment cavities. A complete closed-loop heat dissipation system is formed together with the Cooling Distribution Unit (CDU) and outdoor cold source system.

This system is perfectly compatible with ultra-high heat density scenarios including AI large model training, High-Performance Computing (HPC), cloud computing data centers and edge computing nodes. The single cabinet heat dissipation capacity covers the full range of 20kW~1200kW, and the system PUE can be stably controlled between 1.03 and 1.08. It saves more than 40% energy compared with traditional air-cooled data centers, while the equipment operating noise is ≤35dB. It thoroughly addresses industry pain points of traditional air cooling such as high energy consumption, loud noise, high-density computing power bottlenecks and high failure rates.

The KITOZER immersion liquid cooling system strictly complies with national and industrial standards including GB/T Technical Specification for Liquid Cooling Components of Servers and Storage Devices, T/CI 963—2025 Design Specification for Single-Phase Immersion Liquid Cooling Cabinets in Data Centers, T/CECS 1722-2024 Technical Specification for Liquid Cooling Systems in Data Centers, and YD/T 4274-2023 Design Requirements for Single-Phase Immersion Liquid Cooling Data Centers. It boasts core capabilities of full-stack domestic production, modular deployment, customized development and full-lifecycle operation & maintenance support, delivering one-stop integrated liquid cooling solutions covering scheme design, product R&D, manufacturing, installation & commissioning and after-sales operation & maintenance.

2. System Composition

The KITOZER integrated immersion liquid cooling system adopts a dual closed-loop architecture, consisting of two core circulation links: the primary cold source system and the secondary medium circulation system, as well as an intelligent monitoring & operation management system and supporting auxiliary systems. All subsystems collaborate seamlessly to realize efficient, stable and safe heat dissipation control across the whole link.

2.1 Core Immersion Liquid Cooling Cabinet Unit

As the core carrier of the system, the KITOZER immersion liquid cooling cabinet comprises six core modules: frame assembly, inner tank cavity assembly, sealing system, power supply system, fluid inlet & outlet interface, and equipment fixing & guiding system.

  • Frame Assembly: Welded from high-strength cold-rolled steel, 304/316L stainless steel or aluminum alloy with reinforcing ribs to guarantee no deformation under full load of cooling liquid and IT equipment. It includes cabinet frame, openable top cover with safety lock, transparent observation window, casters, load-bearing foot pads, front/rear/side protective doors. The top cover can open ≥90° and stay fixed to support single-person operation & maintenance.
  • Inner Tank Cavity Assembly: The core liquid storage and heat exchange cavity of the liquid cooling system, double-welded with 304/316L stainless steel. All welds pass 100% air tightness and hydraulic pressure tests with zero leakage risk. Internal integrated fluid diversion and uniform flow distribution structures, server fixing brackets, guiding and limiting structures ensure uniform flow field of cooling liquid without heat exchange dead zones, with vertical temperature difference within the cavity ≤5℃.
  • Sealing System: Multi-layer sealing structure made of food-grade fluorine rubber/EPDM rubber to match compatibility requirements of different cooling liquids, reaching IP67 protection grade. Combined with cavity positive/negative pressure monitoring, zero leakage management is realized. The quick-opening compression structure at the top cover balances sealing performance and operation convenience.
  • Cabinet Power Supply System: Built-in T2 nickel-plated copper busbar with A/B dual redundant power supply, supporting 48V DC / 220V AC / 380V HVDC input. Equipped with special power clamps, power frames and overcurrent/short-circuit/leakage protection devices to achieve safe power supply with no exposed live parts for IT equipment, with power supply efficiency ≥99.5%.
  • Fluid Interface System: Liquid inlet, liquid outlet, liquid level balance port, emergency drain port and liquid filling port are standard on cabinet sides, adopting national standard flange/quick-plug connection structure with pressure resistance ≥1.6MPa to adapt pipeline connection demands of various scenarios. Interfaces are equipped with misoperation-proof valves and check valves to avoid medium leakage caused by operation errors.
  • Equipment Fixing & Operation Auxiliary System: Standardized guide rails and positioning holes for IT equipment inside the cavity, compatible with standard rack servers and GPU servers of 1U/2U/4U specifications, supporting live underwater hot swapping. Special operation tools including liquid draining/refilling devices, operation trolleys and hoisting auxiliary structures greatly reduce on-site maintenance difficulty.

2.2 Cooling Distribution Unit (CDU)

The CDU serves as the core heat exchange and control unit connecting the primary cold source and secondary immersion cavity, undertaking core functions of heat exchange between primary and secondary sides, provision of cooling liquid circulation power, regulation of flow, temperature and pressure, system safety protection and physical isolation to prevent condensation. The KITOZER CDU series includes cabinet-level, cabinet group-level and machine room-level models to adapt to deployment scenarios of different scales.

  • Core Heat Exchange Module: 316L stainless steel plate heat exchanger / brazed plate heat exchanger with heat exchange efficiency ≥98% and strong corrosion resistance, compatible with various cooling liquids including fluorinated liquid, mineral oil and synthetic hydrocarbon. The primary and secondary sides are completely physically isolated with pressure resistance ≥1.6MPa, eliminating risks of cooling water leakage contaminating IT equipment.
  • Circulation Power Module: Standard one-working-one-standby redundant magnetic levitation centrifugal pump / canned pump with zero leakage, low noise and long service life. Flow adjustment range covers 0~100% and lift ranges from 5m to 50m to match different cabinet quantities and pipeline resistance scenarios. Pumps are equipped with variable frequency control systems to dynamically adjust flow according to IT load for optimal energy efficiency.
  • Monitoring & Regulation Module: Integrated high-precision temperature, pressure, flow, liquid level and conductivity sensors to collect more than 20 operating parameters including supply & return water temperature difference, pressure, flow rate and cooling liquid status of primary and secondary sides in real time. Matched with electric regulating valves, proportional integral valves, pressure relief valves and pressure supplement devices to realize full-automatic closed-loop control of system temperature, pressure and flow.
  • Safety Protection Module: Built-in multi-link interlock protection mechanisms against over-temperature, over-pressure, low pressure, low liquid level, leakage and pump failure. Three-level responses including graded alarm, automatic regulation and emergency shutdown are triggered under abnormal conditions. An emergency bypass system is equipped so single-point faults will not disrupt normal system operation to guarantee IT equipment safety.
  • Intelligent Control Module: Standard PLC controller + 7/10-inch industrial touch screen, supporting standard communication protocols such as Modbus, TCP/IP and BACnet for access to machine room environment monitoring systems. It enables remote monitoring, data storage, fault early warning and historical data traceback, and adopts an AI adaptive temperature control algorithm to predict thermal load in advance according to changes in computing load and dynamically adjust operating parameters.

2.3 Cooling Liquid Medium

Cooling liquid is the core heat transfer medium of the immersion liquid cooling system. KITOZER provides a full range of special cooling liquids for different technical routes and application scenarios. All media meet core requirements of high insulation, high thermal conductivity, chemical stability, environmental non-toxicity and full compatibility with IT equipment materials.

  • Single-phase Immersion Special Cooling Liquid: Divided into synthetic hydrocarbon, mineral oil and eco-friendly fluorinated liquid categories, with boiling point ≥120℃, freezing point ≤-40℃, breakdown voltage ≥35kV and thermal conductivity ≥0.08W/(m·K). Featuring strong chemical stability with no decomposition or deterioration within the full lifecycle and annual loss rate ≤3%, it adapts to most general immersion liquid cooling scenarios.
  • Two-phase Immersion Special Cooling Liquid: Low-boiling eco-friendly fluorinated liquid with boiling point of 45~60℃, latent heat of vaporization ≥100kJ/kg and breakdown voltage ≥40kV. Ozone Depletion Potential (ODP) = 0 and extremely low Global Warming Potential (GWP), suitable for ultra-high heat density phase change immersion scenarios (≥100kW per cabinet).
  • Auxiliary Additives for Cooling Liquid: Matching corrosion inhibitors, antioxidants, defoamers and other special additives to effectively suppress cavity and pipeline corrosion, extend cooling liquid service life and ensure long-term stable system operation.

2.4 Primary Cold Source System

The primary cold source system ultimately discharges heat carried away by secondary cooling liquid into the natural environment. KITOZER delivers a full lineup of cold source solutions based on local climate conditions, project energy consumption requirements and on-site installation conditions. Main types are as follows:

  • Dry Cooler Natural Cooling System: Suitable for northern low-temperature regions, realizing natural cooling for over 80% of the year without turning on chillers, with system PUE as low as 1.03. Equipped with EC variable frequency fans that dynamically adjust air volume based on ambient temperature, featuring low operating noise and convenient installation & maintenance.
  • Closed Cooling Tower Cooling System: Adaptable to medium-to-high temperature and high-humidity regions, adopting evaporative cooling principles with high cooling efficiency. Supply water temperature can be stably controlled 2~3℃ above ambient wet-bulb temperature, suitable for full-year high-load operation scenarios. A matched water treatment device prevents pipeline scaling to guarantee heat exchange efficiency.
  • Chiller Auxiliary Cooling System: For scenarios with year-round high temperature, ultra-high heat density or strict temperature control precision requirements. Combined with natural cooling systems to form composite cooling and ensure stable system operation under extreme working conditions. Screw/centrifugal chillers are available.
  • Waste Heat Recovery System: Matched with plate heat exchangers and waste heat recovery units to recycle waste heat generated by IT equipment for building heating, domestic hot water, agricultural greenhouses and industrial process heating. It realizes cascaded energy utilization to further reduce overall data center energy consumption and support carbon neutrality goals.

2.5 Intelligent Monitoring & Operation Management System

The KITOZER immersion liquid cooling system is standardly equipped with a full-stack intelligent monitoring platform to realize centralized monitoring, intelligent regulation, fault early warning and operation management of the full liquid cooling system, guaranteeing uninterrupted stable operation 7×24 hours.

  • Data Collection & Real-time Monitoring: A distributed sensor network collects more than 200 operating data points in real time, including cavity liquid level, temperature, pressure, cooling liquid status, CDU operating parameters, cold source system status and core IT equipment temperatures. A 3D visual interface presents full-dimensional data for blind-spot-free monitoring.
  • Intelligent Control & Dynamic Regulation: Built-in AI adaptive temperature control algorithm dynamically adjusts cooling liquid flow and cold source output according to changes in IT load and ambient temperature to achieve optimal energy efficiency across all load ranges. It supports collaborative control of multiple cabinet clusters for uniform flow distribution and local overheating prevention.
  • Fault Early Warning & Emergency Protection: A three-level fault early warning mechanism covering warning, alarm and emergency shutdown grades responds to abnormalities such as over-temperature, over-pressure, leakage and low liquid level within milliseconds, triggering corresponding protective actions automatically while pushing alarm information to operation staff, shifting maintenance from passive repair to active early warning.
  • Operation Management & Data Traceability: The system automatically stores historical operating data for no less than 10 years, supporting query, export and analysis of historical data to provide data support for system optimization and troubleshooting. Built-in work order management, equipment asset management and maintenance plan reminder functions realize digital full-lifecycle operation management.
  • Remote Access & Multi-terminal Adaptation: Accessible via Web, mobile terminals and local touch screens, allowing operation staff to view system status, adjust parameters remotely and handle faults anytime, anywhere to greatly improve operation efficiency.

2.6 Supporting Auxiliary Systems

  • Pipeline System: Adopts 304/316L stainless steel pipes or steady-state PPR pipes with special fittings, valves and flexible connections. Pipes follow the equal-flow layout principle to guarantee uniform flow distribution across all cabinets. All pipelines are fully insulated to avoid condensation and cold loss.
  • Leakage Detection & Emergency Treatment System: Distributed cable-type leakage detection sensors are laid at key positions including cabinet bottoms, pipeline interfaces and CDU machine rooms with detection precision ≤1mm and response time ≤1s. Once leakage is detected, alarms are triggered instantly while corresponding pipeline valves are automatically closed and emergency liquid drainage systems activated to avoid leakage expansion.
  • Liquid Filling & Draining System: Standard centralized liquid filling devices, emergency liquid storage tanks and drainage pumps realize full-automatic system liquid filling and rapid draining/recycling of media during maintenance. Matched medium filtration & purification devices online filter impurities in cooling liquid to avoid IT equipment contamination.
  • Fire Protection & Safety Protection System: Matching inert gas protection devices fill nitrogen inside cavities to form an inert gas protective layer, inhibiting cooling liquid oxidative volatilization and isolating oxygen to reduce fire risks. Equipped with emergency power cut-off, emergency pressure relief and fire linkage interfaces to meet safety specifications of Class A data centers.

3. System Classification

The full KITOZER immersion liquid cooling cabinet product matrix is categorized by heat exchange principle, deployment form, power density and application scenarios as follows:

3.1 Classification by Heat Exchange Principle (Core Technical Route)

3.1.1 Single-phase Immersion Liquid Cooling System

Single-phase immersion liquid cooling is the mainstream commercial technical route in the market with over 80% market share, relying on sensible heat exchange. The cooling liquid remains liquid throughout the circulation without phase change. It absorbs heat from IT heat-generating components via forced circulation or natural convection, and the heated cooling liquid flows back to the CDU for cooling before recirculating into immersion cavities to complete closed-loop circulation.

  • Core Features: Simple system structure, mature control logic, low deployment cost and high operation convenience. Loose requirements for cooling liquid, compatible with synthetic hydrocarbon, mineral oil and fluorinated liquid media. No pressure-resistant sealing design needed as cavity operating pressure is close to atmospheric pressure with low safety risks. Strong compatibility without server hardware modification — only cooling fans need removal for direct immersion, supporting mainstream servers and GPUs from most brands.
  • Performance Parameters: Single cabinet heat dissipation capacity 20kW~150kW, system PUE stably 1.05~1.09, vertical cavity temperature difference ≤5℃, annual cooling liquid loss rate ≤3%, service life ≥15 years.
  • Applicable Scenarios: General cloud computing data centers, enterprise computing power centers, medium-sized AI training clusters, university research HPC platforms and air-cooled-to-liquid-cooled renovation projects of traditional machine rooms, the most widely adopted immersion liquid cooling technical route.

3.1.2 Two-phase (Phase Change) Immersion Liquid Cooling System

Two-phase immersion liquid cooling serves as the ultimate heat dissipation solution for ultra-high heat density scenarios, adopting latent heat exchange principles with low-boiling special fluorinated liquid as cooling medium. When the surface temperature of IT heat-generating components reaches the boiling point of cooling liquid, nuclear boiling occurs and liquid vaporizes into gas, absorbing massive heat via latent heat of vaporization. The rising steam condenses into liquid on condenser tubes at the top of the cavity after heat exchange with primary cooling water, flowing back to the cavity bottom by gravity to complete closed-loop circulation.

  • Core Features: Extremely high heat exchange efficiency, 3~5 times that of single-phase liquid cooling, supporting single cabinet heat dissipation of 100kW~1200kW ultra-high heat density. Passive pump-free circulation can be realized with lower system energy consumption and PUE as low as 1.02~1.05. Boiling phase change achieves uniform chip temperature control without local hot spots, with chip temperature difference ≤2℃ to fully release GPU/CPU overclocking performance and boost computing power by over 10%.
  • Performance Parameters: Single cabinet heat dissipation capacity 100kW~1200kW, system PUE stably 1.02~1.05, cavity gas zone pressure control accuracy ±5kPa, chip surface temperature difference ≤2℃, annual cooling liquid loss rate ≤5%, service life ≥20 years.
  • Applicable Scenarios: Ten-thousand-card AI large model training clusters, national supercomputing centers, autonomous driving simulation computing power centers, quantum computing and other ultra-high heat density computing power scenarios, the core heat dissipation solution for next-generation megawatt-level computing power infrastructure.

3.2 Classification by Deployment Form

3.2.1 Standard Rack-mounted Immersion Liquid Cooling Cabinet

Adopts standard 19-inch rack design with widths of 600mm/800mm and heights of 42U/48U/72U, depths of 1200mm/1500mm/1500mm. Fully compatible with floor modulus and channel layout of traditional data centers, enabling direct replacement of traditional air-cooled cabinets without large-scale machine room reconstruction for rapid deployment.

  • Core Features: Standardized design with strong universality, supporting independent single cabinet operation or multi-machine cluster deployment. Suitable for renovation projects of traditional machine rooms to greatly reduce reconstruction cost and cycle. Supports hot & cold aisle closed layout with operation space complying with machine room design specifications.
  • Performance Parameters: Height range 42U~72U, single cabinet heat dissipation capacity 20kW~120kW, compatible with standard rack servers and GPU servers. Each cabinet can hold 36 sets of 2U servers or 18 sets of 4U GPU servers.

3.2.2 Integrated Container-type Immersion Liquid Cooling Data Center

Integrates immersion liquid cooling cabinets, CDU units, cold source systems, power supply systems, monitoring systems and fire protection systems inside standard containers to form prefabricated, modular and movable integrated liquid cooling computing power centers with “plug-and-play, power-on-ready” functionality.

  • Core Features: Full prefabricated production with pre-installation and commissioning completed in factories. On-site connection of water and electricity only required, cutting deployment cycle by over 80% compared with traditional machine rooms. High mobility allows flexible relocation and capacity expansion according to computing power demands. Unrestricted by building space, deployable in industrial parks, wild areas and remote regions to support rapid construction of national hub nodes under the “East Data, West Computing” initiative. Windproof, rainproof, dustproof, shockproof and thermal insulation properties adapt to various complex environments.
  • Performance Parameters: Container specifications cover 20ft/40ft/45ft standard containers, single-box computing power density up to 2 PFLOPS, PUE stably ≤1.08, supporting parallel expansion of multiple containers for rapid construction of ultra-large-scale liquid cooling computing power clusters.

3.2.3 Pool-type Immersion Liquid Cooling System

Adopts large immersion liquid pool design with dozens to hundreds of IT equipment centrally immersed in one large liquid cooling pool, matched with centralized CDU and cold source systems to form large-scale pool-type deployed liquid cooling clusters for ultra-large-scale computing power center construction.

  • Core Features: Lower cost for large-scale deployment, unit kW heat dissipation cost reduced by over 30% compared with single cabinet deployment. Higher system redundancy and more convenient operation with high-efficiency centralized management. Supports deployment of high-density computing power clusters with unit area computing power density over 5 times that of traditional machine rooms.
  • Performance Parameters: Customizable single pool capacity with single pool heat dissipation capacity ranging from 500kW to 50MW, suitable for ten-thousand-card AI training clusters and ultra-large-scale cloud computing data centers with PUE stably ≤1.05.

3.2.4 Edge-level Miniature Immersion Liquid Cooling Cabinet

Miniaturized silent immersion liquid cooling cabinets developed for edge computing scenarios, with heights ranging from 7U to 24U and heat dissipation capacity of 2kW~20kW. Directly deployable in office buildings, factory workshops, base station machine rooms and business halls without supporting dedicated air conditioning.

  • Core Features: Compact size with floor area ≤0.5㎡ and flexible installation. Operating noise ≤35dB without fan noise, deployable in office environments. Fully enclosed design with dustproof and moistureproof properties adapting to complex environments. Built-in integrated air-cooled cold source without external cooling water system, ready for operation after power connection.
  • Applicable Scenarios: 5G edge computing nodes, industrial internet edge computing, smart parks, video rendering workstations, small and micro enterprise computing power machine rooms and small experimental platforms of research institutes.

3.3 Classification by Power Density Grade

表格

GradeSingle Cabinet Heat Dissipation CapacityCore Applicable Scenarios
Entry-level2kW~20kWEdge computing, small and micro enterprise machine rooms, small rendering workstations
Medium Grade20kW~60kWEnterprise-level data centers, general cloud computing platforms, medium-sized AI inference clusters
High Density60kW~150kWLarge AI training clusters, high-performance computing platforms, supercomputing centers
Ultra-high Density150kW~1200kWTen-thousand-card AI large model training, national supercomputing centers, quantum computing, megawatt-level computing power clusters

3.4 Classification by Cooling Liquid Medium Type

3.4.1 Synthetic Hydrocarbon Immersion Liquid Cooling System

Adopts eco-friendly synthetic hydrocarbon cooling liquid, the mainstream medium solution in the market with cost only 1/6 of imported fluorinated liquid. It features excellent insulation, thermal conductivity and material compatibility, with biodegradability ≥90%, non-toxicity and zero ozone depletion risk.

  • Core Advantages: Moderate cost and strong material compatibility with no swelling or corrosion on server PCBs, electronic components, rubber and plastic materials. Strong chemical stability with service life ≥8 years and ultra-low annual loss rate. High flash point as a flame-retardant medium with low safety risks, suitable for most general immersion liquid cooling scenarios.

3.4.2 Mineral Oil Immersion Liquid Cooling System

Adopts deeply refined mineral oil as cooling medium with the lowest procurement cost and excellent insulation (breakdown voltage ≥30kV), suitable for large-scale general scenarios with limited budgets.

  • Core Advantages: Low procurement cost and sufficient supply with stable insulation and good fluidity, greatly reducing initial project investment for non-sensitive large-scale general computing power scenarios.

3.4.3 Fluorinated Liquid Immersion Liquid Cooling System

Divided into perfluoropolyether and hydrofluoroether eco-friendly fluorinated liquids with extreme insulation, chemical stability and material compatibility, non-flammable with zero flash point and highest safety grade. Split into high-boiling single-phase fluorinated liquid and low-boiling two-phase fluorinated liquid for high-end, ultra-high heat density and high-safety scenarios.

  • Core Advantages: Non-flammable with zero fire risk; extremely chemically inert with 100% compatibility with all electronic component materials without corrosion or swelling; service life ≥15 years with no replacement required throughout the full lifecycle. Ultra-low surface tension penetrates tiny chip gaps for dead-zone-free heat exchange. Two-phase fluorinated liquid realizes extreme phase change heat dissipation for ultra-high heat density AI computing power scenarios.

4. System Schematic Diagrams

4.1 Single-phase Immersion Liquid Cooling System Working Principle Diagram

The KITOZER single-phase immersion liquid cooling system adopts a dual closed-loop architecture split into the secondary IT medium circulation loop and primary cold source circulation loop. Heat is transferred without contact via plate heat exchangers inside the CDU, with complete physical isolation between primary and secondary sides to thoroughly eliminate risks of cooling water leakage contaminating IT equipment.

4.1.1 Secondary IT Medium Circulation Loop (Core Heat Exchange Link)

  1. Low-temperature cooling liquid is pressurized by CDU circulation pumps and delivered to liquid cooling cabinet liquid inlets via liquid supply pipelines, entering inner tanks from cabinet bottoms. Diversion and uniform flow structures distribute liquid evenly upward to fully immerse servers, GPUs and other IT equipment.
  2. Heat-generating components including CPUs, GPUs, memory and hard drives transfer heat directly to cooling liquid, which warms up and flows out of cabinet liquid outlets at the top back to the CDU via return pipelines.
  3. Heated high-temperature cooling liquid enters plate heat exchangers inside the CDU to exchange heat with primary low-temperature cooling water, releasing heat and cooling down into low-temperature liquid again.
  4. Cooled low-temperature cooling liquid passes through CDU filters, pressure stabilizers and flow regulating devices before being repressurized by circulation pumps and delivered back to liquid cooling cabinets to complete closed-loop circulation.

4.1.2 Primary Cold Source Circulation Loop

  1. Low-temperature cooling water enters the primary side inlet of CDU plate heat exchangers, absorbs heat transferred from secondary cooling liquid and warms up, flowing out of heat exchanger outlets to outdoor cold source systems (dry coolers / closed cooling towers / chillers) via pipelines.
  2. High-temperature cooling water discharges heat into the atmosphere through air cooling, evaporative cooling or mechanical refrigeration inside outdoor cold source systems and cools back into low-temperature cooling water.
  3. Cooled low-temperature cooling water passes through filtration and pressure stabilization before being repressurized by circulation pumps and delivered back to CDU plate heat exchangers to complete closed-loop circulation.

4.1.3 Intelligent Monitoring & Protection Link

Distributed sensors collect full-link operating parameters including primary & secondary supply/return water temperature difference, pressure, flow rate, cavity liquid level, temperature, cooling liquid conductivity and pump status in real time, uploading data to PLC controllers and intelligent monitoring platforms. Platforms automatically adjust pump speed, valve opening and cold source output based on set parameters and real-time operating data to realize full-automatic closed-loop system control. Graded alarms and interlock protective actions are automatically triggered under abnormal conditions to guarantee safe and stable system operation.

4.2 Two-phase (Phase Change) Immersion Liquid Cooling System Working Principle Diagram

The KITOZER two-phase immersion liquid cooling system relies on phase change heat exchange principles, split into an in-cavity phase change condensation circulation link and primary cooling water circulation link. Passive pump-free circulation can be realized with lower system energy consumption.

  1. Low-boiling fluorinated cooling liquid is stored at the cavity bottom with fully immersed IT equipment. Heat generated by operating components raises contact cooling liquid temperature to boiling point, triggering nuclear boiling and liquid-to-gas vaporization that absorbs massive heat from components via latent heat of vaporization.
  2. Low-density cooling liquid steam rises naturally to condenser tube bundles at the cavity top, where low-temperature primary cooling water flows inside tubes. High-temperature steam releases heat upon contact with low-temperature tube walls, condensing back into liquid cooling liquid that flows down tube walls by gravity to the cavity bottom for renewed phase change heat exchange, completing closed-loop in-cavity phase change circulation.
  3. Primary cooling water absorbs heat released by steam inside condenser tubes and warms up, delivered to outdoor cold source systems via pipelines to discharge heat into the atmosphere. Cooled low-temperature cooling water flows back to condenser tube bundles to complete primary closed-loop circulation.
  4. Matched pressure, temperature and liquid level monitoring devices track cavity pressure, temperature and cooling liquid liquid levels in real time. Primary cooling water flow and temperature are regulated to precisely control saturated cavity pressure and temperature for accurate IT equipment temperature management. Pressure relief and emergency protective devices are equipped to guarantee system safety.

4.3 System Architecture Visual Schematic

[IT Equipment Heat Generation] → [Direct Heat Absorption by Cooling Liquid (Single/Two-phase Heat Exchange)] → [High-temperature Cooling Liquid/Steam] → [CDU/Condenser Heat Exchange] → [Heat Transferred to Primary Cooling Water] → [Outdoor Cold Source Discharges Heat to Atmosphere]

↓

[Intelligent Monitoring System] ← [Full-link Sensor Data Collection] ← [Dynamic Regulation of Circulation Pumps/Valves/Cold Source Systems]

  • Core heat exchange nodes of single-phase system: IT Equipment → Cooling Liquid → Plate Heat Exchanger → Cooling Water → Outdoor Cold Source
  • Core heat exchange nodes of two-phase system: IT Equipment → Cooling Liquid Boiling Phase Change → Steam Condensation → Cooling Water → Outdoor Cold Source

5. Full System Configuration List

KITOZER immersion liquid cooling cabinet system configurations are divided into Entry-level (low spec), Enterprise-level (medium spec) and Flagship-level (high spec) to cover all scenario demands, all branded KITOZER with detailed breakdowns below.

5.1 Entry-level Single-phase Immersion Liquid Cooling System Configuration List (20kW Single Cabinet, Edge Computing & Small Enterprise Machine Rooms)

表格

No.Product NameModelTechnical ParametersQtyUnitBrandRemarks
1Standard Single-phase Immersion Liquid Cooling CabinetKTZ-JM-DX-20kW-42U19-inch standard rack, dimensions 600mm×1200mm×2000mm (W×D×H), 42U usable space; inner tank 304 stainless steel ≥2mm thick; frame cold-rolled steel with electrostatic plastic spraying; rated heat dissipation capacity 20kW; atmospheric operating pressure; IP67 protection; standard transparent observation window, A/B dual busbars, server guide rails, liquid inlet/outlet ports, drain port, foot pads + casters; load capacity ≥1500kg1SetKITOZERCustomizable size & U slots
2Single-phase Immersion Synthetic Hydrocarbon Cooling LiquidKTZ-MED-SH-46Synthetic hydrocarbon grade 46 viscosity; breakdown voltage ≥35kV; thermal conductivity ≥0.08W/(m·K); flash point ≥220℃; freezing point ≤-30℃; kinematic viscosity 46mm²/s @40℃; acid value ≤0.03mgKOH/g; fully compatible with electronic components; biodegradability ≥90%200LKITOZERConfigured by cavity volume, supplementary on demand
3Cabinet-level Cooling Distribution Unit (CDU)KTZ-CDU-JG-20kWRated heat exchange capacity 20kW; primary/secondary 316L stainless steel plate heat exchanger, heat exchange efficiency ≥98%; one-working-one-standby canned pumps 0.75kW×2, lift 15m, flow 10m³/h; 220V AC input; standard high-precision temp/pressure/flow/liquid level sensors; 7-inch touch screen, PLC controller, Modbus protocol; built-in filter, pressure stabilizer, electric regulating valve, safety relief valve; IP54 protection1SetKITOZEROne-to-one cabinet matching, wall/floor mountable
4Air-cooled Dry CoolerKTZ-GLQ-FL-25kWRated cooling capacity 25kW; standard EC variable frequency fans 0.55kW×2, air volume 8000m³/h; copper tube aluminum fin heat exchange coils; 220V AC input; operating temp -30℃~45℃; water outlet temp control accuracy ±2℃; low-temperature antifreeze protection, variable frequency fan control; IP54 protection1SetKITOZER1.25x redundant design for northern regions
5Intelligent Monitoring SystemKTZ-JK-ENT-100Industrial monitoring host, 10.1-inch touch screen; standard data acquisition, alarm and remote communication modules; full-system real-time parameter monitoring, historical data storage, fault early warning, remote access; compatible with environment monitoring systems; supporting monitoring software V1.01SetKITOZERStandard, includes 1-year software upgrade service
6Cabinet Power Distribution SystemKTZ-PD-42U-63AA/B dual input, 63A/2P circuit breaker ×2; T2 nickel-plated copper busbar rated 63A; matched 12×C13 + 4×C19 output PDU rated 32A; leakage, overcurrent and short-circuit protection; voltage/current/power monitoring1SetKITOZERCustomizable input/output specifications
7Pipeline SystemKTZ-GL-20kW304 stainless steel DN25 pipelines; matched ball valves, check valves, flexible connections, pressure gauges, thermometers; pipeline insulation ≥20mm thick, flame retardant Class B1; includes pipeline supports and fixings1SetKITOZERCustomized by on-site deployment distance
8Leakage Detection SystemKTZ-LD-44m cable-type leakage detection sensor; 1 positioning controller; response time ≤1s, detection precision ≤1mm; supports sound-light alarm, relay output and valve interlock closure1SetKITOZERStandard full bottom cabinet coverage
9Liquid Filling & Draining DeviceKTZ-BY-50L50L 304 stainless steel storage tank; matched filling/draining pumps 0.37kW; inlet/outlet valves, filters, liquid level gauges; manual/automatic filling modes1SetKITOZEROptional, centralized configuration for multiple cabinets
10Emergency Protection DeviceKTZ-EP-20kWMatched emergency pressure relief valve, emergency shut-off valve, bypass pipeline, fire linkage interface; interlock protection module for over-temperature, over-pressure and low liquid level1SetKITOZERStandard, CDU interlocked

5.2 Enterprise-level Single-phase Immersion Liquid Cooling System Configuration List (6-Cabinet Cluster, 40kW per cabinet, Total 240kW Heat Dissipation, Enterprise Data Centers & Medium AI Training Clusters)

表格

No.Product NameModelTechnical ParametersQtyUnitBrandRemarks
1Standard Single-phase Immersion Liquid Cooling CabinetKTZ-JM-DX-40kW-48U19-inch standard rack, dimensions 800mm×1500mm×2200mm (W×D×H), 48U usable space; inner tank 316L stainless steel ≥3mm thick; frame high-strength cold-rolled steel electrostatic sprayed; rated heat dissipation capacity 40kW; atmospheric operating pressure; IP67 protection; double-opening top cover opening ≥90° with safety lock; 2 tempered glass observation windows; A/B dual redundant T2 nickel-plated copper busbars; dedicated server guide rails & positioning structures; liquid inlet/outlet, liquid level balance and emergency drain ports; reinforced frame with zero deformation under full load; static load capacity ≥3000kg; 4 load-bearing foot pads + 4 heavy-duty casters6SetKITOZERCustomizable U slots, dimensions and materials for GPU servers
2Single-phase Immersion Eco-friendly Fluorinated LiquidKTZ-MED-FH-120High-boiling single-phase fluorinated liquid; boiling point ≥120℃; freezing point ≤-40℃; breakdown voltage ≥40kV; thermal conductivity ≥0.075W/(m·K); kinematic viscosity 1.2mm²/s @25℃; surface tension ≤15mN/m; chemically inert with full compatibility with all electronic materials; non-flammable with zero flash point; ODP=0, eco-friendly non-toxic; annual loss rate ≤3%1500LKITOZER250L per cabinet + 10% spare allowance
3Machine Room-level Cooling Distribution Unit (CDU)KTZ-CDU-JF-300kWRated heat exchange capacity 300kW (1.25x redundant); primary/secondary 316L stainless steel plate heat exchanger, heat exchange efficiency ≥98%, pressure resistance 1.6MPa; one-working-one-standby magnetic levitation centrifugal pumps 5.5kW×2, lift 30m, flow 120m³/h; 380V AC 50Hz input; standard high-precision PT100 temp sensors, pressure transmitters, electromagnetic flowmeters, liquid level & conductivity sensors; 10-inch industrial touch screen, Siemens PLC controller, Modbus TCP/IP & BACnet protocols; built-in full-automatic pressure makeup water unit, multi-stage filter, electric proportional regulating valve, safety relief valve and check valve; full physical primary/secondary isolation; built-in emergency bypass; IP54 protection; supports multi-cabinet cluster collaborative control & AI adaptive temperature regulation1SetKITOZERCentralized deployment for 6 cabinets, expandable to 10
4Closed Cooling Tower Cold Source SystemKTZ-BSL-350kWRated cooling capacity 350kW (1.2x redundant); evaporative cooling, 304 stainless steel coils ≥1.2mm thick; 4 EC variable frequency axial fans single power 1.5kW, total air volume 60000m³/h; spray pumps 3kW one-working-one-standby; supply/return water temp 32℃/37℃; operating temp -30℃~45℃; standard electronic water processor, water makeup & blowdown unit, low-temperature antifreeze protection, variable frequency fan control; IP55 protection; CDU linkage control compatible1SetKITOZERFor medium-high temperature high-humidity regions, replaceable with dry cooler natural cooling systems
5Waste Heat Recovery DeviceKTZ-YHS-300kW316L stainless steel plate heat exchanger rated 300kW heat exchange capacity; matched electric regulating valves and temp sensors, circulation pumps; graded waste heat recovery with stable output water temp 45~60℃; compatible with building heating & domestic hot water linkage; built-in intelligent control module for automatic heat regulation1SetKITOZEROptional, customizable recovery capacity on demand
6Cluster Intelligent Monitoring & Operation Management PlatformKTZ-JK-CLU-2000Industrial I5 controller, 8G memory, 1T SSD; 27-inch 4K high-definition display; distributed data acquisition modules, redundant communication modules; 3D visual monitoring interface tracking 200+ full-system parameters in real time; built-in AI adaptive temperature control algorithm, fault early warning & diagnosis system, historical data storage & analysis system, operation work order management system; Web/multi-mobile terminal access compatible; connects to machine room BMS environment monitoring systems; data storage cycle ≥10 years1SetKITOZERIncludes 3-year software upgrade & technical support service
7Cabinet Power Distribution SystemKTZ-PD-48U-125ASingle cabinet A/B dual redundant input, 125A/3P molded case circuit breaker ×2; T2 nickel-plated copper busbar rated 125A; matched hot-swappable power frames with 36kW single frame rated 48V DC output; matched 16×C13 + 8×C19 intelligent PDU rated 63A with voltage/current/power/power factor monitoring and remote circuit breaking control; standard leakage, overcurrent, short-circuit, overvoltage and surge protection6SetKITOZERCustomizable AC/DC input specifications for HVDC power supply
8Cluster Pipeline SystemKTZ-GL-CLU-300kWMain pipelines 304 stainless steel DN100, branch pipelines DN50; matched national standard flange connections, manual ball valves, electric regulating valves, check valves, flexible expansion joints, bellows compensators; local pressure gauges and bimetallic thermometers; polyurethane pipeline insulation ≥30mm thick, flame retardant Class B1 with PVC outer protective layer; includes pipeline supports, fixings and seismic hangers; equal-flow layout for uniform cabinet flow distribution1SetKITOZERCustomized by on-site deployment distance, includes hydraulic & air tightness pipeline testing
9Distributed Leakage Detection SystemKTZ-LD-CLU-50Positioning cable-type leakage detection sensor total length 50m; 1 main controller + 6 regional controllers; response time ≤1s, positioning precision ±0.5m; supports sound-light alarm, screen pop-up, SMS & email alarm; interlocks CDU and emergency valves to auto-close corresponding pipeline segments and trigger emergency draining upon leakage1SetKITOZERFull coverage of cabinet bottoms, pipeline interfaces, CDU and cold source machine rooms
10Centralized Liquid Filling & Draining SystemKTZ-BY-CLU-2000L2000L 304 stainless steel storage tank with liquid level gauge and high/low liquid level alarm; matched filling/draining pumps 2.2kW, flow 20m³/h, lift 20m one-working-one-standby; multi-stage filtration device precision 5μm; online purification device to remove liquid impurities and moisture; manual/automatic filling modes supporting independent single cabinet filling/draining; matched emergency storage tank with capacity ≥ single cabinet total volume1SetKITOZERCluster shared, customizable capacity on demand
11Emergency Protection & Safety SystemKTZ-EP-CLU-300kWSystem-level interlock protection module for over-temperature, over-pressure, low pressure, low liquid level, leakage and pump failure; three-level graded alarm response (warning/alarm/emergency shutdown); emergency bypass system ensuring normal operation under single-point faults; emergency pressure relief valves, emergency shut-off valves, fire linkage interfaces; inert gas protection device with nitrogen sealing inside cavities to suppress liquid oxidation; emergency power supply interface to maintain monitoring & emergency system operation during power outages1SetKITOZERFully interlocked with CDU and monitoring platform
12Operation Toolkit SuiteKTZ-YW-GJ-01Server dedicated lifting fixture, dedicated drain/fill connectors, medium sampling tools, seal replacement tools, insulation protective gear, leak detection tools; matched dedicated operation trolley and mobile platform1SetKITOZERStandard, adapts to on-site maintenance demands

5.3 Flagship Two-phase Immersion Liquid Cooling System Configuration List (10-Cabinet Cluster, 120kW per cabinet, Total 1200kW Heat Dissipation, Ten-thousand-card AI Large Model Training & Supercomputing Centers)

表格

No.Product NameModelTechnical ParametersQtyUnitBrandRemarks
1Two-phase Phase Change Immersion Liquid Cooling CabinetKTZ-JM-LX-120kW-72UDimensions 1200mm×1800mm×2400mm (W×D×H), 72U usable space; inner tank 316L stainless steel ≥5mm thick, double-sided welding with 100% air tightness testing; frame high-strength carbon steel anti-corrosion sprayed; rated heat dissipation capacity 120kW, peak 150kW; design working pressure 0.6MPa, pressure resistance 1.0MPa; IP68 protection; quick-opening high-pressure sealed top cover with fluorine rubber multi-layer sealing and safety interlock; 3 explosion-proof tempered glass observation windows; A/B dual redundant HVDC T2 silver-plated copper busbars rated 250A; dedicated GPU server fixing brackets and guiding positioning structures; built-in microchannel condenser tube bundles 316L stainless steel with heat exchange area ≥80㎡; standard steam diversion and condensed liquid reflux structures; water inlet/outlet, liquid level balance, emergency drain and pressure relief ports; reinforced frame static load capacity ≥8000kg; 8 heavy-duty load-bearing foot pads + shock absorption devices10SetKITOZERCustomizable power, dimensions and pressure resistance for NVIDIA H100/H200, AMD MI300X and other high-end GPUs
2Two-phase Immersion Low-boiling Fluorinated LiquidKTZ-MED-FH-55Low-boiling eco-friendly fluorinated liquid, boiling point 55℃ @ standard atmospheric pressure; freezing point ≤-80℃; breakdown voltage ≥45kV; latent heat of vaporization ≥110kJ/kg; thermal conductivity ≥0.07W/(m·K); kinematic viscosity 0.7mm²/s @25℃; surface tension ≤12mN/m; extremely chemically inert with 100% compatibility with all electronic materials; non-flammable zero flash point with zero explosion risk; ODP=0, ultra-low GWP meeting environmental standards; annual loss rate ≤5%3500LKITOZER350L per cabinet + 10% spare allowance
3Megawatt Machine Room-level Cooling Distribution Unit (CDU)KTZ-CDU-MW-1500kWRated heat exchange capacity 1500kW (1.25x redundant); primary/secondary 316L stainless steel dual-circuit plate heat exchanger, heat exchange efficiency ≥99%, pressure resistance 1.6MPa; two-working-two-standby magnetic levitation centrifugal pumps 11kW×4, lift 40m, flow 600m³/h; 380V AC 50Hz dual redundant input power supply; standard 0.1-class high-precision PT100 temp sensors, high-precision pressure transmitters, electromagnetic flowmeters, liquid level, conductivity and oxygen content sensors; 15-inch industrial touch screen, redundant Siemens PLC controller, Profinet/Modbus TCP/IP/BACnet/IP protocols; built-in full-automatic constant pressure makeup water unit, multi-stage precision filter, electric proportional regulating valve, safety relief valve, check valve and emergency cut-off valve; full physical primary/secondary isolation with dual-circuit redundancy; N+1 emergency bypass supporting maintenance without shutdown; built-in AI intelligent load prediction & dynamic regulation system; IP54 protection; supports dual machine room redundancy deployment & cluster collaborative control1SetKITOZERCentralized deployment for 10 cabinets, expandable to 20
4Composite Cold Source System (Natural Cooling + Chiller)KTZ-LY-MW-1800kWRated cooling capacity 1800kW (1.5x redundant); composite design integrating dry cooler natural cooling + screw chiller; dry cooler copper tube aluminum fin structure with EC variable frequency fans total air volume 300000m³/h, natural cooling ratio ≥85% annually; twin-screw chiller COP ≥6.2 full liquid evaporator, R134a eco-friendly refrigerant; design supply/return water temp 30℃/35℃; standard full-automatic control system auto-switching natural cooling/mechanical cooling/composite cooling modes by ambient temperature; matched electronic water treatment system, full-automatic makeup water unit, antifreeze protection system and variable frequency control; IP55 protection; CDU linkage for optimal system energy efficiency1SetKITOZERAdapts to national climate conditions nationwide, customizable cold source solutions on demand
5High-efficiency Waste Heat Recovery SystemKTZ-YHS-MW-1500kWRated recovered heat capacity 1500kW; three-stage waste heat recovery architecture with 316L stainless steel plate heat exchanger heat exchange efficiency ≥98%; matched variable frequency pump sets two-working-two-standby; intelligent temperature control system stably outputting 50~85℃ hot water; compatible with multi-scenario waste heat utilization including building heating, domestic hot water, agricultural greenhouses, industrial process heating and absorption refrigeration; built-in heat metering module and data statistical analysis system; connectable to park energy management systems for cascaded energy utilization1SetKITOZEROptional, customizable recovery temperature and heat capacity on demand
6Data Center-level Intelligent Operation & Control PlatformKTZ-JK-DC-5000Redundant industrial server dual CPU, 32G memory, 4T SSD redundant array; dual 49-inch 4K splicing screens; distributed I/O acquisition modules, redundant fiber communication architecture; full-system 3D digital twin visual interface real-time mapping physical system operating status; built-in AI large model prediction algorithm forecasting load changes 72 hours in advance to dynamically optimize system operating parameters; fault self-diagnosis & self-recovery system with 2000+ fault model library and fault positioning accuracy ≥99%; full-lifecycle asset management system, maintenance plan management system, closed-loop work order management system and personnel authority management system; Web/mobile terminal/control room multi-terminal access compatible; connects to data center BMS/DCIM systems; data storage cycle ≥20 years supporting backup & export; complies with Class 2.0 Cybersecurity Level 3 requirements1SetKITOZERIncludes 5-year software upgrade & technical support service, customizable functional modules
7Cabinet HVDC Power Distribution SystemKTZ-PD-72U-250A-HVDCSingle cabinet A/B dual redundant 380V HVDC input, 250A/3P DC circuit breaker ×2; T2 silver-plated copper busbar rated 250A with temperature rise ≤30K; matched N+1 redundant hot-swappable power frames single frame rated 72kW efficiency ≥96.5%; matched intelligent HVDC PDU supporting per-circuit voltage/current/power monitoring and remote circuit breaking control; standard leakage, overcurrent, short-circuit, overvoltage, undervoltage, surge and insulation monitoring protection; underwater live hot-swap design supporting maintenance without shutdown10SetKITOZERCustomizable 240V/380V DC, 220V/380V AC input specifications
8Megawatt Cluster Pipeline SystemKTZ-GL-MW-1500kWMain pipelines 316L stainless steel DN200, branch pipelines DN80; welded connections with 100% non-destructive flaw detection; matched national standard flanges, manual ball valves, electric emergency cut-off valves, proportional regulating valves, check valves, bellows compensators and shock absorption flexible connections; high-precision pressure transmitters and PT100 temp sensors installed locally; polyurethane rigid foam pipeline insulation ≥50mm thick, flame retardant Class B1 with aluminum alloy outer protective layer; includes heavy-duty pipeline supports, seismic hangers and fixings; equal-flow balanced layout with cabinet flow distribution deviation ≤5%; pipeline design pressure resistance 1.6MPa, hydraulic test pressure 2.4MPa1SetKITOZERCustomized by on-site deployment, includes full pipeline design, installation and testing services
9Full-scenario Distributed Leakage Detection & Emergency SystemKTZ-LD-MW-200Positioning fiber leakage detection system total length 200m; 2 redundant main controllers + 12 regional controllers; response time ≤500ms, positioning precision ±0.2m; supports sound-light alarm, control room pop-up, SMS, telephone and email alarm; three-level emergency linkage mechanism: level 1 alarm, level 2 auto-close corresponding regional valves, level 3 emergency shutdown protection; matched emergency drainage system emptying single cabinet medium to emergency storage tanks within 10 minutes; full-system blind-spot-free coverage including cabinets, pipelines, CDU, cold source machine rooms and liquid storage rooms1SetKITOZERComplies with Class A data center safety specification requirements
10Centralized Medium Storage & Purification SystemKTZ-MED-ST-10000L10000L 316L stainless steel double-insulated storage tank with magnetic flip liquid level gauge and high/low liquid level interlock alarm; matched filling/draining pump sets two-working-two-standby power 4kW, flow 40m³/h, lift 30m; online precision filtration purification system three-stage filtration precision 1μm; online dehydration and medium regeneration devices removing moisture, impurities and degradation products to extend medium service life; full-automatic medium management system supporting independent single cabinet filling, draining and medium replacement; matched 2×5000L emergency storage tanks meeting system emergency draining demands; matched inert gas sealing protection device isolating oxygen to suppress medium oxidation1SetKITOZERCluster shared, customizable capacity on demand
11System-level Safety & Emergency Protection SystemKTZ-EP-MW-1500kWRedundant safety control system physically isolated from main control system; full-system interlock protection against over-temperature, over-pressure, low pressure, low liquid level, vacuum, leakage, insulation abnormality and pump failure; four-level graded alarm & emergency response mechanism; N+1 emergency bypass system supporting maintenance & fault handling without shutdown; spring safety valves and rupture discs for dual pressure relief protection; fire linkage system seamlessly connected to machine room fire protection; inert gas fire extinguishing linkage interface; emergency UPS power supply guaranteeing normal operation of monitoring, emergency systems and valves during power outages; personnel safety interlock device auto-cutting power and pressure relief upon top cover opening1SetKITOZERComplies with national Class A data center and supercomputing center safety design specifications
12Professional Operation Toolkit & Laboratory EquipmentKTZ-YW-PRO-02Server dedicated hydraulic lifting system, underwater live hot-swap special tools, complete seal replacement kit, medium sampling & testing equipment, weld leak detector, insulation tester, temperature & pressure calibrators; matched mobile operation platform, special maintenance ladder and medium recovery device; matched cooling liquid performance testing laboratory equipment for on-site detection of medium conductivity, acid value, moisture, viscosity and breakdown voltage1SetKITOZERProfessional maintenance supporting suite including operation training service
13Machine Room Environment Supporting SystemKTZ-HVAC-ROOMExplosion-proof air conditioning and ventilation systems dedicated to CDU and liquid storage rooms, combustible gas detection system, oxygen concentration detection system; machine room anti-static floor, grounding system and lighting system; matched safety protective fences, warning signs and emergency shower devices1SetKITOZERCustomizable on demand, complies with machine room safety specifications

6. Full Product Technical Parameters

6.1 Full Series Technical Parameters of KITOZER Immersion Liquid Cooling Cabinets

表格

Product SeriesSingle-phase Entry SeriesSingle-phase Enterprise SeriesTwo-phase Flagship SeriesEdge Mini SeriesContainer Integrated Series
ModelKTZ-JM-DX-20kW~40kWKTZ-JM-DX-40kW~150kWKTZ-JM-LX-100kW~1200kWKTZ-JM-BY-2kW~20kWKTZ-JM-JZX-500kW~5MW
Dimensions (W×D×H)600×1200×2000mm800×1500×2200mm1200×1800×2400mm600×800×1200mm12192×2438×2896mm (40ft container)
Usable U Slots42U48U/72U72U/96U7U/12U/24UCustomizable
Rated Heat Dissipation Capacity20kW~40kW40kW~150kW100kW~1200kW2kW~20kW500kW~5MW
Inner Tank Material304 Stainless Steel304/316L Stainless Steel316L Stainless Steel304 Stainless SteelContainer Weather-resistant Steel
Frame MaterialCold-rolled Steel Electrostatic SprayedHigh-strength Cold-rolled Steel Electrostatic SprayedHigh-strength Carbon Steel Anti-corrosion SprayedCold-rolled Steel Electrostatic SprayedContainer Special Weathering Steel
Design Operating PressureAtmosphericAtmospheric0~0.6MPaAtmosphericAtmospheric / 0.6MPa Optional
Protection GradeIP67IP67IP68IP67IP65
Vertical Cavity Temperature Difference≤5℃≤3℃≤2℃≤5℃≤3℃
Rated Load Capacity≥1500kg≥3000kg≥8000kg≥500kgCustomizable
Power Supply Mode220V AC Single/Dual Circuit220V/380V AC / 48V DC Dual Redundant240V/380V HVDC Dual Redundant220V AC Single Circuit380V AC Dual Redundant
Compatible Servers1U/2U Standard Rack Servers2U/4U GPU Servers, Rack Servers4U/8U AI Training Servers, High-end GPUs1U/2U Mini Servers, WorkstationsFull Series Servers & GPU Clusters
Operating Noise≤35dB≤30dB≤28dB≤35dB≤40dB
Design Service Life≥15 Years≥20 Years≥25 Years≥15 Years≥20 Years

6.2 Full Series Technical Parameters of KITOZER Cooling Distribution Units (CDU)

表格

Product SeriesCabinet-level CDUMachine Room-level CDUMegawatt-level CDUEdge Mini CDU
ModelKTZ-CDU-JG-10kW~50kWKTZ-CDU-JF-100kW~500kWKTZ-CDU-MW-500kW~5000kWKTZ-CDU-BY-2kW~20kW
Rated Heat Exchange Capacity10kW~50kW100kW~500kW500kW~5000kW2kW~20kW
Heat Exchanger Type316L Stainless Steel Plate Heat Exchanger316L Stainless Steel Dual-circuit Plate Heat Exchanger316L Stainless Steel Multi-circuit Redundant Plate Heat Exchanger316L Stainless Steel Brazed Plate Heat Exchanger
Heat Exchange Efficiency≥98%≥98%≥99%≥97%
Design Pressure Resistance1.6MPa1.6MPa1.6MPa1.0MPa
Circulation Pump ConfigurationOne-working-one-standby Canned PumpOne-working-one-standby Magnetic Levitation Centrifugal PumpTwo-working-two-standby Magnetic Levitation Centrifugal PumpSingle Pump + Standby Interface
Pump Power0.37kW~1.5kW3kW~7.5kW11kW~30kW0.18kW~0.75kW
Flow Regulation Range0~100%0~100% Variable Frequency Regulation0~100% Variable Frequency Regulation0~100%
Control ModePLC + Touch Screen Full-automatic ControlSiemens PLC + 10-inch Touch Screen, AI Adaptive ControlRedundant Siemens PLC + 15-inch Touch Screen, AI Large Model Prediction ControlSingle-chip Microcomputer + Button Control, PLC Optional
Monitored ParametersTemperature, Pressure, Flow, Liquid LevelTemperature, Pressure, Flow, Liquid Level, Conductivity, pH ValueTemperature, Pressure, Flow, Liquid Level, Conductivity, pH Value, Oxygen Content, TurbidityTemperature, Pressure, Liquid Level
Communication ProtocolsModbus RTU/TCPModbus TCP/IP, BACnetProfinet, Modbus TCP/IP, BACnet/IPModbus RTU
Input Voltage220V AC 50Hz380V AC 50Hz Dual Redundant380V AC 50Hz Dual Redundant220V AC
Protection GradeIP54IP54IP54IP54
Installation ModeWall/Floor MountedFloor MountedFloor Mounted with Shock Absorption FoundationWall / Cabinet Built-in
Design Service Life≥15 Years≥20 Years≥25 Years≥15 Years

6.3 Full Series Technical Parameters of KITOZER Cooling Liquid Media

表格

Product SeriesSynthetic Hydrocarbon LiquidMineral Oil LiquidSingle-phase Fluorinated LiquidTwo-phase Fluorinated Liquid
ModelKTZ-MED-SH-32/46/68KTZ-MED-KW-46KTZ-MED-FH-120/150KTZ-MED-FH-45/55/60
TypeSynthetic HydrocarbonDeeply Refined Mineral OilHydrofluoroether Single-phase Fluorinated LiquidPerfluoropolyether Two-phase Fluorinated Liquid
AppearanceColorless Transparent LiquidLight Yellow Transparent LiquidColorless Transparent LiquidColorless Transparent Liquid
Boiling Point @ Standard Atmospheric Pressure≥260℃≥240℃≥120℃45℃/55℃/60℃
Freezing Point≤-45℃≤-30℃≤-40℃≤-80℃
Flash Point≥220℃≥200℃None, Non-flammableNone, Non-flammable
Breakdown Voltage @25℃≥35kV≥30kV≥40kV≥45kV
Thermal Conductivity @25℃≥0.13W/(m·K)≥0.12W/(m·K)≥0.075W/(m·K)≥0.07W/(m·K)
Kinematic Viscosity @40℃32/46/68mm²/s46mm²/s≤1.5mm²/s≤0.8mm²/s
Latent Heat of Vaporization———≥110kJ/kg
Acid Value≤0.03mgKOH/g≤0.05mgKOH/g≤0.001mgKOH/g≤0.001mgKOH/g
Surface Tension @25℃≤30mN/m≤32mN/m≤15mN/m≤12mN/m
Ozone Depletion Potential (ODP)0000
Biodegradability≥90%≥60%BiodegradableBiodegradable
Electronic Material CompatibilityFully CompatibleFully Compatible100% Fully Compatible100% Fully Compatible
Recommended Service Life≥8 Years≥5 Years≥15 Years≥15 Years
Annual Loss Rate≤3%≤4%≤3%≤5%

6.4 Full Series Technical Parameters of KITOZER Cold Source Systems

表格

Product SeriesAir-cooled Dry CoolerClosed Cooling TowerScrew ChillerComposite Cold Source System
ModelKTZ-GLQ-FL-10kW~5000kWKTZ-BSL-50kW~10000kWKTZ-LSJ-100kW~10000kWKTZ-LY-FH-500kW~20000kW
Rated Cooling Capacity10kW~5000kW50kW~10000kW100kW~10000kW500kW~20000kW
Heat Exchange FormForced Air ConvectionEvaporative CoolingVapor Compression RefrigerationNatural Cooling + Mechanical Refrigeration Composite
Heat Exchange Coil MaterialCopper Tube Aluminum Fin / 304 Stainless Steel304/316L Stainless SteelShell & Tube / Full Liquid TypeCopper Tube Aluminum Fin + Shell & Tube
Fan ConfigurationEC Variable Frequency Axial FanEC Variable Frequency Axial Fan—EC Variable Frequency Fan Redundant Design
Compressor Type——Twin-screw CompressorTwin-screw Compressor One-working-one-standby
Rated COP——≥6.2 @ National Standard Working ConditionAnnual Comprehensive COP ≥15
Natural Cooling Ratio≥80% Northern Regions≥60% Central Regions—≥85% Annual Average
Design Supply/Return Water Temp32℃/37℃32℃/37℃7℃/12℃30℃/35℃
Ambient Operating Temp Range-30℃~45℃-15℃~45℃-5℃~45℃-35℃~45℃
Control ModeFull-automatic Variable Frequency Fan Control, Linkage CompatibleFull-automatic Variable Frequency Control, Linkage CompatiblePLC Full-automatic Control, Linkage CompatibleAI Intelligent Adaptive Control, Auto Mode Switching
Input Voltage220V/380V AC380V AC380V AC380V AC Dual Redundant
Protection GradeIP54IP55IP54IP55
Antifreeze ProtectionStandard Dry Antifreeze, Electric Heat TracingStandard Winter Antifreeze, Blowdown DeviceStandard Antifreeze Liquid CirculationFull-scenario Antifreeze Protection
Design Service Life≥15 Years≥15 Years≥20 Years≥20 Years

6.5 Technical Parameters of KITOZER Intelligent Monitoring Systems

表格

ItemEnterprise Monitoring SystemData Center-level Control PlatformEdge Monitoring Module
ModelKTZ-JK-CLU-2000KTZ-JK-DC-5000KTZ-JK-BY-100
ProcessorIndustrial Grade I5 ProcessorDual Redundant Industrial Server CPU32-bit ARM Processor
Memory/Storage8G RAM / 1T SSD32G RAM / 4T SSD RAID Array2G RAM / 32G EMMC
Display Interface27-inch 4K Touch ScreenDual 49-inch 4K Splicing Screens7-inch Touch Screen
Analog Input Channels32 Channels Expandable256 Channels Unlimited Expansion8 Channels
Digital Input Channels16 Channels Expandable128 Channels Expandable4 Channels
Relay Output Channels16 Channels Expandable64 Channels Expandable4 Channels
Communication InterfacesRS485, Ethernet, FiberRedundant Ethernet, Fiber, RS485, 5GRS485, Ethernet
Communication ProtocolsModbus, BACnetProfinet, Modbus, BACnet, OPC UAModbus
Data Collection Frequency100ms10ms1s
Data Storage Cycle≥10 Years≥20 Years≥1 Year
Alarm Response Time≤1s≤500ms≤2s
Control AlgorithmPID Closed-loop Control, AI Adaptive Temperature ControlAI Large Model Load Prediction, Adaptive Optimization, Fault Self-diagnosisPID Closed-loop Control
Access TerminalsWeb, MobileControl Room, Web, Mobile, Mini ProgramLocal Touch Screen, Web
Security LevelClass 2.0 Cybersecurity Level 2Class 2.0 Cybersecurity Level 3—
Input Voltage220V AC UPS Power Supply380V AC Dual UPS Redundant Power Supply220V AC
Operating Temperature0℃~50℃0℃~50℃-20℃~60℃
Protection GradeIP30IP30IP54

7. Full Product Application Scope

The KITOZER immersion liquid cooling cabinet system fully covers full-scenario computing power heat dissipation demands ranging from miniature edge computing nodes to national supercomputing centers, core application breakdowns as follows:

7.1 Artificial Intelligence & Large Model Computing Power Scenarios

  • AI Large Model Training & Inference Clusters: Compatible with ten-thousand-card NVIDIA H100/H200, AMD MI300X, Huawei Ascend 910 and other high-end GPU clusters, single cabinet heat dissipation capacity up to 1200kW to thoroughly break ultra-high heat density heat dissipation bottlenecks of AI training clusters. Chips operate at full rated frequency with computing power boosted by over 10% and training cycles shortened by over 20%.
  • Autonomous Driving Simulation Computing Power Centers: Adapts to ultra-high density computing power demands of autonomous driving algorithm training and simulation testing, enabling deployment of high-density GPU clusters with unit area computing power density over 5 times higher than traditional air cooling and drastically cutting energy costs.
  • AIGC, Digital Human & Video Rendering Computing Platforms: Suitable for film & television rendering, animation production and digital content generation, deployable inside office buildings with silent operation eliminating dedicated machine room requirements and lowering deployment barriers significantly.

7.2 High-performance Computing (HPC) & Supercomputing Center Scenarios

  • National/Provincial Supercomputing Centers: Adaptable to scientific computing tasks including weather forecasting, ocean environment simulation, aerospace simulation, nuclear physics research, gene sequencing and drug development. Enables deployment of megawatt-level computing power clusters with PUE stably controlled below 1.03 to meet green and low-carbon requirements of the national “East Data, West Computing” initiative.
  • University Research Institute Supercomputing Platforms: Suitable for small supercomputing clusters in university laboratories and research institutes with standardized modular design, short deployment cycles and convenient operation & maintenance without dedicated professional operation teams, supporting unattended operation.
  • Industrial Simulation & CAE Computing Platforms: Matches industrial simulation, finite element analysis and fluid mechanics computing demands for automotive, machinery, shipbuilding and electronics industries, enabling high-density computing power deployment and drastically shortening simulation calculation cycles.

7.3 Cloud Computing & Internet Data Center Scenarios

  • Ultra-large-scale Cloud Computing Data Centers: Adaptable to public, private and hybrid cloud platforms with pool-style large-scale deployment cutting unit kW heat dissipation cost by over 30% compared with traditional air cooling. PUE stably ≤1.05 to drastically reduce data center operating costs and meet national mandatory green data center PUE ≤1.3 requirements.
  • Internet Enterprise Computing Power Centers: Suitable for business servers, database servers and cache server clusters of e-commerce, short video, gaming and social platforms. Seamless upgrade renovation of traditional air-cooled machine rooms without large-scale civil engineering reconstruction, raising single cabinet power from 5kW to 60kW and boosting machine room computing power density by over 10 times.
  • Financial Industry Data Centers: Adaptable to core trading systems, data backup and risk calculation scenarios of banks, securities and insurance institutions with high reliability and safety design supporting uninterrupted 7×24-hour stable operation without single-point faults, complying with high-level financial industry safety specifications.

7.4 Edge Computing & Distributed Computing Power Scenarios

  • 5G Core Network & Edge Computing Nodes: Suitable for operator 5G base stations and edge data centers with miniature silent design deployable in base station machine rooms and business halls without dedicated air conditioning, adapting to complex environments to deliver edge computing power support for 5G + industrial internet, smart transportation and smart cities.
  • Industrial Internet Edge Computing Platforms: Adaptable to industrial internet platforms, intelligent manufacturing systems and machine vision inspection scenarios in factory workshops and industrial parks with fully enclosed dustproof and moistureproof design adapting to harsh industrial environments. Deployable on-site in workshops to realize local data processing and reduce transmission latency.