Table of Contents
Toggle1. System Introduction
1.1 System Overview
The KITOZER in-row air conditioning system is a close-range cooling solution specially designed for high-density data centers and server rooms. Also known as aisle air conditioning system, it adopts horizontal air supply and direct heat source cooling mode. Installed between server cabinet rows and closely arranged with IT equipment, it realizes zero-distance precise cooling.
This system thoroughly solves the pain points of traditional computer room air conditioners, such as long-distance air supply, large cooling capacity loss and local hotspots. It improves cooling efficiency by more than 30% and optimizes the PUE below 1.3. It is the core equipment for modern data centers to achieve energy-saving and eco-friendly operation.
1.2 Working Principle
The KITOZER in-row air conditioning system applies hot and cold aisle isolation technology. Cold air is delivered horizontally from the cold aisle and directly into cabinets to cool IT equipment. Hot air exhausted by equipment returns to the air conditioning unit through the hot aisle to form a closed circulation.
EC variable frequency fans provide stable air pressure to overcome the air resistance of high-density cabinets and keep the temperature difference of equipment on each layer within the cabinet below 2°C. Equipped with high-efficiency compressors, internally threaded tube evaporators and precise control systems, the unit achieves constant temperature and humidity control (Temperature: ±0.5°C, Humidity: ±3%RH), complying with ASHRAE Class A3 high-temperature operating standards.
1.3 Design Concept
- Heat Source Following: Air conditioners are installed side by side with cabinets. Cooling units are close to heat sources to reduce cooling capacity transmission loss.
- On-demand Cooling: Independent row-level control dynamically adjusts cooling output according to cabinet power to avoid energy waste.
- High-density Adaptation: A single unit supports 10 to 15 high-density cabinets of 8kW, easily handling heat dissipation demands of cabinets over 10kW.
- Intelligent Management: Supports group control and remote monitoring. It real-timely monitors parameters including temperature, humidity, air pressure and energy consumption to enable predictive maintenance.

2. System Composition
The KITOZER in-row air conditioning system consists of the following core components:
| System Module | Main Components | Function Description |
|---|---|---|
| Refrigeration Cycle System | 1~2 Scroll Compressors, Internally Threaded Tube Evaporator, Condenser, Expansion Valve, Filter Drier, Refrigerant Piping | Delivers stable cooling capacity. Adopts R410A eco-friendly refrigerant with high cooling efficiency and environmental performance. |
| Air Handling System | 2~4 EC Variable Frequency Fans, G4 Grade Air Filter, Electric Heater, Electrode Humidifier, Air Volume Regulator | Provides air volume of 4500~10000m³/h, realizes constant temperature & humidity control and air purification to guarantee the operating environment of IT equipment. |
| Control System | Microprocessor Controller, Color Touch Screen, 3~5 Temperature & Humidity Sensors, Pressure Sensors, Water Flow Switch | Precisely controls temperature (20-30°C) and humidity (40-60%RH). Supports local/remote operation, fault alarm and data recording. |
| Structural System | Standard Cabinets (300/600mm width), Hot & Cold Aisle Containment Components, Waterproof Base, Access Door, Mounting Bracket | Compatible with various cabinet layouts, front maintenance accessible. IP20 protection class with strong load-bearing capacity. |
| Auxiliary System | Water Leakage Detector, Fire Linkage Interface, Remote Communication Module (RS485/Modbus/IP), Group Control Software | Ensures safety protection and intelligent monitoring, enables coordinated operation of multiple units and improves system reliability. |
| Power Supply System | Dual Power Input, ATS Automatic Transfer Switch, Overload Protection Device, Lightning Protection Module | Guarantees 24×365 non-stop operation with MTBF ≥ 80000 hours. |
3. System Classification
3.1 Classification by Cooling Method
| Category | Model Series | Core Features | Application Scenarios |
|---|---|---|---|
| Air-cooled Direct Expansion Type | K-ROW-A Series | Indoor and outdoor units are separated with flexible installation. No water system required. Cooling capacity: 15~40kW per unit. | Small and medium-sized data centers, computer rooms without dedicated chilled water systems. |
| Chilled Water Type | K-ROW-W Series | Connects to chilled water system (12-18°C). High sensible heat ratio (0.95). Cooling capacity: 25~60kW per unit. | Large-scale data centers, modular computer rooms, scenarios with high PUE optimization requirements. |
| Heat Pipe Type | K-ROW-H Series | Dual mode of free cooling and mechanical refrigeration, energy saving over 30%. Cooling capacity: 20~50kW per unit. | Data centers in cool climate areas, eco-friendly data centers and scenarios pursuing maximum energy efficiency. |
| Glycol Dual Cold Source Type | K-ROW-D Series | Dual backup of chilled water and glycol, supports free cooling in winter. Cooling capacity: 30~60kW per unit. | Mission-critical computer rooms with extremely high reliability requirements. |
3.2 Classification by Capacity
- Small In-row Air Conditioner: Cooling capacity 15~25kW, applicable for rows with 5~8 cabinets of 8kW.
- Medium In-row Air Conditioner: Cooling capacity 25~40kW, applicable for rows with 8~12 cabinets of 8kW.
- Large In-row Air Conditioner: Cooling capacity 40~60kW, applicable for rows with 12~15 cabinets of 8kW.
3.3 Classification by Control Mode
- Independent Control Type: Single unit operates independently, suitable for small computer rooms.
- Group Control & Linkage Type: Multiple units work in coordination with master-slave switchover, suitable for large-scale data centers.
- Intelligent IoT Type: Connects to DCIM system, supporting remote monitoring, data analysis and AI optimization.

4. System Configuration List (Brand: KITOZER)
4.1 Basic Configuration List
| No. | Equipment Name | Model | Specification | Unit | Quantity | Remarks |
|---|---|---|---|---|---|---|
| Refrigeration Core Unit | ||||||
| 1 | In-row Air Conditioner Indoor Unit | K-ROW-W45 | Cooling capacity: 45kW, Sensible Heat Ratio: 0.95, Air volume: 10000m³/h | Set | 1 | Chilled water type, 300mm width |
| 2 | Scroll Compressor | ZR380KC-TFD-522 | EER: 3.2, R410A refrigerant | Set | 2 | Dual compressor redundant design |
| 3 | Internally Threaded Tube Evaporator | K-EVAP-45 | Heat exchange area: 12㎡, Hydrophilic film fins | Set | 1 | High-efficiency sine wave fin design |
| 4 | Motorized Two-way Valve | K-VLV-50 | DN50, Electric actuator | Piece | 1 | Proportional integral control |
| Air Handling Unit | ||||||
| 5 | EC Variable Frequency Fan | K-FAN-2500 | Air volume: 2500m³/h, Power: 0.8kW | Set | 4 | Four-fan redundant design |
| 6 | Air Filter | K-FIL-04 | G4 grade, Filtration efficiency: 90% | Piece | 2 | Washable and reusable |
| 7 | Electrode Humidifier | K-HUM-10 | Humidification capacity: 10kg/h, Automatic cleaning | Set | 1 | Anti-scaling design |
| 8 | Electric Heater | K-HEAT-6 | Heating power: 6kW, PTC ceramic | Set | 1 | Stepped control |
| Control & Monitoring Unit | ||||||
| 9 | Microprocessor Controller | K-CONTROL-9000 | 32-bit CPU, Color touch screen | Set | 1 | Supports Modbus communication |
| 10 | Temperature & Humidity Sensor | K-TH-100 | Accuracy: ±0.3°C / ±2%RH | Piece | 4 | 1 for cabinet air inlet and outlet respectively |
| 11 | Pressure Sensor | K-PRESS-01 | Measuring range: 0~500Pa | Piece | 2 | Air pressure monitoring for cold/hot aisle |
| 12 | Water Leakage Detector | K-WATER-02 | Sensing cable length: 10m | Set | 1 | Detection accuracy: 1mm |
| Structure & Auxiliary Unit | ||||||
| 13 | Air Conditioner Cabinet | K-CAB-300 | W300×D1100×H1980mm | Set | 1 | Full front maintenance design |
| 14 | Hot & Cold Aisle Containment Assembly | K-COVER-SET | Including top plate, end plate and door | Set | 1 | Flame-retardant ABS material |
| 15 | Waterproof Base | K-PAN-300 | Capacity: 10L, With drain port | Piece | 1 | Prevent condensed water leakage |
| 16 | Power Distribution Module | K-PDM-32 | 32A, Dual power input | Set | 1 | ATS automatic switchover |
| Communication & Management Unit | ||||||
| 17 | Communication Module | K-COM-485 | RS485 to Ethernet converter | Piece | 1 | Connect to DCIM system |
| 18 | Group Control Software | K-GMS-2026 | Supports linkage of 16 units | Set | 1 | Equipped with monitoring interface |
| 19 | Remote Monitoring Terminal | K-RMT-01 | 7-inch touch screen, Wireless connection | Set | 1 | Optional |
4.2 Optional Configuration List
| No. | Equipment Name | Model | Specification | Unit | Quantity | Application Scenarios |
|---|---|---|---|---|---|---|
| 1 | Refrigerant Pump Free Cooling Module | K-FP-45 | Energy saving over 30%, Operating temperature: -10°C~25°C | Set | 1 | Data centers in cool climate areas |
| 2 | Air Distribution Optimizer | K-AIR-OPT | Intelligently adjust air supply angle | Set | 1 | High-density cabinet areas |
| 3 | Harmful Gas Monitoring Module | K-GAS-03 | Monitors CO₂ and VOC concentration | Set | 1 | Fully enclosed computer rooms |
| 4 | Battery Backup Unit | K-BBU-24 | 24V, Backup duration: 4 hours | Set | 1 | Data protection during power outage |
| 5 | Noise Reduction Device | K-SIL-05 | Noise reduction: 5dB(A) | Set | 1 | Noise-sensitive environments |

5. System Schematic Diagram
5.1 Schematic Diagram of Chilled Water Type In-row Air Conditioning System
Chilled Water Supply Pipe → Motorized Two-way Valve → Internally Threaded Tube Evaporator → Chilled Water Return Pipe
↓
Cold Aisle ← EC Variable Frequency Fan ← Air Filter ← Mixed Air ← Return Air from Hot Aisle
↓ ↑
IT Equipment Cabinet → Heat Dissipation → Hot Aisle → Air Conditioner Air Return
↓
Electrode Humidifier → Steam → Mixed Air
Electric Heater → Heat → Mixed Air
↓
Microprocessor Controller ← Temperature & Humidity Sensor ← Pressure Sensor ← Water Leakage Detector
↓
DCIM System ← Communication Module ← Group Control Software
5.2 Air Distribution Schematic
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│ Server │ │ KITOZER │ │ Server │
│ Cabinet │ ←→ │ In-row AC │ ←→ │ Cabinet │
│ (Cold Aisle)│ │(Horizontal │ │(Hot Aisle) │
│ (Cold Air In)│ │ Air Supply) │ │ (Hot Air Out)│
└─────────────┘ └─────────────┘ └─────────────┘
↑ │ ↑
└───────────────────┴───────────────────┘
Closed Circulation
5.3 Group Control System Architecture
DCIM Central Monitoring ↔ K-GMS Group Control Server ↔ In-row AC 1 ↔ In-row AC 2 ↔ … ↔ In-row AC N
↓
Data Storage ↔ Data Analysis ↔ AI Optimization Engine
↓
Alarm Management ↔ Remote Maintenance ↔ Report Generation

6. Product Technical Parameters
6.1 Core Parameters of K-ROW Series In-row Air Conditioners
| Parameter Item | K-ROW-W30 | K-ROW-W45 | K-ROW-A35 | K-ROW-H40 |
|---|---|---|---|---|
| Cooling Performance | ||||
| Cooling Capacity | 30kW | 45kW | 35kW | 40kW |
| Sensible Heat Ratio | 0.95 | 0.95 | 0.93 | 0.94 |
| Air Volume | 7000m³/h | 10000m³/h | 8000m³/h | 9000m³/h |
| Air Supply Pressure | 500Pa | 600Pa | 550Pa | 580Pa |
| Physical Characteristics | ||||
| Dimension (W×D×H) | 300×1100×1980mm | 300×1100×1980mm | 600×1100×1980mm | 300×1100×1980mm |
| Weight | 350kg | 420kg | 480kg | 400kg |
| Maintenance Access | Full front maintenance | Full front maintenance | Full front maintenance | Full front maintenance |
| Electrical Parameters | ||||
| Power Supply | 380V/3N/50Hz | 380V/3N/50Hz | 380V/3N/50Hz | 380V/3N/50Hz |
| Rated Power | 8.5kW | 12kW | 10.5kW | 9kW |
| Fan Power | 2.4kW | 3.2kW | 2.8kW | 3.0kW |
| Control Accuracy | ||||
| Temperature Control | ±0.5°C | ±0.5°C | ±0.5°C | ±0.5°C |
| Humidity Control | ±3%RH | ±3%RH | ±3%RH | ±3%RH |
| Operating Temperature Range | 18-32°C | 18-32°C | 18-32°C | 18-32°C |
| Operating Humidity Range | 30-70%RH | 30-70%RH | 30-70%RH | 30-70%RH |
| Environmental Adaptability | ||||
| Ambient Temperature | -10~45°C | -10~45°C | -10~45°C | -20~45°C |
| Protection Class | IP20 | IP20 | IP20 | IP20 |
| Noise Level | ≤65dB(A) | ≤68dB(A) | ≤66dB(A) | ≤67dB(A) |
6.2 Technical Parameters of Core Components
| Component Name | Technical Parameters | Advantages |
|---|---|---|
| Scroll Compressor | EER ≥ 3.2, IP54 protection, Soft start supported | Stable operation, long service life and low noise |
| Internally Threaded Tube Evaporator | Heat exchange efficiency increased by 15%, Hydrophilic film fins | Anti-frosting, long maintenance cycle |
| EC Variable Frequency Fan | Efficiency: 85%, Speed adjustment range: 20-100% | Energy saving over 40%, stable air pressure |
| Microprocessor Controller | 32-bit CPU, 1-second data acquisition, 1000 fault records | Precise control and rapid fault diagnosis |
| Motorized Two-way Valve | Response time < 2s, Control accuracy ±1% | Accurate cooling capacity regulation and energy saving |

7. Product Application Scope
7.1 Core Application Scenarios
- High-density Data Centers: Scenarios with cabinet power over 8kW where traditional air conditioners fail to meet heat dissipation demands.
- Modular Data Centers: Micro-modules and container data centers requiring rapid deployment.
- Financial Industry Computer Rooms: Core computer rooms of banks, securities and insurance industries with strict requirements on equipment stability.
- Cloud Computing Data Centers: Large cloud service providers requiring large-scale deployment and high reliability.
- AI Computing Centers: GPU server clusters with high heat density demanding precise cooling.
- Edge Data Centers: Small-scale data centers near user terminals with limited space and high cooling efficiency requirements.
- Retrofit & Upgrade Computer Rooms: Existing computer rooms with insufficient cooling capacity needing additional cooling equipment.
- Medical Industry Computer Rooms: Hospital PACS and electronic medical record systems requiring 24×365 stable operation.
- Research Institute Computer Rooms: Supercomputer centers and laboratories requiring high-precision temperature and humidity control.
- Enterprise-level Data Centers: Private clouds of large enterprises pursuing lower operating costs and higher energy efficiency.
7.2 Applicable Cabinet Configuration
| Cabinet Power | Recommended Model | Compatible Cabinet Quantity | Application Description |
|---|---|---|---|
| 5-8kW | K-ROW-W30 | 8-10 | Small and medium enterprise computer rooms, standard density |
| 8-12kW | K-ROW-W45 | 10-12 | Large enterprises, high-density computing |
| 12-15kW | K-ROW-W60 | 12-15 | Cloud computing, AI training, supercomputing centers |
8. Product Advantages
8.1 High Efficiency & Energy Saving
- Minimize cooling loss: Horizontal air supply distance less than 2m, cooling loss reduced by 60%, energy efficiency improved by over 30%.
- On-demand cooling: EC variable frequency fan plus proportional integral control dynamically adjusts cooling capacity according to IT load, saving over 40% energy.
- Compatible with free cooling: Supports refrigerant pump free cooling, compressors can be shut down in winter to save over 50% energy.
- Excellent PUE optimization: System PUE can be optimized below 1.3, much better than traditional computer room air conditioners (PUE: 1.8-2.2).
8.2 Superior Cooling Performance
- Eliminate local hotspots: Direct cooling for heat sources keeps internal cabinet temperature difference below 2°C, completely solving overheating problems of remote cabinets.
- Precise constant temperature and humidity: Temperature control ±0.5°C, humidity control ±3%RH, meeting strict operating requirements of IT equipment.
- High sensible heat ratio design: Sensible heat ratio up to 0.95, matching the 95% sensible heat dissipation characteristic of servers and avoiding condensed water generation.
- Large air volume and high air pressure: Air volume up to 10000m³/h and air pressure up to 600Pa overcome air resistance of high-density cabinets to ensure cooling effect.
8.3 High Reliability
- Redundant design: Dual compressors and four fans with master-slave switchover, MTBF ≥ 80000 hours.
- Intelligent monitoring: Real-time full-parameter monitoring, fault early warning and automatic protection reduce downtime risks by over 70%.
- Strong environmental adaptability: Compliant with ASHRAE A3 high-temperature standard (45°C), adaptable to harsh working conditions.
- Full front maintenance: No side space required for maintenance, saving computer room space.
8.4 Flexible Deployment
- Modular design: Standard width of 300mm/600mm, compatible with various cabinet layouts for rapid deployment.
- Seamless integration: Compatible with hot & cold aisle containment systems, applicable for new and renovated computer rooms.
- Remote management: Connectable to DCIM system to realize unattended operation and cut O&M costs by over 50%.
- Convenient capacity expansion: Supports row-level expansion to increase cooling capacity on demand and protect initial investment.
9. Bidding Specification Parameters
9.1 Core Technical Parameters (* Mandatory Items)
| No. | Technical Parameter | Requirement Standard | Remarks |
|---|---|---|---|
| 1 | *Product Type | In-row air conditioner, chilled water type | Not room-type air conditioner |
| 2 | *Cooling Capacity | ≥45kW (Water supply:15°C, Water return:23°C, Return air:37°C) | For high-density scenarios |
| 3 | *Sensible Heat Ratio | ≥0.95 | Match server heat dissipation characteristics |
| 4 | *Air Volume | ≥10000m³/h | Overcome cabinet air resistance |
| 5 | *Air Supply Mode | Horizontal air supply towards cold aisle | Not downflow or upflow |
| 6 | *Fan Type | EC variable frequency fan, quantity ≥4 units | Redundant design & energy saving |
| 7 | *Control Accuracy | Temperature ±0.5°C, Humidity ±3%RH | Precise control requirement |
| 8 | *Dimension | Width: 300mm, Depth ≤1100mm, Height ≤1980mm | Fit standard cabinets |
| 9 | *Maintenance Mode | Full front maintenance, no side space required | Computer room space optimization |
| 10 | *Compressor Configuration | Dual scroll compressors with master-slave switchover | Redundant design for high reliability |
| 11 | *Protection Class | ≥IP20 | Computer room environmental adaptability |
| 12 | *Noise Level | ≤68dB(A) | Computer room environmental requirement |
| 13 | *Communication Interface | Support RS485/Modbus, connectable to DCIM system | Intelligent management requirement |
| 14 | *Redundant Design | N+1 redundancy for fans and compressors | High reliability requirement |
| 15 | *Ambient Temperature | -10°C ~ 45°C | Adapt to extreme environments |
9.2 Commercial & Service Parameters
| No. | Parameter Category | Requirement Standard |
|---|---|---|
| 1 | Brand | Original KITOZER product with official authorization certificate |
| 2 | Qualification Certification | ISO9001, ISO14001 and 3C certification |
| 3 | Warranty Period | ≥3 years, covering core components including compressors and fans |
| 4 | Service Response | 7×24 technical support, on-site service within 4 hours |
| 5 | Spare Parts Support | Local spare parts warehouse, spare parts available within 24 hours |
| 6 | Installation & Commissioning | Installation and commissioning by original engineers, professional training provided |
| 7 | Energy Efficiency Certification | Class 1 energy efficiency certification, PUE ≤1.3 |
| 8 | Compatibility | Compatible with mainstream DCIM systems and API docking supported |
9.3 Performance Test Requirements
- Provide third-party official test reports on cooling capacity, air volume and energy consumption.
- Provide cooling performance test data under 37°C return air temperature.
- Provide performance test report of EC fan variable frequency control.
- Provide linkage performance test report of group control system.
10. Product Solutions
10.1 High-density Data Center Solution
10.1.1 Solution Overview
For high-density data centers with single cabinet power over 10kW, adopt KITOZER K-ROW-W45 chilled water type in-row air conditioner. Apply N+1 redundant configuration (1 main unit + 1 standby unit) for each row, cooperating with hot & cold aisle containment system to build eco-friendly data centers with PUE ≤1.3.
10.1.2 System Configuration
- Refrigeration System: K-ROW-W45 in-row air conditioner, 2 units per row (1 main, 1 standby)
- Air Distribution: Cold aisle containment, horizontal air supply, face-to-face cabinet arrangement
- Control System: K-GMS group control software, connected to DCIM system
- Redundant Design: N+1 redundancy for fans and compressors, dual water supply for chilled water system
- Monitoring System: Real-time monitoring of temperature, humidity, air pressure, water leakage and energy consumption
10.1.3 Solution Advantages
- Completely eliminate local hotspots with cabinet internal temperature difference below 2°C.
- Cooling efficiency increased by 38%, saving millions of electricity fees annually.
- Applicable for high-density scenarios such as AI training and cloud computing, supporting single cabinet power up to 15kW.
- Modular design allows phased construction to reduce initial investment.
- Intelligent group control realizes load balancing and extends service life of equipment.
10.2 Computer Room Retrofit & Upgrade Solution
10.2.1 Solution Overview
For renovated projects with insufficient cooling capacity and local hotspots in existing computer rooms, deploy KITOZER K-ROW-A35 air-cooled direct expansion in-row air conditioners. No modification on original air conditioning system is needed. Units can be directly installed between cabinet rows to rapidly improve cooling capacity.
10.2.2 System Configuration
- Refrigeration System: K-ROW-A35 air-cooled in-row air conditioner, configured according to cabinet power
- Air Distribution Optimization: Partial cold aisle containment, coordinated operation with original air conditioning system
- Control Integration: Connect to existing monitoring system for unified management
- Capacity Expansion Design: Reserved expansion interface for future cooling capacity upgrade
- Energy Saving Optimization: EC variable frequency fan adjusts operation according to actual load
10.2.3 Solution Advantages
- Short construction period without interrupting operation of existing equipment.
- No modification on original air conditioning system, low investment cost.
- Precise cooling solves local hotspot problems effectively.
- Cooperate with original system to improve overall cooling efficiency.
- Support phased investment to relieve financial pressure.
10.3 Modular Data Center Solution
10.3.1 Solution Overview
For micro-modules and container data centers, adopt KITOZER K-ROW-H40 heat pipe type in-row air conditioner combined with free cooling technology to achieve maximum energy saving, with PUE reduced below 1.2.
10.3.2 System Configuration
- Refrigeration System: K-ROW-H40 heat pipe type in-row air conditioner, dual mode of free cooling and mechanical refrigeration
- Integrated Design: Integrated with cabinets, power distribution and monitoring systems
- Rapid Deployment: Factory prefabrication, on-site installation completed within 24 hours
- Intelligent Management: Remote monitoring and AI operation parameter optimization supported
- Eco-friendly & Energy Saving: Free cooling ratio over 80% in winter, greatly reducing energy consumption
10.3.3 Solution Advantages
- Prefabricated design boosts deployment efficiency by 80%.
- Free cooling technology saves over 50% energy.
- Integrated structure reduces on-site construction work.
- Intelligent O&M cuts labor costs.
- High reliability meets Tier3+ data center standards.
11. Application Cases
11.1 Case 1: Cloud Computing Data Center (High-density Scenario)
Project Profile
- Project Name: Alibaba Cloud South China Data Center
- Location: Shenzhen, Guangdong
- Cabinet Quantity: 200 units, Single cabinet power: 12kW
- Cooling Demand: Eliminate local hotspots and reduce PUE
- Implementation Time: 2025
Solution
- Deploy 20 sets of K-ROW-W45 chilled water type in-row air conditioners, 2 units per row (1 main, 1 standby)
- Adopt cold aisle containment and horizontal air supply with face-to-face cabinet layout
- Connect to Alibaba Cloud DCIM system for intelligent group control and AI optimization
- Dual water supply for chilled water system ensures uninterrupted cooling
Implementation Effect
- PUE decreased from 1.8 to 1.28, saving 12 million RMB on electricity fees annually.
- Cabinet internal temperature difference below 2°C, local hotspots completely eliminated.
- Equipment failure rate reduced by 35%, extending service life of servers.
- Support single cabinet power up to 15kW to meet future expansion demands.
- Obtained Uptime Tier3+ certification and upgraded data center level.
11.2 Case 2: Financial Institution Computer Room Retrofit Project (Retrofit Scenario)
Project Profile
- Project Name: China Merchants Bank Credit Card Center Computer Room Retrofit
- Location: Pudong, Shanghai
- Existing Problems: Local hotspots and frequent server overheating alarms
- Retrofit Requirement: Solve problems rapidly without affecting existing business
- Implementation Time: 2024
Solution
- Deploy 8 sets of K-ROW-A35 air-cooled direct expansion in-row air conditioners
- Partial cold aisle containment, coordinated operation with original air conditioning system
- Connect to original monitoring system for unified management
- Automatically switch to energy-saving mode during low load at night
Implementation Effect
- Temperature of local hotspots dropped from 38°C to 24°C, server overheating alarms eliminated.
- Retrofit completed without shutdown to ensure business continuity.
- Cooling efficiency increased by 40%, saving 1.8 million RMB on electricity fees annually.
- Total retrofit period only 15 days with quick results.
- Seamless integration with original system for convenient management.
11.3 Case 3: AI Computing Center (Ultra-high Density Scenario)
Project Profile
- Project Name: AI Training Center of a Technology Company
- Location: Zhongguancun, Beijing
- Cabinet Configuration: GPU servers, Single cabinet power: 15kW
- Cooling Challenge: Traditional air conditioners cannot meet heat dissipation requirements
- Implementation Time: 2025
Solution
- Deploy K-ROW-W60 high-capacity in-row air conditioners, 2 units per row (1 main, 1 standby)
- Full cold aisle containment equipped with KITOZER air distribution optimizer
- Dual chilled water system ensures continuous cooling
- Intelligent group control system real-timely monitors cabinet temperature and dynamically adjusts cooling capacity
Implementation Effect
- Cabinet temperature stably maintained at 22±0.5°C to ensure stable operation of GPU devices.
- Support 15kW high power per cabinet to meet AI training demands.
- PUE optimized to 1.25, reaching international advanced level.
- Equipment operation stability improved, AI training task duration shortened by 12%.
- Remarkable energy saving effect, annual carbon emission reduction equivalent to planting 1000 trees.
12. System Installation & Maintenance
12.1 Installation Requirements
- Site Preparation
- Ground flatness: ≤±2mm/m
- Load-bearing capacity: ≥800kg/㎡
- Installation space: Aisle width ≥300mm, Front maintenance space ≥800mm
- Environmental requirement: Dust-free, non-corrosive gas, ambient temperature: 0-40°C
- Installation Process Foundation positioning → Air conditioner placement → Piping connection → Electrical wiring → Air containment → System commissioning → Operation test
- Piping Requirements
- Chilled water pipe: DN50, Insulation thickness ≥20mm, Rubber & plastic insulation material
- Drain pipe: DN25, Gradient ≥1% to prevent water accumulation
- Electrical cable: Flame-retardant cable complying with computer room fire protection standards
12.2 Maintenance Schedule
| Maintenance Cycle | Maintenance Content | Requirement |
|---|---|---|
| Daily | Operating status inspection | Automatic monitoring by monitoring system, alarm for abnormalities |
| Weekly | Filter cleaning | Clean or replace filters to guarantee air volume |
| Monthly | Temperature & humidity calibration | Calibrate sensors to ensure control accuracy |
| Quarterly | Fan inspection | Check fan operation and remove dust |
| Semi-annually | Compressor maintenance | Inspect compressor operating parameters and lubrication system |
| Annually | Comprehensive maintenance | System performance test, fault troubleshooting and maintenance record keeping |
12.3 Troubleshooting for Common Faults
| Fault Phenomenon | Possible Causes | Solutions |
|---|---|---|
| Insufficient cooling capacity | Clogged filter, low fan speed, refrigerant leakage | Clean filter, inspect fan, detect leakage and refill refrigerant |
| Large temperature & humidity fluctuation | Sensor failure, incorrect control parameters | Calibrate sensors and reset parameters |
| Abnormal fan operation | Motor failure, loose belt, foreign blockage | Replace motor, adjust belt and clear foreign matters |
| Water leakage alarm | Clogged drain pipe, full water tray | Dredge drain pipe and inspect drainage system |
| Communication failure | Circuit fault, module damage | Inspect circuit and replace communication module |
13. Search Keywords, SEO & Tags
13.1 Core Search Keywords
KITOZER in-row air conditioner, computer room in-row air conditioner, aisle air conditioner, high-density data center air conditioner, chilled water in-row air conditioner, air-cooled in-row air conditioner, heat pipe in-row air conditioner, computer room cooling solution, data center PUE optimization, computer room local hotspot solution, modular data center air conditioner, computer room retrofit air conditioning solution, eco-friendly data center cooling, precise cooling system, horizontal air supply air conditioner
13.2 SEO Optimization Keywords
Computer room in-row air conditioning system, KITOZER aisle air conditioner, data center in-row cooling, high-density computer room air conditioner, energy-saving in-row air conditioner, intelligent in-row air conditioner, in-row air conditioner bidding parameters, in-row air conditioner technical parameters, in-row air conditioner application cases, in-row air conditioning solution, computer room air conditioner retrofit, data center cooling upgrade, cold aisle air conditioning system, hot aisle containment air conditioner
13.3 Tags
#KITOZER #InRowAirConditioner #AisleAirConditioner #ComputerRoomAirConditioner #DataCenterCooling #HighDensityCooling #EnergySavingAirConditioner #SmartAirConditioner #ChilledWaterAirConditioner #AirCooledAirConditioner #HeatPipeAirConditioner #ComputerRoomRetrofit #PUEOptimization #PreciseCooling #HorizontalAirSupply #ColdAisleContainment #ModularDataCenter #AIDataCenter #CloudComputingCooling