KITOZER Integrated Cabinet Solution for Computer Rooms

Table of Contents

1. System Introduction

The KITOZER computer room cabinet system is a complete solution integrating intelligent all-in-one cabinets, modular hot and cold aisles, intelligent liquid cooling cabinets, standard server cabinets, standard network cabinets, PDU power distribution units and cabinet accessories. It provides a safe, reliable, energy-efficient and intelligently managed physical bearing platform for data centers, computer rooms and IT infrastructure.

Combining modern data center design concepts and cutting-edge technologies, the system integrates power supply & distribution, cooling, monitoring, cabling and other infrastructure into standardized cabinet units. It supports independent single cabinet deployment, multi-cabinet cluster deployment and modular expansion, meeting diverse demands from miniature computer rooms to large-scale data centers, and realizing high-density deployment, refined management and energy-saving operation of IT equipment.

Core Design Concepts

  1. Modular Architecture: Adopt standardized modular design to support rapid deployment and flexible expansion, reducing construction and operation & maintenance costs.
  2. Intelligent Management & Control: Built-in intelligent monitoring system to realize real-time monitoring of environmental parameters, remote control and fault early warning.
  3. High Efficiency & Energy Saving: Optimize airflow organization and reduce PUE via hot-cold aisle isolation, intelligent liquid cooling and other technologies to achieve low-carbon and eco-friendly operation.
  4. Safety & Reliability: Equipped with multiple protection mechanisms to ensure stable operation and extend service life of IT equipment.
  5. Full Lifecycle Management: Provide full-process support from design, deployment, operation & maintenance to upgrade, and improve asset utilization.
kitozer data center rack solution 1 (10)

2. System Composition

The KITOZER computer room cabinet system consists of seven core components. All components work collaboratively to form a complete physical infrastructure solution.

System ComponentCore FunctionsKey Parts
Intelligent All-in-One CabinetFully enclosed IT cabinet integrating power supply, cooling, monitoring and cabling, providing a complete operating environment for IT devicesCabinet body, precision air conditioner, UPS power supply, intelligent monitoring module, fire fighting components, cabling system
Modular Hot & Cold AisleIsolate hot and cold airflow, optimize computer room airflow organization, improve cooling efficiency and reduce energy consumptionEnclosed aisle frame, tempered glass door, blanking panel, airflow deflector, lighting system, access control system
Intelligent Liquid Cooling CabinetDesigned for high-density computing devices. Adopt liquid cooling technology to solve heat dissipation problems of high-power equipment and support ultra-high power density deployment per cabinetLiquid cooling cabinet body, cold plate / immersion liquid cooling system, CDU cooling distribution unit, pipeline system, leakage detection system
Standard Server CabinetProvide standard installation space for general servers and storage devices with excellent ventilation, heat dissipation and cable management performanceStandard 19-inch cabinet frame, high-density mesh door, load-bearing tray, cable management trough
Standard Network CabinetSpecially designed for network equipment, optimize cable management and support high-density deployment of switches, routers and other network devicesNetwork cabinet frame, front & rear mesh doors, cable manager, fiber trough, earthing system
PDU Power Distribution UnitDeliver safe and reliable power distribution and management, support remote monitoring, intelligent switch control and power meteringInput module, output socket, intelligent monitoring module, lightning protection, overload protection
Cabinet AccessoriesAssist cabinet operation and improve convenience and safetyCable manager, cooling fan, door lock, blanking panel, shelf, guide rail, earthing copper bar, etc.

3. System Classification

3.1 Classification by Function Orientation

CategoryApplication ScenariosCore Features
Intelligent All-in-One CabinetMini data centers, edge computing nodes, branch office computer roomsHigh integration, rapid deployment, independent operation, intelligent management
Modular Hot & Cold Aisle Cabinet SystemSmall & medium-sized data centers, enterprise computer rooms, cloud computing centersHot-cold airflow isolation, energy saving & high efficiency, flexible expansion, centralized management
Intelligent Liquid Cooling CabinetHigh-density computing centers, AI training clusters, supercomputing centersStrong heat dissipation capacity (1500W/m²), low PUE (1.12), support ultra-high power density (30kW+)
Standard Server CabinetGeneral data centers, enterprise IT computer rooms, virtualization platformsStandard 19-inch design, good ventilation, load capacity ≥ 1500kg
Standard Network CabinetNetwork computer rooms, communication hubs, data center network zonesOptimized cable management, good ventilation & heat dissipation, compatible with various network devices

3.2 Classification by Deployment Scale

  1. Single Cabinet Solution: Applicable to miniature computer rooms and small branch offices. Single cabinet operates independently with all integrated infrastructures.
  2. Multi-Cabinet Cluster Solution: Applicable to small & medium-sized data centers and enterprise computer rooms. Multiple cabinets are connected in parallel to share part of infrastructure resources.
  3. Modular Data Center Solution: Applicable to large-scale data centers and cloud computing centers. Deployed by functional zones and support rapid capacity expansion.

3.3 Classification by Cooling Mode

  1. Air-Cooled Cabinet System: Adopt traditional air cooling technology with precision air conditioners and fans for heat dissipation. Suitable for scenarios with medium and low power density.
  2. Liquid-Cooled Cabinet System: Adopt cold plate liquid cooling or immersion liquid cooling technology. Suitable for high power density scenarios, with heat dissipation efficiency 5 times higher than air cooling.
  3. Hybrid Cooling Cabinet System: Combine advantages of air cooling and liquid cooling. Apply differentiated cooling schemes for devices in different areas to optimize energy consumption.
kitozer data center rack solution 1 (9)

4. System Configuration List (Brand: KITOZER)

4.1 Configuration List of Intelligent All-in-One Cabinet

No.Device NameModelQuantityRemarks
1Intelligent All-in-One Cabinet BodyKITOZER-IIC-42U1 Set600mm(W)×1200mm(D)×2200mm(H), 42U standard height, SPCC cold rolled steel, upright thickness 2.0mm, static load ≥ 1500kg, IP20
2Integrated Precision Air ConditionerKITOZER-PA-12.5kW1 SetIn-row air conditioner, cooling capacity 12.5kW, dual-side active air supply, intelligent temperature control, PUE reduced by over 15%
3UPS Power ModuleKITOZER-UPS-10kVA1 SetOnline double conversion, input/output 220V/380V, dual power input, backup time optional
4Intelligent Monitoring SystemKITOZER-IMS-011 SetIntegrated temperature & humidity, smoke, access control and video monitoring; support remote Web management and mobile APP real-time monitoring
5PDU Power Distribution UnitKITOZER-PDU-32A-16C2 Sets32A input, 16×10A C13 output, intelligent metering, remote monitoring, overload protection
6Fire Fighting SystemKITOZER-FS-011 SetHFC-227ea gas fire extinguishing, automatic detection, manual / automatic dual-mode activation
7Integrated Cabling SystemKITOZER-CA-011 SetFiber trough, copper cable ladder, cable manager; compatible with Cat.6/Cat.6A/Cat.7 and multi-mode / single-mode fiber
8Cabinet AccessoriesKITOZER-AC-011 SetBlanking panel, cable manager, cooling fan, door lock, guide rail, shelf, etc.

4.2 Configuration List of Modular Hot & Cold Aisle

No.Device NameModelQuantityRemarks
1Hot & Cold Aisle FrameKITOZER-HCC-6001 SetFor 600mm wide cabinets, aluminum alloy, height 2200mm, adjustable length
2Tempered Glass DoorKITOZER-GD-18002 PcsHeight 1800mm, transparent tempered glass with safety lock and anti-glare treatment
3Aisle Enclosed Top PanelKITOZER-CT-011 SetFlame-retardant thermal insulation material, sealed connection with cabinet top to reduce air leakage
4Blanking PanelKITOZER-BP-1U/2UQty. on demand1U/2U specification, for cabinet vacant positions to optimize airflow
5Airflow DeflectorKITOZER-AD-011 SetGuide cold air to equipment air inlet and improve cooling efficiency
6Aisle Lighting SystemKITOZER-CL-011 SetLED energy-saving light, human body induction control, auto on/off
7Aisle Access Control SystemKITOZER-AC-021 SetCard / password / fingerprint recognition, remote authorization support, access log recording
8Environmental Monitoring SensorKITOZER-ES-012 PcsTemperature, humidity and air pressure monitoring; real-time data upload to monitoring system

4.3 Configuration List of Intelligent Liquid Cooling Cabinet

No.Device NameModelQuantityRemarks
1Intelligent Liquid Cooling Cabinet BodyKITOZER-LC-42U1 Set600mm(W)×1200mm(D)×2200mm(H), 42U standard height, anti-corrosion coating, static load ≥ 2000kg, IP54
2Cold Plate Liquid Cooling SystemKITOZER-LCS-30kW1 SetSupport 30kW power density per cabinet; cold plate directly contacts heat source with high thermal conductivity
3CDU Cooling Distribution UnitKITOZER-CDU-50kW1 SetCoolant circulation control, real-time temperature/pressure/flow monitoring and intelligent adjustment
4Pipeline SystemKITOZER-PLS-011 SetStainless steel, quick connector, anti-leakage design, hot-swap support
5Leakage Detection SystemKITOZER-LDS-011 SetMulti-point sensors, real-time monitoring, leakage alarm and automatic valve cut-off
6PDU Power Distribution UnitKITOZER-PDU-63A-24C2 Sets63A input, 24×16A C19 output, intelligent metering, remote monitoring, overload protection
7Intelligent Monitoring SystemKITOZER-LMS-011 SetIntegrated liquid cooling system monitoring, environmental monitoring, remote control and fault early warning
8Cabinet AccessoriesKITOZER-LA-011 SetLiquid cooling dedicated guide rail, fixing bracket, sealing components, etc.

4.4 Configuration List of Standard Server Cabinet

No.Device NameModelQuantityRemarks
1Server Cabinet BodyKITOZER-SC-42U1 Set600mm(W)×1200mm(D)×2200mm(H), 42U standard height, SPCC cold rolled steel, upright thickness 2.0mm, static load ≥ 1500kg, IP20
2High-Density Mesh Front DoorKITOZER-FM-011 PcHex arc mesh, ventilation rate ≥ 70%, tempered glass observation window, mechanical lock
3Double-Opening Mesh Rear DoorKITOZER-BM-011 PcHex mesh, ventilation rate ≥ 75%, double-opening design for easy maintenance
4Three-Section Side DoorKITOZER-SM-012 PcsDetachable design for easy installation and maintenance with lock
5PDU Power Distribution UnitKITOZER-PDU-32A-16C2 Sets32A input, 16×10A C13 output, intelligent metering, remote monitoring, overload protection
6Load-Bearing TrayKITOZER-TP-012 Pcs2.0mm steel plate, load capacity ≥ 500kg, height adjustable
7Cabinet AccessoriesKITOZER-SA-011 SetCable manager, blanking panel, guide rail, door lock, earthing copper bar, etc.
kitozer data center rack solution 1 (7)

4.5 Configuration List of Standard Network Cabinet

No.Device NameModelQuantityRemarks
1Network Cabinet BodyKITOZER-NC-42U1 Set600mm(W)×800mm(D)×2200mm(H), 42U standard height, SPCC cold rolled steel, upright thickness 1.5mm, static load ≥ 1000kg, IP20
2High-Density Mesh Front DoorKITOZER-FM-021 PcHex arc mesh, ventilation rate ≥ 70%, tempered glass observation window, mechanical lock
3Double-Opening Mesh Rear DoorKITOZER-BM-021 PcHex mesh, ventilation rate ≥ 75%, double-opening design for easy maintenance
4Fiber TroughKITOZER-FCS-011 SetFlame-retardant material, capacity ≥ 48 cores, compatible with fiber splice box
5Cable ManagerKITOZER-PM-014 Sets19-inch standard mounting, compatible with Cat.6/Cat.6A/Cat.7 cables, port capacity ≥ 24 ports
6PDU Power Distribution UnitKITOZER-PDU-32A-12C2 Sets32A input, 12×10A C13 output, intelligent metering, remote monitoring, overload protection
7Cabinet AccessoriesKITOZER-NA-011 SetBlanking panel, guide rail, door lock, earthing copper bar, etc.

4.6 Configuration List of PDU Power Distribution Unit

No.Device NameModelQuantityRemarks
1Basic PDUKITOZER-PDU-16A-8CQty. on demand16A input, 8×10A C13 output, overload protection, lightning protection
2Intelligent PDUKITOZER-PDU-32A-16CQty. on demand32A input, 16×10A C13 output, intelligent metering, remote monitoring, overload protection, Web management support
3High-Density PDUKITOZER-PDU-63A-24CQty. on demand63A input, 24×16A C19 output, intelligent metering, remote monitoring, overload protection, for high-density equipment
4Custom PDUKITOZER-PDU-CUSTOMQty. on demandCustom output port type, quantity and power level per customer requirements

4.7 Configuration List of Cabinet Accessories

No.Device NameModelQuantityRemarks
1Cable ManagerKITOZER-PM-01/02Qty. on demand1U/2U, 19-inch standard, compatible with Cat.6/Cat.6A/Cat.7 cables, port capacity ≥ 24 ports
2Cooling FanKITOZER-FAN-01Qty. on demand120mm×120mm, 1U height, speed 2000rpm, air volume ≥ 300CFM, noise ≤ 45dB
3Door LockKITOZER-LOCK-01Qty. on demandMoon handle cabinet lock, master key design, excellent anti-theft performance
4Blanking PanelKITOZER-BP-1U/2UQty. on demand1U/2U standard size, for cabinet vacant positions to optimize airflow
5ShelfKITOZER-SHELF-01Qty. on demandLoad capacity ≥ 50kg, height adjustable, for non-rack-mounted equipment
6Guide RailKITOZER-RAIL-01Qty. on demand19-inch standard, load capacity ≥ 45kg, sliding installation for servers / network devices
7Earthing Copper BarKITOZER-GP-01Qty. on demandCopper material, thickness ≥ 2mm, width ≥ 30mm, reliable earthing protection
8Fiber TroughKITOZER-FCS-01Qty. on demandFlame-retardant material, capacity ≥ 48 cores, compatible with fiber splice box
kitozer data center rack solution 1 (5)

5. System Schematic Diagram

5.1 Schematic of Intelligent All-in-One Cabinet System

┌─────────────────────────────────────────────────────────┐
│ KITOZER Intelligent All-in-One Cabinet │
│ ┌─────────────┐ ┌─────────────┐ ┌─────────────┐ │
│ │ Power System│ │Cooling System│ │Monitor System│ │
│ │ (UPS+PDU) │ │(Precision AC)│ │Temp/Hum/Smoke│ │
│ └─────────────┘ └─────────────┘ └─────────────┘ │
│ │ │ │ │
│ ▼ ▼ ▼ │
│ ┌─────────────┐ ┌─────────────┐ ┌─────────────┐ │
│ │Fire System │ │Cabling System│ │Access Control│ │
│ │(Gas Extinguish)││(Fiber/Cable) │ │(Card/Password)│ │
│ └─────────────┘ └─────────────┘ └─────────────┘ │
│ │ │ │ │
│ └──────────────┼──────────────┘ │
│ ▼ │
│ ┌─────────────────────────────────────────────┐ │
│ │ IT Equipment Area │ │
│ │(Server/Storage/Network, High-Density 42U) │ │
│ └─────────────────────────────────────────────┘ │
└─────────────────────────────────────────────────────────┘
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│ Power Input │ │Coolant Input│ │Network Access│
└─────────────┘ └─────────────┘ └─────────────┘

5.2 Schematic of Modular Hot & Cold Aisle System

┌─────────────────────────────────────────────────────────┐
│ KITOZER Modular Hot & Cold Aisle │
│ ┌─────────────┐ ┌─────────────┐ ┌─────────────┐ │
│ │ Cold Aisle │ │ Hot Aisle │ │Enclosed Frame│ │
│ │(Cold Air In)│ │(Hot Air Out)│ │(Aluminum) │ │
│ └─────────────┘ └─────────────┘ └─────────────┘ │
│ │ │ │ │
│ ▼ ▼ ▼ │
│ ┌─────────────┐ ┌─────────────┐ ┌─────────────┐ │
│ │Tempered Glass│ │Blanking Panel│ │Airflow Deflector│ │
│ │(Trans/Anti-Glare)││(1U/2U) │ │(Optimize Airflow)│ │
│ └─────────────┘ └─────────────┘ └─────────────┘ │
│ │ │ │ │
│ └──────────────┼──────────────┘ │
│ ▼ │
│ ┌─────────────────────────────────────────────┐ │
│ │ Cabinet Cluster Area │ │
│ │(Server Cabinet+Network Cabinet+PDU+Accessories) │
│ └─────────────────────────────────────────────┘ │
└─────────────────────────────────────────────────────────┘
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│Precision AC │ │Lighting System│ │Access Control│
└─────────────┘ └─────────────┘ └─────────────┘

5.3 Schematic of Intelligent Liquid Cooling Cabinet System

┌─────────────────────────────────────────────────────────┐
│ KITOZER Intelligent Liquid Cooling Cabinet│
│ ┌─────────────┐ ┌─────────────┐ ┌─────────────┐ │
│ │Liquid Cooling│ │CDU Unit │ │Leakage Detect│ │
│ │(Cold Plate/Immersion)││(Cycle Control)││(Multi-Sensor)│
│ └─────────────┘ └─────────────┘ └─────────────┘ │
│ │ │ │ │
│ ▼ ▼ ▼ │
│ ┌─────────────┐ ┌─────────────┐ ┌─────────────┐ │
│ │Pipeline System│ │Power System│ │Monitor System│ │
│ │(Stainless Steel)││(UPS+PDU) │ │(Temp/Pressure)│ │
│ └─────────────┘ └─────────────┘ └─────────────┘ │
│ │ │ │ │
│ └──────────────┼──────────────┘ │
│ ▼ │
│ ┌─────────────────────────────────────────────┐ │
│ │ High-Density IT Equipment Area │ │
│ │(AI Server/Supercomputing Node, 30kW+ Density) │ │
│ └─────────────────────────────────────────────┘ │
└─────────────────────────────────────────────────────────┘
│ │ │
▼ ▼ ▼
┌─────────────┐ ┌─────────────┐ ┌─────────────┐
│ Power Input │ │Coolant Input│ │Network Access│
└─────────────┘ └─────────────┘ └─────────────┘

kitozer data center rack solution 1 (3)

6. Product Technical Parameters

6.1 Technical Parameters of Intelligent All-in-One Cabinet

Parameter ItemTechnical Specification
Dimension600mm(W)×1200mm(D)×2200mm(H), 42U standard height
MaterialHigh-quality SPCC cold rolled steel; upright thickness 2.0mm, other parts 1.2mm
Surface TreatmentDegreasing, pickling, phosphating and electrostatic powder coating with excellent anti-corrosion performance
Load CapacityStatic load ≥ 1500kg, dynamic load ≥ 1000kg
Ingress ProtectionIP20; third-party test report available
Cooling SystemIntegrated 12.5kW precision air conditioner, dual-side active air supply; PUE reduced by over 15%
Power System10kVA UPS, dual power input, intelligent PDU distribution
Monitoring SystemTemperature & humidity (0-50℃ / 10-90%RH), smoke, access control and video monitoring; remote Web management supported
Fire Fighting SystemHFC-227ea gas fire extinguishing, automatic detection, manual / automatic dual-mode activation
Deployment ModeIndependent single cabinet deployment, support multi-cabinet cluster connection

6.2 Technical Parameters of Modular Hot & Cold Aisle

Parameter ItemTechnical Specification
Compatible Cabinet600mm/800mm wide standard cabinet, 42U height
Frame MaterialAluminum alloy with anodized surface treatment and good corrosion resistance
Enclosure ComponentsTempered glass door (thickness ≥ 5mm), flame-retardant thermal insulation top panel (thickness ≥ 20mm)
Blanking Panel1U/2U, flame-retardant ABS material, ventilation rate ≤ 5%
Airflow OrganizationComplete hot-cold aisle isolation, air leakage rate ≤ 3%
Lighting SystemLED energy-saving lamp, power ≤ 10W, human body induction control
Access Control SystemCard / password / fingerprint recognition, remote authorization and access log recording supported
Environmental MonitoringTemperature & humidity (0-50℃ / 10-90%RH), air pressure monitoring; accuracy ±0.5℃ / ±3%RH
Deployment ModeSingle-row / double-row cabinet deployment, expandable to multi-row clusters

6.3 Technical Parameters of Intelligent Liquid Cooling Cabinet

Parameter ItemTechnical Specification
Dimension600mm(W)×1200mm(D)×2200mm(H), 42U standard height
MaterialHigh-quality SPCC cold rolled steel with anti-corrosion coating; upright thickness 2.0mm
Load CapacityStatic load ≥ 2000kg, for high-density equipment deployment
Ingress ProtectionIP54, dustproof and waterproof for computer room environment
Liquid Cooling SystemCold plate liquid cooling; heat dissipation capacity 1500W/m², 5 times higher than traditional air cooling
CDU UnitMax flow 50L/min, temperature control accuracy ±1℃, pressure monitoring range 0-1MPa
Pipeline SystemStainless steel, quick connector, anti-leakage design, hot-swap supported
Leakage DetectionMulti-point sensors, detection accuracy ≤ 0.1ml, response time ≤ 1s
Power System63A input, high-density PDU distribution, support 60kW power density
Monitoring SystemReal-time monitoring of liquid cooling system (temperature/pressure/flow) and environmental parameters; fault early warning supported

6.4 Technical Parameters of Standard Server Cabinet

Parameter ItemTechnical Specification
Dimension600mm(W)×1200mm(D)×2200mm(H), 42U standard height
MaterialHigh-quality SPCC cold rolled steel; upright 2.0mm, tray 2.0mm, other parts 1.2mm
Surface TreatmentDegreasing, pickling, phosphating and electrostatic powder coating with excellent anti-corrosion performance
Door & LockHex arc mesh front door (ventilation ≥70%), double-opening hex mesh rear door (ventilation ≥75%), three-section side door; moon handle cabinet lock
Load CapacityStatic load ≥ 1500kg, dynamic load ≥ 1000kg
Ingress ProtectionIP20; third-party test report available
Cable ManagementCable management space: 25-30mm (600mm width) or 123mm (800mm width) on both sides
Deployment ModeIndependent single cabinet deployment, support multi-cabinet cluster connection

6.5 Technical Parameters of Standard Network Cabinet

Parameter ItemTechnical Specification
Dimension600mm(W)×800mm(D)×2200mm(H), 42U standard height
MaterialHigh-quality SPCC cold rolled steel; upright 1.5mm, other parts 1.2mm
Surface TreatmentDegreasing, pickling, phosphating and electrostatic powder coating with excellent anti-corrosion performance
Door & LockHex arc mesh front door (ventilation ≥70%), double-opening hex mesh rear door (ventilation ≥75%); moon handle cabinet lock
Load CapacityStatic load ≥ 1000kg, dynamic load ≥ 700kg
Ingress ProtectionIP20; third-party test report available
Cable ManagementBuilt-in fiber trough (capacity ≥48 cores) and 1U/2U cable managers for high-density cabling
Deployment ModeIndependent single cabinet deployment, support multi-cabinet cluster connection

6.6 Technical Parameters of PDU Power Distribution Unit

Parameter ItemBasic PDUIntelligent PDUHigh-Density PDU
Input Spec.16A/32A, 220V/380V32A, 220V/380V63A, 380V
Output Spec.8×10A C1316×10A C1324×16A C19
Intelligent Function—Power metering (±1% accuracy), remote monitoring, switch controlPower metering (±1% accuracy), remote monitoring, switch control
ProtectionOverload protection, lightning protection (≥2kV)Overload, lightning (≥2kV) & short circuit protectionOverload, lightning (≥2kV) & short circuit protection
Management—Web & mobile APP monitoringWeb & mobile APP monitoring
Installation19-inch standard, horizontal / vertical19-inch standard, horizontal / vertical19-inch standard, horizontal / vertical

6.7 Technical Parameters of Cabinet Accessories

Parameter ItemCable ManagerCooling FanDoor LockBlanking Panel
Spec.1U/2U, 19-inch standard120mm×120mm, 1U heightMoon handle, master key design1U/2U standard cabinet size
MaterialCold rolled steel, electrostatic powder coatingEngineering plastic + metal meshZinc alloy, chrome platedFlame-retardant ABS
PerformancePort capacity ≥24, compatible with Cat.6/Cat.6A/Cat.7Speed 2000rpm, air volume ≥300CFM, noise ≤45dBGood anti-theft performance, service life ≥10000 operationsVentilation rate ≤5%, optimize airflow
Installation19-inch standard, front / rearCabinet top / bottom, hot-swap supportedCabinet front / rear / side doorCabinet square hole bar, quick detachable

7. Application Scope

7.1 Data Center Industry

  1. Large Data Center: Adopt modular hot & cold aisle and intelligent liquid cooling cabinets for high-density deployment, lower PUE and improve operation efficiency.
  2. Cloud Computing Center: Intelligent all-in-one cabinets and modular design support rapid capacity expansion to meet elastic demands of cloud services.
  3. Edge Computing Node: Intelligent all-in-one cabinet with full integrated infrastructure for independent single cabinet deployment in edge environments.
  4. Supercomputing / AI Training Cluster: Intelligent liquid cooling cabinets solve heat dissipation of high-power equipment and support 30kW+ power density per cabinet.

7.2 Enterprise IT Industry

  1. Enterprise Computer Room: Standard server cabinets + network cabinets + PDU provide reliable physical bearing for enterprise IT equipment.
  2. Branch Office Computer Room: Intelligent all-in-one cabinets realize rapid deployment, lower O&M cost and centralized management.
  3. Finance / Medical Computer Room: High-reliability design and multi-protection mechanisms ensure stable operation of core services.
  4. Education & Research Institute Computer Room: Flexible configuration supports deployment of various IT equipment and meets scientific computing demands.

7.3 Special Industry

  1. Industrial Control Computer Room: High ingress protection grade for stable operation in harsh industrial environments.
  2. Outdoor Computer Room: IP54 rating, dustproof & waterproof, adapt to outdoor environment (-40℃ ~ +60℃).
  3. Military & Aerospace: High security design and optional electromagnetic shielding to guarantee data safety.
  4. Telecom Computer Room: Optimized cable management supports high-density network equipment deployment and improves communication efficiency.

8. Product Advantages

8.1 Intelligence & High Efficiency

  1. Intelligent Management: Real-time environmental monitoring, remote control and fault early warning improve O&M efficiency by over 30%.
  2. Energy Saving: Hot-cold aisle isolation reduces PUE below 1.2; intelligent liquid cooling further lowers PUE to 1.12 for eco-friendly operation.
  3. Resource Optimization: Intelligent PDU monitors power consumption in real time to optimize power distribution and cut energy use by 10-15%.

8.2 Safety & Reliability

  1. Multi-Protection: IP20/IP54 dustproof & waterproof; overload, short circuit and lightning protection ensure equipment safety.
  2. Stable Operation: Dual power input and UPS uninterrupted power supply avoid core service interruption.
  3. Wide Temperature Adaptation: Operate normally within -40℃ ~ +60℃ for diverse deployment environments.
  4. Anti-Theft Design: Moon handle cabinet lock with master key enhances physical security.

8.3 Flexible Expansion

  1. Modular Design: Standard modules support rapid deployment and expansion, cutting construction cycle by over 50%.
  2. Diversified Configuration: Support single cabinet, multi-cabinet cluster and modular expansion to meet demands of different scales.
  3. Strong Compatibility: Compatible with 19-inch standard IT equipment, support mixed deployment of new and old devices to protect existing investment.

8.4 Cost Advantages

  1. Lower Construction Cost: Factory prefabrication and on-site quick assembly reduce construction cost by over 30%.
  2. Lower O&M Cost: Intelligent remote management reduces on-site staff and cuts O&M cost by over 40%.
  3. Longer Service Life: Optimized operating environment reduces equipment failure rate and extends service life by over 20%.
  4. Higher Asset Utilization: High-density deployment improves computer room space utilization by over 50%.

8.5 Full Lifecycle Support

  1. Design Phase: Provide professional design consultation and customized solutions.
  2. Deployment Phase: Offer on-site installation guidance for fast and accurate deployment.
  3. O&M Phase: Remote monitoring and fault diagnosis with quick response.
  4. Upgrade Phase: Modular upgrade protects customer investment and adapts to technical development.

9. Bid Specification Parameters

9.1 General Bid Parameters

  1. Cabinet Body: Made of high-quality SPCC cold rolled steel; upright thickness ≥2.0mm, other parts ≥1.2mm. Surface treatment: degreasing, pickling, phosphating and electrostatic powder coating. Third-party test report required.
  2. Load Capacity: Static load of server cabinet ≥1500kg; static load of network cabinet ≥1000kg. Load test report required.
  3. Ingress Protection: ≥IP20; liquid cooling cabinet ≥IP54. Third-party IP test report required.
  4. Compatibility: Comply with ANSI/EIA RS-310-D, IEC 297-2, DIN41491 and other international standards, compatible with 19-inch standard IT equipment.
  5. Environmental Protection: Comply with RoHS directive; material recycling rate ≥90%. Environmental certification required.

9.2 Bid Parameters for Intelligent All-in-One Cabinet

  1. Integrated System: Must integrate power supply & distribution (UPS+PDU), cooling (precision air conditioner), monitoring (temperature/humidity/smoke/access control) and fire fighting (gas extinguishing) systems.
  2. Cooling Capacity: Integrated 12.5kW precision air conditioner with dual-side active air supply; PUE reduced by over 15%. Energy efficiency test report required.
  3. Power System: Support dual power input; UPS backup time ≥30 minutes; intelligent PDU with power metering and remote monitoring.
  4. Monitoring System: Monitor temperature & humidity (0-50℃ / 10-90%RH), smoke, access control and video; remote Web and mobile APP management supported.
  5. Fire Fighting System: Adopt HFC-227ea gas fire extinguishing with automatic detection and dual-mode activation. Fire certification required.

9.3 Bid Parameters for Modular Hot & Cold Aisle

  1. Sealing Performance: Complete hot-cold aisle isolation, air leakage rate ≤3%. Airflow organization test report required.
  2. Frame Material: Aluminum alloy with anodized treatment, corrosion resistance and service life ≥10 years.
  3. Enclosure Components: Tempered glass door thickness ≥5mm; flame-retardant thermal insulation top panel ≥20mm; blanking panel ventilation rate ≤5%.
  4. Lighting System: LED energy-saving lamp with power ≤10W and human body induction control. Energy-saving certification required.
  5. Access Control System: Support card / password / fingerprint recognition, remote authorization and access log recording.

9.4 Bid Parameters for Intelligent Liquid Cooling Cabinet

  1. Liquid Cooling System: Adopt cold plate liquid cooling technology; heat dissipation capacity ≥1500W/m², 5 times higher than air cooling. Heat dissipation performance test report required.
  2. CDU Unit: Temperature control accuracy ±1℃, pressure monitoring range 0-1MPa. Flow/temperature/pressure accuracy test report required.
  3. Leakage Detection: Multi-point sensors with detection accuracy ≤0.1ml and response time ≤1s. Leakage test report required.
  4. Pipeline System: Stainless steel material, quick connector, anti-leakage and hot-swap design. Pipeline test report required.
  5. Power System: Support 60kW power density; PDU input ≥63A. Power capacity test report required.

9.5 Bid Parameters for PDU Power Distribution Unit

  1. Input Spec.: Intelligent PDU input ≥32A; high-density PDU input ≥63A. Electrical safety test report required.
  2. Output Spec.: Intelligent PDU ≥16×10A C13; high-density PDU ≥24×16A C19.
  3. Intelligent Function: Intelligent / high-density PDU must have power metering (±1% accuracy), remote monitoring and switch control. Function test report required.
  4. Protection: Equipped with overload, lightning (≥2kV) and short circuit protection. Protection performance test report required.
  5. Management: Support Web and mobile APP monitoring. Management function test report required.

10. Product Solutions

10.1 Mini Computer Room Solution (1-3 Cabinets)

Application: Small branch offices, edge computing nodes, mini data centers

Solution:

  1. Adopt KITOZER intelligent all-in-one cabinet integrating power, cooling, monitoring and fire fighting.
  2. Deploy 1-3 sets of intelligent all-in-one cabinets for independent or parallel operation.
  3. Built-in intelligent monitoring system for remote management and fault early warning.
  4. Support rapid deployment; on-site installation time ≤ 1 day.

Core Advantages:

  • High integration, no professional computer room decoration needed; construction cost reduced by over 50%.
  • Intelligent management cuts on-site O&M demand and O&M cost by over 40%.
  • Independent operation adapts to edge environment and meets IT demands of branch offices.

10.2 Small & Medium-Sized Data Center Solution (10-30 Cabinets)

Application: Enterprise data centers, cloud computing centers, finance / medical computer rooms

Solution:

  1. Adopt KITOZER modular hot & cold aisle system for hot-cold airflow isolation and PUE reduction.
  2. Deploy server cabinets, network cabinets, PDU and accessories for high-density IT equipment deployment.
  3. Intelligent monitoring system for real-time environmental monitoring, remote control and fault early warning.
  4. Equip precision air conditioners for high-efficiency cooling to meet medium & high power density demands.
  5. Modular expansion available for business growth.

Core Advantages:

  • Hot-cold aisle isolation reduces PUE below 1.2 with remarkable energy-saving effect.
  • Modular design realizes rapid deployment and expansion; construction cycle shortened by over 60%.
  • Intelligent management improves O&M efficiency by over 30% and reduces O&M cost.

10.3 Large-Scale Data Center Solution (More than 50 Cabinets)

Application: Large data centers, supercomputing centers, AI training clusters

Solution:

  1. Combine KITOZER intelligent liquid cooling cabinets and modular hot & cold aisles to solve high-power heat dissipation.
  2. Deploy high-density server cabinets, network cabinets, high-density PDU and accessories to support 30kW+ power density per cabinet.
  3. Unified intelligent monitoring platform for overall data center management and intelligent scheduling.
  4. Equip CDU for centralized management and intelligent adjustment of coolant.
  5. Modular deployment by functional zones for rapid expansion.

Core Advantages:

  • Liquid cooling technology boosts heat dissipation efficiency 5 times and supports ultra-high power density deployment.
  • Unified intelligent platform realizes refined management and improves overall operation efficiency by over 50%.
  • Modular expansion adapts to rapid business growth and protects customer investment.

10.4 High-Density Computing Center Solution (AI / Supercomputing)

Application: AI training clusters, supercomputing centers, high-performance computing scenarios

Solution:

  1. Adopt KITOZER intelligent liquid cooling cabinets supporting 30kW+ power density per cabinet.
  2. Deploy cold plate liquid cooling system and CDU for high-efficiency heat dissipation.
  3. Equip high-density PDU to support 60kW power input for high-power equipment.
  4. Leakage detection system ensures safe operation of liquid cooling system.
  5. Integrated intelligent monitoring system for collaborative management of liquid cooling and IT equipment.

Core Advantages:

  • Powerful heat dissipation solves heat problems of high-power AI / supercomputing equipment.
  • PUE as low as 1.12 to realize green low-carbon operation.
  • Collaborative optimization of liquid cooling and IT equipment improves computing efficiency by over 20%.

11. Application Cases

11.1 Case 1: Cloud Computing Center of Internet Enterprise

Project Background: Build a 20-cabinet cloud computing center with rapid expansion capability for elastic cloud services.

Solution:

  1. Deploy KITOZER modular hot & cold aisle system for airflow isolation and PUE reduction.
  2. Equip 16 server cabinets + 4 network cabinets for high-density IT deployment.
  3. Intelligent monitoring system for real-time environmental monitoring, remote control and early warning.
  4. Intelligent PDU for power metering and remote management.

Effect:

  • PUE dropped from 1.8 to 1.2, saving over 300,000 RMB on electricity annually.
  • Deployment cycle shortened to 2 weeks, 50% faster than traditional schemes.
  • Intelligent management reduces on-site O&M staff and cuts O&M cost by 40%.
  • Modular design supports rapid expansion for business growth.

11.2 Case 2: Branch Computer Rooms of Financial Institution

Project Background: Build standardized computer rooms for 50 nationwide branches, requiring rapid deployment, unified management and high reliability.

Solution:

  1. Adopt KITOZER intelligent all-in-one cabinets with integrated power, cooling, monitoring and fire fighting.
  2. Deploy 1 set of intelligent all-in-one cabinet for each branch for independent operation.
  3. Central monitoring platform for unified management of 50 branch computer rooms.
  4. Dual power input + UPS to ensure stable core business operation.

Effect:

  • Single branch construction cost reduced by 60%, total investment saved over 2 million RMB.
  • 1 day deployment per branch; all 50 branches completed within 1 month.
  • Central remote management reduces on-site O&M demand by 80%.
  • High reliability reduces equipment failure rate by 50% and guarantees financial business stability.

11.3 Case 3: AI Training Cluster of Technology Company

Project Background: Build a 10-cabinet AI training cluster supporting 30kW+ power density to solve high-power heat dissipation.

Solution:

  1. Deploy KITOZER intelligent liquid cooling cabinets equipped with cold plate liquid cooling system and CDU.
  2. 10 sets of intelligent liquid cooling cabinets for 30kW+ power density deployment.
  3. Leakage detection system ensures safe liquid cooling operation.
  4. High-density PDU for 60kW power input.

Effect:

  • Heat dissipation efficiency increased 5 times, completely solving heat problems of AI training equipment.
  • PUE as low as 1.12, saving over 500,000 RMB on electricity annually.
  • Support 30kW+ power density per cabinet, computing density increased more than twice.
  • Collaborative monitoring of liquid cooling and IT equipment improves O&M efficiency by 30%.

12. Search Keywords, SEO & Tags

12.1 Search Keywords

KITOZER computer room cabinet, intelligent all-in-one cabinet, modular hot and cold aisle, intelligent liquid cooling cabinet, standard server cabinet, standard network cabinet, PDU power distribution unit, cabinet accessories, computer room cabinet solution, data center cabinet, modular data center, energy-saving cabinet, high-density cabinet, intelligent monitoring cabinet, liquid cooling data center

12.2 SEO Optimization Suggestions

  1. Title Optimization: Embed core keywords, e.g. “KITOZER Integrated Computer Room Cabinet Solution – Intelligent All-in-One Cabinet – Modular Hot & Cold Aisle – Liquid Cooling Cabinet”
  2. Meta Description: Briefly introduce core advantages of the solution with main keywords included.
  3. Content Optimization: Distribute keywords naturally with density 2-3%; use H1-H3 heading tags for key content.
  4. Image Optimization: Add Alt tags with core keywords, e.g. “Schematic of KITOZER Intelligent All-in-One Cabinet System”
  5. Link Optimization: Internal links to related product pages; external links to authoritative industry websites.
  6. Mobile Optimization: Responsive design compatible with mobile phones and tablets.

12.3 Tags

#KITOZER #ComputerRoomCabinet #IntelligentAllInOneCabinet #ModularHotColdAisle #IntelligentLiquidCoolingCabinet #ServerCabinet #NetworkCabinet #PDU #DataCenter #EnergySaving #HighDensityDeployment #IntelligentMonitoring #LiquidCoolingTechnology #ModularDataCenter #ComputerRoomSolution

Shopping Cart